Before you call for service… | ge.com |
Troubleshooting Tips
Save time and money! Review the chart below first and you may not need to call for service.
Problem |
| Possible Causes | What To Do |
|
|
|
|
Air conditioner |
| The air conditioner | • Make sure the air conditioner plug is pushed completely |
does not start |
| is unplugged | into the outlet. |
|
|
|
|
|
| The fuse is blown/circuit | • Check the house fuse/circuit breaker box and replace |
|
| breaker is tripped | the fuse or reset the breaker. |
|
|
|
|
|
| Power failure | • The unit will automatically |
|
|
| used after the power is restored. |
|
|
| • There is a protective time delay (approximately |
|
|
| 3 minutes) to prevent tripping of the compressor |
|
|
| overload. For this reason, the unit may not start |
|
|
| normal cooling or heating for 3 minutes after it |
|
|
| is turned back on. |
|
|
|
|
|
| The current interrupter | • Press the RESET button located on the power cord plug. |
|
| device is tripped | • If the RESET button will not stay engaged, discontinue |
|
|
| use of the air conditioner and contact a qualified service |
|
|
| technician. |
|
|
|
|
Air conditioner |
| Ice blocks the air flow | • Set the mode control at FAN or HIGH COOL with the |
freezing up |
| and stops the air conditioner | temp control at a warmer setting. |
|
| from cooling the room |
|
|
|
|
|
Air conditioner does not |
| Airflow is restricted | • Make sure there are no curtains, blinds or furniture |
cool as it should |
|
| blocking the front of the air conditioner. |
|
|
|
|
|
| The temp control may | • Turn the temperature knob clockwise as far as possible. |
|
| not be set correctly |
|
|
|
|
|
|
| The air filter is dirty | • Clean the filter at least every 30 days. See the Operating |
|
|
| Instructions section. |
|
|
|
|
|
| The room may have been hot | • When the air conditioner is first turned on you need |
|
|
| to allow time for the room to cool down. |
|
|
|
|
|
| Cold air is escaping | • Check for open furnace floor registers and |
|
|
| cold air returns. |
|
|
| • Set the air conditioner’s vent to the closed position. |
|
|
|
|
|
| Cooling coils have iced up | • See “Air conditioner freezing up” below. |
|
|
|
|
Air conditioner does not |
| Airflow is restricted | • Make sure there are no curtains, blinds or furniture |
warm as it should |
|
| blocking the front of the air conditioner. |
|
|
|
|
|
| The temp control may | • Turn the knob counterclockwise as far as possible. |
|
| not be set low enough | The lowest setting provides maximum warming. |
|
|
|
|
|
| The air filter is dirty | • Clean the filter at least every 30 days. See the Operating |
|
|
| Instructions section. |
|
|
|
|
|
| The room may have been cold | • When the air conditioner is first turned on, you need to |
|
|
| allow time for the room to warm up. |
|
|
|
|
|
| Warm air is escaping | • Check for open furnace floor registers and |
|
|
| cold air returns. |
|
|
|
|
13
Safety Instructions Operating Instructions Installation Instructions Troubleshooting Tips Consumer Support