Johnson Controls 16 SEER - CZF Section Viii AC Control Board Functionality, LOW Voltage Detection

Page 12

562156-UIM-A-0610

NOTICE

On 5 Ton unit the outdoor fan motor is a permanent magnet DC brushless type. The motor requires a separate Electronic Control to operate. Do not attempt to replace this motor with a typical PSC type. Damage to Electronic Control may result.

3.If the coil needs to be cleaned, use clean water to wash dust, dirt, and debris from outdoor condensing coil.

5.The indoor coil and drain pan should be inspected and cleaned reg- ularly to prevent odors and assure proper drainage.

Do not connect manifold gauges unless trouble is suspected. Approximately 3/4 ounce of refrigerant will be lost each time a stan- dard manifold gauge is connected.

NOTICE

DO NOT use coil cleaners to clean outdoor condensing coil. clean- ers containing HF-, hydroxides, chlorides, and sulfates can greatly reduce the lifetime of the aluminum condensing coil.

4.Refer to the furnace or air handler instructions for filter and blower motor maintenance.

TABLE 1: R-410A Saturation Properties

IT IS UNLAWFUL TO KNOWINGLY VENT, RELEASE OR DIS- CHARGE REFRIGERANT INTO THE OPEN AIR DURING REPAIR, SERVICE, MAINTENANCE OR THE FINAL DISPOSAL OF THIS UNIT.

WHEN THE SYSTEM IS FUNCTIONING PROPERLY AND THE OWNER HAS BEEN FULLY INSTRUCTED, SECURE THE OWNER’S APPROVAL.

TEMP. °F

PRESSURE

TEMP. °F

PRESSURE

TEMP. °F

PRESSURE

TEMP. °F

PRESSURE

TEMP. °F

PRESSURE

PSIG

PSIG

PSIG

PSIG

PSIG

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

45

129.70

60

169.60

75

217.40

90

274.10

105

340.50

 

 

 

 

 

 

 

 

 

 

46

132.20

61

172.60

76

220.90

91

278.20

106

345.30

 

 

 

 

 

 

 

 

 

 

47

134.60

62

175.50

77

224.40

92

282.30

107

350.10

 

 

 

 

 

 

 

 

 

 

48

137.10

63

178.50

78

228.00

93

286.50

108

355.00

 

 

 

 

 

 

 

 

 

 

49

139.60

64

181.60

79

231.60

94

290.80

109

360.00

 

 

 

 

 

 

 

 

 

 

50

142.20

65

184.60

80

235.30

95

295.10

110

365.00

 

 

 

 

 

 

 

 

 

 

51

144.80

66

187.70

81

239.00

96

299.40

111

370.00

 

 

 

 

 

 

 

 

 

 

52

147.40

67

190.90

82

242.70

97

303.80

112

375.10

 

 

 

 

 

 

 

 

 

 

53

150.10

68

194.10

83

246.50

98

308.20

113

380.20

 

 

 

 

 

 

 

 

 

 

54

152.80

69

197.30

84

250.30

99

312.70

114

385.40

 

 

 

 

 

 

 

 

 

 

55

155.50

70

200.60

85

254.10

100

317.20

115

390.70

 

 

 

 

 

 

 

 

 

 

56

158.20

71

203.90

86

258.00

101

321.80

116

396.00

 

 

 

 

 

 

 

 

 

 

57

161.00

72

207.20

87

262.00

102

326.40

117

401.30

 

 

 

 

 

 

 

 

 

 

58

163.90

73

210.60

88

266.00

103

331.00

118

406.70

 

 

 

 

 

 

 

 

 

 

59

166.70

74

214.00

89

270.00

104

335.70

119

412.20

 

 

 

 

 

 

 

 

 

 

SECTION VIII: AC CONTROL BOARD FUNCTIONALITY

ANIT-SHORT CYCLE DELAY

The control includes a five-minute anti-short cycle delay (ASCD) timer to prevent the compressor from short cycling after a power interruption or thermostat signal interruption. The ASCD timer is applied when the control is first powered from the indoor unit thermostat and immediately following the completion of a compressor run cycle. The compressor and the outdoor fan will not operate during the five minutes that the timer is active.

The ASCD timer can be bypassed by connecting the TEST terminals for three seconds while the thermostat is calling for compressor opera- tion (Y1 input signal energized).

LOW VOLTAGE DETECTION

The control monitors the transformer secondary (24 VAC) voltage and provides low voltage protection for the AC unit and its components. In particular, the control prevents contactor chatter during low voltage con- ditions. If the voltage drops below approximately 19 VAC, the control will continue to energize any relays that are already energized but will not energize any additional relays until the voltage level increases. If the voltage drops below approximately 16 VAC, the control will immedi- ately de-energize the relay outputs and will not energize any relays until the voltage level increases. The control will store and display the appro- priate fault codes when low voltage conditions occur.

TEST INPUT

The control includes a TEST input connector that can be used for vari- ous testing functions during installation and service. Table 2 summa- rizes the behavior of the control when the two TEST pins are connected.

12

Johnson Controls Unitary Products

Image 12
Contents Installation Manual Section III Unit Installation ADD-ON REPLACEMENT/RETROFITInspection LimitationsGround Installation Roof InstallationUnit Placement TXV InstallationsPrecautions During Line Installation Precautions During Brazing of LinesPrecautions During Brazing Service Valve Section IV Evacuation Section V Electrical ConnectionsGeneral Information & Grounding Field Connections Power Wiring Field Connections Control Wiring ConventionalField Connections Control Wiring Serial Communication CFM Selection Board Settings Dehumidification Control+-++ ?,++ ?&&E 655 416C54 456 $FF9GB $8CF9 +GB Maintenance Section VI System ChargeSection VII Instructing the Owner Measurement MethodANIT-SHORT Cycle Delay Section Viii AC Control Board FunctionalityLOW Voltage Detection Test InputLED Diagnostic Indicators Operational Mode DetectionOperational Mode Display Status Code DisplayFault Code Display Sensor or Switch Fault CodesWiring Related Fault Codes Lockout ModesHIGH-PRESSURE Switch Fault LOW-PRESSURE Switch FaultOutdoor Ambient Temperature Sensor Cooling OperationSection IX Wiring Diagram Wiring Diagram 2 4 Ton Johnson Controls Unitary ProductsWiring Diagram 5 Ton Johnson Controls Unitary Products York Drive Norman, OK

AL6B SERIES, AC6B, 16 SEER - CZF specifications

The Johnson Controls AC6B, AL6B Series air conditioning units are designed to deliver efficient cooling solutions for residential and commercial applications. Known for their advanced technology and superior performance, these units comply with the latest standards in energy efficiency, boasting a 16 SEER (Seasonal Energy Efficiency Ratio) rating. This high rating indicates that these air conditioning systems consume less power while delivering optimum cooling, leading to significant cost savings on energy bills.

One of the standout features of the AC6B, AL6B Series is their variable-speed compressor technology. This allows the unit to adjust its cooling output in response to the specific demands of the environment, ensuring consistent temperatures while minimizing energy consumption. The variable-speed operation helps reduce wear and tear on the system, increasing longevity and reliability.

Another key characteristic of these units is their eco-friendly refrigerant, which contributes to lower environmental impact. The AC6B, AL6B Series utilize advanced heat exchanger designs that enhance heat transfer efficiency, further optimizing cooling performance while reducing energy usage.

Designed with user comfort in mind, these systems come equipped with advanced dehumidification capabilities, effectively managing indoor humidity levels. This ensures a more comfortable living or working environment, especially in humid climates.

In addition to performance, installation and maintenance are simplified with the AC6B, AL6B Series. The units are engineered for ease of installation, featuring lightweight components that reduce labor costs. Maintenance is also straightforward, with accessible service panels and clear maintenance guidelines, offering further convenience for homeowners and facility managers alike.

The aesthetic design of the AC6B, AL6B Series blends seamlessly into various architectural styles, making them an attractive choice for both new constructions and retrofits. The robust construction quality ensures durability, suitable for varying weather conditions.

Overall, the Johnson Controls AC6B, AL6B Series air conditioning units present a comprehensive solution for those seeking energy-efficient, reliable, and user-friendly cooling systems. With their multitude of features and advanced technology, they stand as a robust option for enhancing indoor comfort while minimizing environmental impact.