Burner Specification & Data sheet — Beckett Gas Burners
Burner specifications and settings (continued)
Table 2 | Gas train components and flame safeguards |
|
|
|
|
|
|
|
|
|
| |||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
| Standard Gas Control Components and Sizes in Inches |
|
|
|
|
|
| ||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
Boiler |
| Manual |
|
| Combination |
| Safety |
| Manual Checking | |||||||||
Model |
| Hand Valve |
| Diaphragm | Gas Valve |
| Gas Valve | |||||||||||
Number |
| (Field Gas Train |
| Operating Gas Valve |
|
|
|
|
|
|
| |||||||
|
|
|
| Connection) |
| And Regulator |
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
| 1 |
|
|
|
| 1 |
|
|
| 1 |
|
| 1 | |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
588 & 688 |
|
|
|
|
|
| ||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
| |||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
| 2 |
|
|
|
| 2 |
|
|
| 2 |
|
| 2 | |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
1388 |
|
|
|
|
|
|
| |||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||
|
|
|
| Flame Safeguard Provided with Listed Control Systems by Code |
|
|
|
| ||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Boiler |
|
|
| UL/ CSD1 |
|
|
|
| FM |
|
|
|
| IRI |
|
| ||
Model |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| OO or LFS | LHL |
| MOD |
| OO or LFS |
| LHL |
| MOD |
| OO or LFS |
| LHL |
| MOD | ||
Number |
|
|
|
|
|
|
|
| ||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
| RM7897A |
|
| RM7897A |
|
|
| RM7897A |
|
| ||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| RM7897C |
| RM7840L |
|
| RM7897C |
| RM7840L |
|
| RM7897C |
| RM7840L | ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
| Additional control suppliers are available |
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Notes for Table 1 and Table 2
1.Standard motor voltage is 120/60/1 for CG10, CG25 , and 230/60/1 for CG50.
2.Direct Spark Ignition is standard on all models.
3.CG10 models are available only as OO
4.CG25 and CG50 are available as: LHL
•Must be wired with boiler temperature or pressure control switch or operation will be
•MOD –
•Modulation control drives combustion air damper and fuel metering valve in response to boiler demand. Fixed damper
•Open damper
5.Burner capacities listed for elevations up to 2,000 feet. For higher elevations, consult local
6.Gas ratings based on natural gas with heating value of 1,000 btu per cubic foot and specific gravity of 0.60.
7.
8.Minimum gas pressures listed are subject to variations due to job conditions. Gas burners for other gas pressures are available. Consult local
9.Gas manifold pressures shown are for initial
10.Combustion Controls:
a.RM7897 flame safeguard control uses ultraviolet elec- tronic flame detector to monitor gas burner flame, and provides
b.RM7840L flame safeguard control monitors the gas burner flame, provides
11.Burners listed by Underwriters Laboratories, Inc., Canadian Gas Association, state of Connecticut, Fire Marshal state of Massachusetts, city of New York MEA, and others.
12.Special controls can be provided to meet other code require- ments not listed. Consult your local
Part No. | 3 |