Johnson Controls 13 SEER Piping Connections, OIL Trapping, Precautions During Line Installation

Page 3

347337-UIM-A-0408

PIPING CONNECTIONS

The outdoor condensing unit must be connected to the indoor evapora- tor coil using field supplied refrigerant grade (ACR) copper tubing that is internally clean and dry. Units should be installed only with the tubing sizes for approved system combinations as specified in tabular data sheet. The charge given is applicable for total tubing lengths up to 15 feet. See Application Data Part Number 036-61920-000 for installing tubing of longer lengths and elevation differences.

NOTE: Using a larger than specified line size could result in oil return problems. Using too small a line will result in loss of capacity and other problems caused by insufficient refrigerant flow. Slope horizontal vapor lines at least 1" every 20 feet toward the out- door unit to facilitate proper oil return.

OIL TRAPPING

When the outdoor unit is above the indoor coil, oil trapping is necessary. An oil trap should be provided for every 20 ft. of rise. See Figure 2.

 

OUTDOOR COIL

 

10 In.

 

20 Ft.

INDOOR

6 In.

COIL

20 Ft.

FIGURE 2: Oil Trap

PRECAUTIONS DURING LINE INSTALLATION

1.Install the lines with as few bends as possible. Care must be taken not to damage the couplings or kink the tubing. Use clean hard drawn copper tubing where no appreciable amount of bending around obstruction is necessary. If soft copper must be used, care must be taken to avoid sharp bends which may cause a restriction.

2.The lines should be installed so that they will not obstruct service access to the coil, air handling system, or filter.

3.Care must also be taken to isolate the refrigerant lines to minimize noise transmission from the equipment to the structure.

4.The vapor line must be insulated with a minimum of 1/2" foam rub- ber insulation (Armaflex or equivalent). Liquid lines that will be exposed to direct sunlight, high temperatures, or excessive humid- ity must also be insulated.

5.Tape and suspend the refrigerant lines as shown. DO NOT allow tube metal-to-metal contact. See Figure 3.

6.Use PVC piping as a conduit for all underground installations as shown in Figure 4. Buried lines should be kept as short as possible to minimize the build up of liquid refrigerant in the vapor line during long periods of shutdown

7.Pack fiberglass insulation and a sealing material such as perma- gum around refrigerant lines where they penetrate a wall to reduce vibration and to retain some flexibility.

8.For systems with total line length exceeding 50 ft., see APPLICA- TION DATA and worksheet "General Piping Recommendations and Refrigerant Line Length" for vapor and liquid line sizing, cali- bration of liquid line pressure loss or gain, determination of vapor line velocity, elevation limitations, orifice connections, system charging, traps, etc.

Sheet Metal Hanger

Liquid

Line

Incorrect

Tape

Correct

Insulated Vapor Line

FIGURE 3: Installation of Vapor Line

TO INDOOR COIL

 

TO OUTDOOR UNIT

Liquid Line

Insulated

 

 

Cap

 

Vapor Line

 

 

PVC

 

 

Conduit

 

 

FIGURE 4: Underground Installation

PRECAUTIONS DURING BRAZING OF LINES

All outdoor unit and evaporator coil connections are copper-to-copper and should be brazed with a phosphorous-copper alloy material such as Silfos-5 or equivalent. DO NOT use soft solder. The outdoor units have reusable service valves on both the liquid and vapor connections. The total system refrigerant charge is retained within the outdoor unit during shipping and installation. The reusable service valves are pro- vided to evacuate and charge per this instruction.

Serious service problems can be avoided by taking adequate precau- tions to assure an internally clean and dry system.

Dry nitrogen should always be supplied through the tubing while it is being brazed, because the temperature required is high enough to cause oxidation of the copper unless an inert atmosphere is pro- vided. The flow of dry nitrogen should continue until the joint has cooled. Always use a pressure regulator and safety valve to insure that only low pressure dry nitrogen is introduced into the tubing. Only a small flow is necessary to displace air and prevent oxidation.

PRECAUTIONS DURING BRAZING SERVICE VALVE

Precautions should be taken to prevent heat damage to service valve by wrapping a wet rag around it as shown in Figure 5. Also, protect all painted surfaces, insulation, and plastic base during brazing. After braz- ing, cool joint with wet rag.

This is not a backseating valve. The service access port has a valve core. Opening or closing valve does not close service access port.

If the valve stem is backed out past the chamfered retaining wall, the O-ring can be damaged causing leakage or system pressure could force the valve stem out of the valve body possibly causing personal injury.

Valve can be opened by removing the plunger cap and fully inserting a hex wrench into the stem and backing out counter-clockwise until valve stem just touches the chamfered retaining wall.

Johnson Controls Unitary Products

3

Image 3
Contents List of Tables Section II SafetyList of Sections List of FiguresSection III Unit Installation Piping Connections Precautions During Line InstallationPrecautions During Brazing of Lines Precautions During Brazing Service ValveTions During Brazing Service Valve Section IV Orifice InstallationSubcooling Charging Method Mixed Match Coils Section V Installations Requiring AN ADD-ON TXV KITSection VI Evacuation Section VII System ChargeGeneral Information & Grounding Field Connections Power WiringField Connections Control Wiring Section Viii Electrical ConnectionsAIR Handler AIR Conditioner AC 1AID Models Thermostat PSC Single StageAIR Handler Conditioner AC 1BThermostat AIRPSC AIR Furnace Conditioner AC 5DAC 5E PSC AIRFurnace Conditioner Cooling Indications of Proper OperationJohnson Controls Unitary Products York Drive Norman, OK

13 SEER specifications

Johnson Controls has long been a leader in the HVAC industry, renowned for its commitment to energy efficiency and innovative technology. One of its prominent offerings is the 13 SEER air conditioning unit, which stands for Seasonal Energy Efficiency Ratio. This rating signifies a balance between initial cost and ongoing energy savings, making it an ideal choice for a range of residential and commercial applications.

The 13 SEER unit boasts several key features that set it apart from other air conditioning systems. Firstly, its robust design incorporates high-quality materials, ensuring durability and longevity. This unit is built to withstand various environmental conditions, making it a reliable option for any climate.

One of the standout technologies within the 13 SEER unit is its advanced scroll compressor. This component increases efficiency by minimizing energy consumption while maximizing cooling output. By operating quietly and smoothly, the scroll compressor contributes to a more comfortable indoor environment without the disruptive sounds often associated with traditional AC units.

Additionally, Johnson Controls has equipped the 13 SEER system with environmentally friendly refrigerants, aligning with modern standards for sustainability and reduced environmental impact. This eco-conscious approach ensures that the unit not only performs efficiently but also meets regulatory guidelines for emissions.

Ease of installation and maintenance is another significant advantage. The 13 SEER system is designed with user-friendliness in mind, allowing for straightforward setup, which can save on initial installation costs. Maintenance practices have also been simplified, with features such as easy access panels and diagnostic capabilities that help technicians identify and resolve issues quickly.

In terms of characteristics, the 13 SEER unit often comes equipped with a range of customizable options, including variable speed blower fans and smart connectivity features. These enhancements allow homeowners to optimize their cooling experience based on their individual preferences, promoting energy savings while ensuring comfort during the warmer months.

Overall, Johnson Controls' 13 SEER air conditioning unit provides an exceptional blend of efficiency, reliability, and innovative technology. With its eco-friendly refrigerants, advanced scroll compressor, and commitment to user-friendly design, this unit offers an optimal cooling solution for those seeking energy-efficient options in today’s environmentally conscious landscape. Whether for residential or commercial use, the 13 SEER air conditioning unit stands as a testament to Johnson Controls' dedication to excellence in the HVAC market.