Stovax Stockton Log Effect Stove Range manual Flame Failure Functional Check, No Spark

Page 21

FLAME FAILURE FUNCTIONAL CHECK 3

PILOT WILL NOT STAY LIT OR FIRE GOES OUT IN USE

Ensure there is no debris around the pilot assembly, (e.g. coal, soot

etc.) which could short the spark, clear the area.

Light the pilot and keep the control knob pushed in at least 10

seconds before letting go.

IGNITION FUNCTIONAL CHECK 2

NO SPARK

Ensure there is no debris around the pilot assembly, (e.g. coal, soot

etc.) which could short the spark, clear the area.

From Ignition Fault Finding

 

Consult the Users Instructions,

Chart Part 1.

 

retry.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

21

 

 

 

NO

 

 

 

 

YES

With the fire

 

 

 

 

With the pilot

Will the pilot stay

 

 

 

 

 

 

 

 

lit?

 

 

 

 

running on full, is

 

 

 

 

running, is the gas

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

the gas at the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

pressure stated on

NO

 

 

 

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Problem is with the

pressure stated on

 

 

 

 

the databadge?

 

 

 

pipework or fittings

 

 

 

 

the databadge?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

which lead to the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

fire. Correct and

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

retry.

 

 

 

 

Run for no more

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

than 60 seconds,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

turn off, time

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Is the pilot flame of

 

 

 

Is thermocouple

NO

interval until mag

 

 

 

 

the correct length?

 

 

 

 

 

 

 

 

 

 

connection good in

 

 

 

 

unit shuts with a

 

 

 

 

See diagram 1 on

 

 

 

 

 

 

 

 

 

 

 

 

 

 

back of valve?

 

 

 

 

click. Is this greater

 

 

 

 

page

19.

 

 

 

 

 

 

 

 

 

 

 

than 7 seconds?

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Replace the

 

 

 

 

Tighten the

 

 

 

 

NO

 

 

 

 

 

 

 

 

connection and

 

 

 

 

 

 

 

 

thermocouple.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

retry.

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Run for 60 seconds,

 

 

 

 

Change the pilot

 

 

 

Will pilot stay alight?

 

 

 

 

turn off, time

 

 

 

 

unit.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

interval until mag

 

 

 

 

 

 

 

 

 

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

unit shuts with a

 

 

 

 

 

 

 

 

 

 

 

 

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

click. Is this greater

 

 

 

 

 

 

 

 

 

Change mag unit.

 

 

 

 

than 7 seconds?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SYSTEM OK

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Operate the valve to light the pilot, does the valve ‘click’?

 

 

 

YES

 

 

 

 

 

 

Is the pilot burner horizontal?

 

 

See diagram 1 on page 20.

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

Has ignition lead become

 

 

detached or is connection

 

 

poor?

 

 

 

 

 

 

 

NO

 

 

 

 

 

 

Remove the electrode lead

YES

from electrode with insulated

 

 

pliers. Hold the tip 4mm from

 

 

 

 

the pilot pipework, is there a

 

 

spark when the valve ‘clicks’?

 

 

 

 

 

 

 

NO

 

 

 

 

 

 

Is the electrode wire detached

 

 

from the piezo in the valve?

 

 

 

 

 

 

 

NO

 

 

 

 

 

 

 

 

 

Replace the combined lead,

 

 

retry.

 

 

 

 

 

 

 

 

 

 

Replace the pilot unit.

 

 

 

 

 

 

NO

NO

YES

YES

Is the valve being operated

YES

properly?

 

Reset the electrode gap, retry.

 

Correct and retry.

 

Check the defective or

 

damaged control knob spindle

 

or cam operation. Check for

 

correct location of piezo

 

components. Correct and

 

retry.

 

Remove the electrode lead from the piezo. Operate the valve. Does a spark jump from the piezo to the valve body?

YES

Replace the electrode lead

and retry.

Image 21
Contents Marlborough & Stockton Log Effect Stove Range PR0846 Issue 2 FebruaryContents Appliance Commissioning Checklist Flue Check Pass FailGAS Check General User InstructionsLighting the Stove Turning OFF the StoveCleaning the Fire Handling & Disposal of Fire CeramicsFuel BED Arrangements Never Operate the Stove When the Door is Removed Flame Failure Device Installation Details‘RUNNING IN’ ServicingTechnical Specification Installation InstructionsSite Requirements Flue and Chimney RequirementsTimber Framed Buildings Guard Supplied TOP ExitALL Appliances TOP Flue UP & OUT with Additional BendOptional Extra Flue Lengths & Bends Nominal Actual Stainless AnthraciteVentilation Installation of the GAS SupplyAppliance Location Minimum ClearanceControl Upgrade InstallationSafety Precautions Installation of the StoveDo not FIX the Flue AT this Stage Vertical & Horizontal Flue Table a TOP Exit Flue Vertical and Horizontal RestrictorsVertical Flue Height Horizontal Length Restrictor Size TOP Exit Vertical Flue Table a TOP Exit Vertical only Including OffsetVertical Height Restrictor Size Fuelbed Arrangements Lighting Commissioning CommissioningServicing Instructions Servicing / Fault Finding ChartsServicing Requirements Ignition Functional CheckFlame Failure Functional Check Pilot will not Stay LIT or Fire Goes OUT in USENo Spark Replacing Parts Main BurnerPilot Unit Ignition Lead Piezo Magnetic Safety ValveGAS Valve Main InjectorPrimary Aeration Plate Changing Between GAS TypesShort Spares List Service Records Member of the Stovax Group

Stockton Log Effect Stove Range specifications

The Stovax Stockton Log Effect Stove Range is a celebrated collection that brings the warmth and ambiance of a traditional log fire into modern homes. Known for its innovative design and high efficiency, this range offers a perfect blend of style and practicality, making it a popular choice among homeowners and interior designers alike.

One of the standout features of the Stockton Log Effect Stove Range is its realistic log effect fuel bed, which creates an inviting and cozy atmosphere. This clever design simulates the look of real logs burning, providing a comforting focal point within any room. The stove is available in various sizes, ensuring that there's a model to fit any space, whether large or small.

The efficacy of the Stockton stoves is further enhanced by advanced technology that promotes efficient heat output. Many models within the range come equipped with a multi-fuel capability, allowing users to choose between burning logs, smokeless fuel, or even coal, depending on availability and preference. This versatility not only maximizes the stove's usability but also reduces reliance on one type of fuel, catering to different heating needs throughout the year.

Another attractive characteristic of the Stovax Stockton Log Effect Stove is its high efficiency rating, which ensures that more heat is extracted from the fuel while minimizing emissions. The inclusion of a clean burn technology helps to burn off gases and particles before they enter the flue, leading to a cleaner, more environmentally friendly burn. This feature not only benefits the environment but also contributes to a more efficient heating source that saves energy costs.

The aesthetic appeal of the Stockton range is further enhanced by its sleek and contemporary design. Available in a variety of finishes and colors, including traditional black and modern gray, these stoves can seamlessly blend into both traditional and contemporary interiors.

Safety is also a priority within the design of these stoves. Many models feature built-in safety measures such as a secure door mechanism and effective air controls, ensuring that users can operate the stove easily and safely.

In conclusion, the Stovax Stockton Log Effect Stove Range combines traditional design elements with modern technology and versatility. It stands out for its realistic log effect, efficiency, and safety features, making it an ideal choice for anyone looking to enhance their living space with both warmth and style.