STEP 3 −− INSTALLING INDOOR EXPANSION VALVE

This outdoor unit is designed for use in systems that include an expansion valve metering device. See the XC21 Product Specifications bulletin (EHB) for approved expansion valve kit match−ups and application information. The expansion valve can be installed internal or external to the indoor coil. In applications where an uncased coil is being installed in a field−pro- vided plenum, install the expansion valve in a manner that will provide access for future field service of the expansion valve. Refer to below illustration for reference during installation of expansion valve.

INDOOR EXPANSION VALVE INSTALLATION

TWO−PIECE

 

(Uncased Coil Shown)

 

PATCH PLATE

 

 

(UNCASED

 

 

 

STUB

 

COIL ONLY)

LIQUID LINE

 

END

 

 

 

ORIFICE

 

 

 

 

 

EXPANSION

 

 

 

HOUSING

 

DISTRIBUTOR

 

VALVE

 

 

 

 

 

TUBES

 

 

 

 

TEFLON®

 

 

 

 

 

 

 

 

 

 

RING

 

 

 

 

TEFLON®

SENSING

 

 

 

 

RING

 

 

 

 

LINE

 

 

 

 

 

DISTRIBUTOR

 

EQUALIZER

 

ASSEMBLY

 

 

LINE

 

 

 

 

 

LIQUID LINE

 

 

 

 

ASSEMBLY WITH

3.Install one of the provided Teflon® rings around the stubbed end of the expansion valve and use refrigerant

oil to lightly lubricate the connector threads and ex- posed surface of the Teflon® ring.

4.Attach the stubbed end of the expansion valve to the liquid line orifice housing. Finger tighten, then use an appropriately sized wrench to turn an additional 1/2 turn clockwise as illustrated in the figure to the right, or tighten to 20 ft−lb.

5.Place the remaining Teflon® washer around the other

end of the expansion valve. Lightly lubricate connector threads and expose surface of the Teflon® ring with refrigerant oil.

6.Attach the liquid line assembly to the expansion valve. Finger tighten, then use an appropriately sized wrench to turn an additional 1/2 turn clockwise as illustrated in the figure above or tighten to 20 ft−lb.

1/2 Turn

11 12

1

10

 

2

9

 

43

8 7

6

5

 

 

BRASS NUT

MALE EQUALIZER LINE

VAPOR

 

FITTING (SEE

 

LINE

 

EQUALIZER LINE

 

 

 

INSTALLATION FOR

 

 

DETAILS)

 

 

Sensing bulb insulation is required if

 

expansion valve is installed external to the

LIQUID LINE

coil casing. See sensing bulb installation for

 

bulb positioning.

 

 

SENSING BULB INSTALLATION

1.Attach the vapor line sensing bulb in the proper orienta- tion as illustrated below using the clamp and screws provided.

2.NOTE − Though it is preferred to have the sensing bulb installed on a horizontal run of the vapor line, installation on a vertical run of piping is acceptable if necessary.

NOTE

and expansion bulb before insulating the sensing bulb.

3.Connect the equalizer line from the expansion valve to the equalizer vapor port on the vapor line. Finger tighten the flare nut, then tighten an additional 1/8 turn (7 ft−lbs) as illustrated to the right.

 

1/8 Turn

 

11 12

1

10

 

2

9

 

 

43

8

7

6

5

EQUALIZER LINE INSTALLATION

1.Remove and discard either the flare seal cap or flare nut with copper flare seal bonnet from the equalizer line port on the vapor line as illustrated in the figure below.

2.Remove the field−provided fitting that temporarily reconnected the liquid line to the indoor unit’s distributor assembly.

VAPOR LINE

ON LINES SMALLER THAN

7/8", MOUNT SENSING

 

BULB AT EITHER THE 3 OR

 

9 O’CLOCK POSITION.

 

12

BULB

BULB

FLARE SEAL CAP

OR

FLARE NUT

VAPOR LINE

COPPER FLARE

 

 

SEAL BONNET

 

 

 

 

12

MALE BRASS EQUALIZER

 

 

LINE FITTING

BULB

BULB

 

 

 

VAPOR LINE

 

 

ON 7/8" AND LARGER LINES, MOUNT SENSING BULB AT EITHER THE 4 OR 8 O’CLOCK POSITION. NEVER MOUNT THE SENSING BULB ON BOTTOM OF LINE.

NOTE

BULB ON BOTTOM OF LINE.

FIGURE 9

Page 8

Image 8
Contents −− Setting the Unit −− Clearances General−− Setting the Unit −− Unit Placement Unit Dimensions − Inches MMAccess View Side ViewPlacement Stabilizing Unit on Uneven SurfacesSlab Mounting Refrigerant Line SETPressor Liquid Line Service Valve Stub END Distributor Tubes TWO−PIECE Patch PlateUncased Coil only Expansion−− Refrigerant Piping −− Brazing Procedures CAP and Core RemovalWrap Service Valves Flow NitrogenBraze Line SET 7PREPARATION for Next StepEqualizer Line Installation Indoor Expansion Valve InstallationSensing Bulb Installation −− Leak Test and Evacuation Lowhigh Manifold Gauge SET Outdoor Unit To Vapor−− Leak Test and Evacuation LOW HighSAE TEE with Swivel Coupler Minimum 3/8 Hose−− Electrical −− Circuit Sizing and Wire Routing Size Circuit and Install Disconnect 1SWITCH2INSTALL Thermostat 24VAC Transformer3A. Route Control Wires Ting Route Control Wires Ting4ROUTE High Voltage and Ground Wires Wiring Entry Points−− Electrical −− Outdoor Control A175 Jumpers and Terminals J3 ALL UnitsHP only J4 TWO−STAGE Heat Pump only J2−− Electrical −− Field Control Wiring Flat metal jumperOn−board link Start−Up Checklists ProcedureCharging TWO−STAGE Compressor PerformanceXC21 Field Operational Checklist Cooling Mode Heating ModeSTART−UP Checks SubcoolingHomeowner Information Outdoor Coil

Dave Lennox Signature Collection XC21 System, XC21 specifications

Lennox International Inc. has long been synonymous with innovative heating and cooling solutions. One of the standout products in their lineup is the Dave Lennox Signature Collection XC21 System, a central air conditioning unit renowned for its remarkable efficiency, advanced technology, and superior performance.

The XC21 features Lennox’s proprietary Signature Series components, ensuring that homeowners receive top-tier comfort with energy-saving capabilities. One of the main highlights of the XC21 is its impressive SEER (Seasonal Energy Efficiency Ratio) rating of up to 21. This high rating signifies exceptional energy efficiency, allowing homeowners to save significantly on energy bills while maintaining a comfortable indoor environment.

One of the key technologies incorporated into the XC21 is the variable-speed compressor. This feature enables the system to adjust its cooling output in response to the current temperature and humidity levels, providing optimal comfort without excessive energy consumption. The variable-speed operation allows for quieter performance, with sound levels as low as 65 decibels, making it one of the quietest systems available.

Furthermore, the XC21 is designed with the Advanced Energy Efficiency feature, which enhances its capability to regulate energy usage intelligently. This is complemented by the Smart Away feature, allowing the unit to enter energy-saving mode when the homeowner is away, ensuring that no energy is wasted during times of inactivity.

Additionally, the XC21 is built with durable and high-quality materials, including a galvanized steel cabinet that resists rust and corrosion, ensuring longevity and consistent performance in varied weather conditions. It also includes a unique design that allows for easier maintenance and serviceability, minimizing downtime and repair costs.

The XC21 system is compatible with the iComfort S30 smart thermostat, which offers advanced climate control capabilities through Wi-Fi connectivity. This feature allows users to manage their home’s heating and cooling system remotely, providing convenience and enhancing energy efficiency.

In summary, the Dave Lennox Signature Collection XC21 System exemplifies Lennox International Inc.’s commitment to cutting-edge technology, energy efficiency, and customer satisfaction. Its innovative features, high energy efficiency ratings, and user-friendly characteristics make it an excellent choice for homeowners looking to enhance their comfort while reducing energy expenses.