Raypak 302BD-2342BD For Your Safety, Pre Start-up Check, Initial Start-up, Tools Needed

Page 6

Propane Supply Pressure

Test Point

Gas Valve

Output Tap

Models: 302BD-902BD

 

Models: 992BD-

 

 

2342BD

Fig. 4: FlexGas Gas Pressure Measurement Locations

Start-up

For Your Safety

WARNING: If you do not follow these instructions exactly, a fire or explosion may result causing prop- erty damage, personal injury or loss of life.

This appliance has a hot surface igniter(s). It is equipped with an ignition device(s) which automatical- ly lights the burners. Do not try to light the burners by hand.

BEFORE OPERATING, smell all around the appli- ance area for gas. Be sure to smell near the floor because some gas is heavier than air and will settle on the floor.

WHAT TO DO IF YOU SMELL GAS:

Do not try to light any appliance.

Do not touch any electrical switch; do not use any telephone in your building.

Immediately call your gas supplier from a neigh- bor’s telephone. Follow the gas supplier’s instructions.

If you cannot reach your gas supplier, call the fire department.

Use only your hand to push in or turn the gas con- trol knob. Never use tools. If the knob will not turn by hand, do not try to repair it, call a qualified serv- ice technician. Forced or attempted repair may result in a fire or explosion.

Do not use this appliance if any part has been under water, immediately call a qualified service technician to inspect the appliance and to replace

any part of the control system and any gas control which has been under water.

Check around unit for debris and remove combus- tible products, i.e. gasoline, etc.

Pre Start-up Check

1.Verify heater is filled with water.

2.Check system piping for leaks. If found, repair immediately.

3.Vent air from system. Air in system can interfere with water circulation.

4.Purge air from gas lines up to FlexGas gas train.

Initial Start-up

Tools Needed:

(1) 12-0-12, 24” scale U-tube manometer

(4) 6-0-6, 12” scale U-tube manometers (min.)

(1) Screwdriver

(1) Multi-meter

(1) 3/16” Allen wrench

NOTE: Digital manometers are not recommended.

6

Image 6
Contents FlexGas Page Model Input Pipe Size Model IdentificationRatings and Certifications NatInstallation Codes Gas SupplyComponent Locations Gas Supply Pressure Bleeds/VentsPre Start-up Check For Your SafetyStart-up Initial Start-upAttach Manometers to Measure Pressures Preparation Check Power SupplyFlexGas System Start-up Check Gas Supply PressureFollow-Up Safety InspectionFlexGas Operation Changing Fuels From NAT to PROWiring Diagram Optional on 302BD-902BDPage Call OUT Description

302BD-2342BD specifications

The Raypak 302BD-2342BD is a standout in the realm of commercial water heating, designed to meet the needs of various applications while ensuring efficiency and reliability. Known for its robust construction and state-of-the-art technology, this model is a preferred choice for both residential and commercial users.

One of the key features of the Raypak 302BD-2342BD is its dual thermostat functionality. This feature allows for precise temperature control, making it suitable for diverse heating requirements. With a maximum output of 302,000 BTUs, this unit can handle large volumes of water, making it ideal for swimming pools, spas, and other high-demand situations.

The Raypak 302BD-2342BD is also equipped with a highly efficient heat exchanger. Constructed from copper, the heat exchanger provides superior thermal conductivity, allowing for faster heating and improved energy efficiency. This contributes to reduced operating costs, a crucial consideration for commercial applications where budget constraints are paramount.

Another notable characteristic of this model is its compact design. The unit is engineered for easy installation, taking up minimal space while still delivering powerful performance. This aspect is particularly advantageous in commercial settings where space can be a significant limiting factor.

Safety and user-friendly operation are prioritized in the design of the Raypak 302BD-2342BD. It features an integrated digital display, providing users with real-time information about the unit's performance and conditions. Furthermore, the model includes built-in diagnostic features, allowing for easy troubleshooting and maintenance.

The Raypak 302BD-2342BD also boasts advanced flame sensing technology, ensuring a secure and reliable ignition process. This feature enhances safety while promoting efficiency by optimizing combustion levels.

Lastly, the unit is compatible with various fuel types, including natural gas and propane. This versatility ensures that users can select the most suitable fuel source based on availability and cost considerations.

In summary, the Raypak 302BD-2342BD represents the pinnacle of modern water heating technology, boasting features such as dual thermostats, a high-efficiency heat exchanger, a compact design, and advanced safety measures. Its combination of power, efficiency, and versatility positions it as a leader in the market, meeting the heating needs of both residential and commercial users alike.