NEC RIH-6867 user manual How to Purge Air Tubes

Page 24

Installation instructions

How to Purge Air Tubes:

(1). Unscrew and remove caps from 2 and 3-way valves.

(2). Unscrew and remove cap from service valve.

(3). Connect vacuum pump flexible hose to the service valve.

(4). Start vacuum pump for 10-15 minutes until reaching a vacuum of 10 mm Hg absolutes.

(5). With vacuum pump still running close the low pressure knob on vacuum pump manifold. Then stop vacuum pump.

(6). Open 2-way valve 1/4 turn then close it after 10 seconds. Check tightness of all joints using liquid soap or an electronic leak detector.

(7). Turn 2 and 3-way valves stem to fully the valves. Disconnect vacuum pump flexible hose.

(8). Replace and tighten all valve caps.

Notes

Please read this manual before installing and using it.

Do not let air enter the refrigeration system or discharge refrigerant when moving the air conditioner.

Testing run the air conditioner after finishing installation, and record details of operation. Type of fuse used on indoor unit controller is 50T, with rating 3.15A,AC250V. .

The fuse for the whole unit is to be provided by the user according to the current at maximum power Input or use other over-current protective device instead.

Only the air conditioner can be connected to the power line.

The power connection for the air conditioner has to be done at the main power distribution which has to be of a low impedance.

In order to ensure the suitability of the equipment for connection, the user should consult with the supply authority, if necessary, that the service current capacity at the interface point is sufficient for the equipment.

Refer to the rating plate of the equipment for power consumption details.

If the supply cord is damaged, it must be replaced by the manufacturer or its service agent or similarly qualified person in order to avoid a hazard.

22

PDF created with pdfFactory Pro trial version www.pdffactory.com

Image 24
Contents Inverter Split room air conditioner Use and Care Manual Auto Restart Presetting Preparation before useSafety precautions Identification of parts Indoor unit Outdoor unitUH series operating and Display Timer Indicator Compressor indicator Temperature display Sleep IndicatorRemote controller Remote controllerIndication symbols on LCD How to Insert the Batteries Storage and Tips for Using the Remote ControllerHow to Use Choose Cooling Only Remote controller or Heat PumpOperation instructions Operation modesAirflow direction control Airflow direction controlSmart mode Your feeling Button Adjustment procedure Slightly warmerSlightly cooler Timer mode Timer-settingSleep mode Super modeMaintenance Cut off the power supplyClean and reinstall the air filter Close the front panel againProtection Protective device will work at following casesTroubleshooting Trouble AnalysisInstallation instructions Installation diagramLocation for Installing Indoor Unit Location for Installing Outdoor UnitIndoor unit installation Installing the Mounting PlateIndoor Unit Piping Installation Drill a Hole for PipingPiping Thermal Insulation Piping ConnectionModel Pipe size Torque Nut width Min.thickness Connecting of the Cable Indoor Unit Outdoor UnitIndoor unit Outdoor unit installation Air purgingVacuum pump How to Purge Air Tubes ABN 86 001 217

RIH-6867 specifications

The NEC RIH-6867 is a cutting-edge, high-performance server designed to meet the demands of modern data centers. Its robust architecture and advanced technologies make it suitable for a wide range of applications, from cloud computing to enterprise resource planning.

One of the standout features of the RIH-6867 is its impressive processing power. The server is powered by the latest generation of Intel Xeon processors, allowing it to handle multiple workloads simultaneously. This multi-core architecture enhances performance in virtualized environments, ensuring that businesses can run resource-intensive applications without encountering bottlenecks.

Memory capacity is another key aspect of the RIH-6867. The server supports large volumes of RAM, enabling it to perform high-speed data processing and rapid information retrieval. This capability is particularly beneficial in scenarios that require real-time data analytics and high throughput. Additionally, the use of error-correcting code (ECC) memory ensures data integrity and reliability, which are crucial for mission-critical applications.

The NEC RIH-6867 also excels in storage options. It offers various configurations, including support for both HDD and SSD drives. This flexibility allows organizations to choose the storage solution that best fits their needs, balancing speed and capacity. Furthermore, integrated RAID support enhances data protection, providing redundancy and improving fault tolerance.

Networking capabilities are robust in the RIH-6867. The server features multiple Ethernet ports, supporting high-speed networking for seamless data transfers. This ensures that the server can efficiently communicate with other devices within the data center, contributing to overall operational efficiency.

Power efficiency is a significant consideration in the design of the RIH-6867. The server is equipped with advanced power management technologies that optimize energy consumption, which can lead to reduced operational costs over time. This aspect is particularly appealing for organizations focused on sustainability and minimizing their carbon footprint.

In addition, the NEC RIH-6867 is designed with maintainability in mind. Hot-swappable components and modular design facilitate easy upgrades and repairs, minimizing downtime and keeping maintenance costs low.

In summary, the NEC RIH-6867 integrates high-performance processing, extensive memory capacity, flexible storage solutions, and efficient networking capabilities. Its focus on energy efficiency and maintainability positions it as a premier choice for enterprises looking to enhance their IT infrastructure.