HP90 Surface HDB2SLW154 or 254
Page 2 of 2
Direct/Indirect Surface Mounted Fluorescent 2' x 4' with Acrylic Linear Prismatic Lens, 1 or 2 Lamp T5
Model No. HDB2SLW154UNVPG
LER = FP - 60.5 IW - 60.8 BF - 1.0 Comparative yearly lighting energy cost per
1000 lumens = $3.97
Report Number: G2008213A
Catalog Number: HDB2SLW154UNVPG
Lamps: (1) F54 T5 HO
Luminaire: HP90 Surface 2' x 4' with linear prismatic lens.
Ballast: QT1X54/120PHO
Report is based on 4400 Lumens per lamp. Efficiency: 83.6%
CIE |
|
|
|
| |||||
Plane: |
|
|
|
|
| ||||
Spacing Criteria: |
|
| 1.2 |
|
| 1.4 | |||
Shielding Angles: |
|
| 90 |
|
| 90 | |||
Plane: |
|
|
|
|
| ||||
Luminous Length: |
| 47.880 |
| 23.040 | |||||
Height of Side: |
|
| 2.280 |
| 2.280 | ||||
COEFFICIENTS OF UTILIZATION – |
|
| |||||||
ZONAL CAVITY METHOD. EFFECTIVE |
| ||||||||
FLOOR CAVITY REFLECTANCE 0.200 |
| ||||||||
RC |
| 80 |
|
| 50 |
|
| 30 |
|
RW | 70 | 50 | 30 | 50 | 30 | 10 | 50 | 30 | 10 |
01 | 88 | 83 | 79 | 78 | 74 | 71 | 74 | 71 | 69 |
02 | 79 | 71 | 65 | 67 | 61 | 57 | 64 | 59 | 55 |
03 | 72 | 62 | 54 | 58 | 52 | 47 | 56 | 50 | 46 |
04 | 66 | 54 | 46 | 51 | 44 | 39 | 49 | 43 | 39 |
05 | 60 | 48 | 40 | 46 | 39 | 34 | 44 | 38 | 33 |
06 | 55 | 43 | 35 | 41 | 34 | 29 | 40 | 34 | 29 |
07 | 51 | 39 | 31 | 37 | 31 | 26 | 36 | 30 | 25 |
08 | 48 | 36 | 28 | 34 | 28 | 23 | 33 | 27 | 23 |
09 | 45 | 33 | 26 | 31 | 25 | 21 | 30 | 25 | 20 |
10 | 42 | 30 | 23 | 29 | 23 | 19 | 28 | 22 | 18 |
CANDELA DISTRIBUTION
| 0.0 | 45.0 | 90.0 | FLUX |
0 | 1053 | 1053 | 1053 |
|
5 | 1046 | 1047 | 1051 | 100 |
15 | 997 | 1015 | 1033 | 287 |
25 | 906 | 955 | 996 | 440 |
35 | 781 | 868 | 937 | 541 |
45 | 626 | 760 | 864 | 581 |
55 | 452 | 641 | 777 | 562 |
65 | 272 | 516 | 677 | 492 |
75 | 121 | 392 | 568 | 391 |
85 | 26 | 282 | 469 | 284 |
90 | 5 | 179 | 338 |
|
|
|
|
|
|
ZONAL LUMEN SUMMARY
ZONE | LUMENS | % LAMP | % FIXT |
827 | 18.8 | 22.5 | |
1368 | 31.1 | 37.2 | |
2511 | 57.1 | 68.3 | |
3678 | 83.6 | 100.0 | |
0000 | 0.0 | 000.0 | |
3678 | 83.6 | 100.0 |
LUMINANCE DATA IN CANDELA/SQ. METER
AVERAGE AVERAGE AVERAGE AVERAGE
IN DEG. | |||
45 | 1187. | 1407. | 1562. |
55 | 1036. | 1421. | 1667. |
65 | 820. | 1482. | 1856. |
75 | 558. | 1670. | 2251. |
85 | 271. | 2473. | 3547. |
Model No. HDB2SLW254UNVPG
LER = FP - 65.9 IW - 101.8 BF - 1.02 Comparative yearly lighting energy cost per
1000 lumens = $3.64
Report Number: G2008216A
Catalog Number: HDB2SLW254UNVPG
Lamps: (2) F54 T5 HO
Luminaire: HP90 Surface 2' x 4' with linear prismatic lens.
Ballast:
Report is based on 4400 Lumens per lamp. Efficiency: 74.8%
CIE |
|
|
|
| |||||
Plane: |
|
|
|
|
| ||||
Spacing Criteria: |
|
| 1.2 |
|
| 1.4 | |||
Shielding Angles: |
|
| 90 |
|
| 90 | |||
Plane: |
|
|
|
|
| ||||
Luminous Length: |
| 47.880 |
| 23.040 | |||||
Height of Side: |
|
| 2.280 |
| 2.280 | ||||
COEFFICIENTS OF UTILIZATION – |
|
| |||||||
ZONAL CAVITY METHOD. EFFECTIVE |
| ||||||||
FLOOR CAVITY REFLECTANCE 0.200 |
| ||||||||
RC |
| 80 |
|
| 50 |
|
| 30 |
|
RW | 70 | 50 | 30 | 50 | 30 | 10 | 50 | 30 | 10 |
01 | 79 | 75 | 71 | 70 | 67 | 64 | 67 | 64 | 62 |
02 | 71 | 64 | 58 | 60 | 55 | 51 | 57 | 53 | 50 |
03 | 64 | 56 | 49 | 52 | 46 | 42 | 50 | 45 | 41 |
04 | 59 | 49 | 42 | 46 | 40 | 35 | 44 | 39 | 35 |
05 | 54 | 43 | 36 | 41 | 35 | 30 | 39 | 34 | 30 |
06 | 50 | 39 | 32 | 37 | 31 | 26 | 36 | 30 | 26 |
07 | 46 | 35 | 28 | 33 | 27 | 23 | 32 | 27 | 23 |
08 | 43 | 32 | 25 | 31 | 25 | 21 | 30 | 24 | 20 |
09 | 40 | 29 | 23 | 28 | 22 | 18 | 27 | 22 | 18 |
10 | 37 | 27 | 21 | 26 | 20 | 17 | 25 | 20 | 17 |
CANDELA DISTRIBUTION0
| 0.0 | 45.0 | 90.0 | FLUX |
0 | 1891 | 1891 | 1891 |
|
5 | 1879 | 1881 | 1888 | 179 |
15 | 1794 | 1825 | 1852 | 516 |
25 | 1635 | 1713 | 1779 | 789 |
35 | 1410 | 1556 | 1679 | 972 |
45 | 1135 | 1367 | 1553 | 1047 |
55 | 822 | 1155 | 1397 | 1014 |
65 | 502 | 928 | 1204 | 885 |
75 | 230 | 699 | 992 | 695 |
85 | 50 | 494 | 782 | 486 |
90 | 9 | 302 | 547 |
|
ZONAL LUMEN SUMMARY
ZONE | LUMENS | % LAMP | % FIXT |
1484 | 16.9 | 22.5 | |
2456 | 27.9 | 37.3 | |
4517 | 51.3 | 68.6 | |
6583 | 74.8 | 100.0 | |
0000 | 00.0 | 000.0 | |
6583 | 74.8 | 100.0 |
LUMINANCE DATA IN CANDELA/SQ. METER
AVERAGE AVERAGE AVERAGE AVERAGE IN DEG.
45 2152. 2530. 2807.
55 1885. 2560. 2997.
65 1514. 2665. 3301.
75 1060. 2979. 3931.
85 522. 4332. 5914.
Ordering Information
Explanation of Catalog Number. Example: HDB2SLW254UNVPG
HD
B
2
S
L
W
54
UNV
|
|
|
|
|
|
|
| Reflector: | Lamp |
|
|
|
|
|
|
|
|
|
HP90 | Body Style: | Fixture | Ceiling |
| Type: | Acrylic Lens |
|
|
|
|
|
|
|
|
| |||
| Lamp: | Voltage: |
|
| Options: | |||||||||||||
Direct/Indirect | B = Surface | Width | Surface |
| White | Quantity | (By Others) |
|
| Add appropriate | ||||||||
Surface | Mounted |
|
|
|
|
|
|
| 1=1 Lamp | 54=T5 54W |
|
|
|
| suffix to catalog | |||
|
|
|
|
|
|
|
|
| 2=2 Lamp | (Nominal 48") |
|
|
|
| no., ie: (A) | |||
|
|
|
|
|
|
|
|
|
|
|
|
|
| Ballast Type: |
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| <20THD <10THD | ||
|
|
|
|
|
|
|
|
|
|
|
|
| 1 Lamp Elec. T5 HO | – | PG †† | |||
|
|
|
|
|
|
|
|
|
|
|
|
| (54 Watt) |
|
|
|
Options/Accessories
Fusing: Internal fast blow fusing: SUFFIX: A.
Internal slow blow fusing: SUFFIX: C.
Electrical Wiring Options: Consult factory.
For motion or light sensor: See Folio
Specifications
Performance: In an installation of 2 lamp 54W luminaires in a room cavity ratio of 1, with reflectance 80% ceiling, 50% wall, 20% floor, the C.U. shall not be less than .75. To reduce glare the average brightness at 65° shall not exceed 3301 candelas per square meter. To control veiling reflections, luminaire output in the
Materials: Chassis parts are
Lamp Shield: Linear prismatic translucent DR acrylic lens.
Finish: Chassis exterior – Soft white post painted polyester powder.. Cavity
–Soft white post painted polyester powder. Rust preventative undercoating. Reflector – Soft white post painted polyester powder.
2 Lamp Elec. T5 HO | – | PG †† |
(54 Watt)
††Program Rapid Start (UNV only)
Specifications (continued)
Electrical: Thermally protected class “P’ ballast C.B.M. approved, non PCB. If K.O. is within 3" of ballast, use wire suitable for at least 90°.
UL Listed for damp locations. Labels: I.B.E.W./UL and ULc Listed.
This product may have a mercury containing lamp. Manage in accord with Disposal Laws. See: www.lamprecycle.org
Job Information Type:
For Factory Technical Information: (978) 657-7600 • Fax (978) 658-0595
631 Airport Road, Fall River, MA 02720 • (508)
www.lightolier.com © 2008 a Philips Group | Section 5/Folio |
Lightolier is a Philips group brand