Weil-McLain 800059000-Brn-PO Rie F5, 800057000-Brn-PO Rie F5 Pump Purge, TWO Line Lift System

Page 13

GB

TWO LINE (LIFT SYSTEM)

A)If a two-line system is required, install the By-pass plug provided. The by-pass plug is installed in the return port of the pump. A 2.5-mm hexagonal key provided with the by-pass plug is to be used to install the plug.

DO NOT use an inch size hexagonal key; damage to the by-pass plug may result.

When operating on a two-line system, supply and return lines should be the same diameter and both should extend to the same depth inside the fuel tank. Be sure there are no air leaks or blockages in the piping sys- tem. Any obstructions in the return line will cause failure of the pump shaft seal.

2 LINE (LIFT) SYSTEM-PIPE LENGTHS

 

 

 

H

3/8” OD

1/2” OD

 

 

FT

 

M

FT

M

FT

M

 

 

0.0

 

0.0

115

35

330

100

 

 

 

 

ATTENTION:

1.5

 

0.5

100

30

330

100

 

 

 

do not exceed

3.0

 

1.0

80

25

330

100

 

 

 

pipe lengths

5.0

 

1.5

65

20

295

90

 

indicated in chart!

6.5

 

2.0

50

15

230

70

 

 

 

 

 

9.5

 

3.0

25

8

100

30

 

 

11

 

3.5

20

6

65

20

 

 

To install the by-pass plug:

1)Remove the return plug (7).

2)Install the by-pass plug (4) using the 2.5 mm hexagonal key.

H

P

D6008

H

B)Attach the two PIPE CONNECTORS (6) to the pump SUPPLY and pump RETURN PORTS (5 and 7). Attach the required piping to these two pipe connectors using the NPT/ METRIC ADAPTERS that are supplied with the burner.

WARNING:

-Pipe dope or Teflon tapes are NOT to be used on any direct oil connection to the fuel pump.

-The height ‘P’ in Pipe Length Charts should not exceed 13 feet (4 m).

-The vacuum should not exceed 11.44 inches of mercury.

IMPORTANT:

An external, appropriately listed and certified oil filter must be placed in the fuel line between the fuel tank and the burner pump.

PUMP PURGE

NOTE: To protect the pump gears, it is advisable to lubricate the pump prior

to purging a lift system. Apply oil through the VACUUM PORT (C).

B

C

A) SINGLE LINE (GRAVITY FEED SYSTEM)

 

 

I. Loosen the bleeder valve (A) until oil flows out. Tighten the bleeder valve

 

 

securely and startburner.

 

 

II.When bleeding the pump by pressure:

1)Loosen the bleeder valve (A).

2)Disconnect nozzle oil supply line at the pump nozzleport (B).

3)Attach a flexible plastic tube to the pump nozzle, port directing the oil

 

flow into a bucket.

 

4)

Loosen the screw(s) securing the air tube cover, allowing it to be re-

 

 

moved freely.

 

5)

Holding the air tube cover in its proper location start the burner.

A

6)

When the solenoid valve is engaged approximately 10 seconds after

 

starting, remove the air tube cover and shine a light source on the

 

 

photocell, allowing it to see false light.

D7284

3223

10

Image 13
Contents Riello AIR for Combustion Installlation PrecautionsTable of Contents Serial Number Identification Package Contents ListBurner Dimensions Technical Data SpecificationsBurner Components Identification Burner ComponentsInitial SET-UP Assembly of AIR Tube to Burner ChassisMounting the Burner to the Boiler or Furnace Method 1 Universal Mounting Flange DRY Base BoilerMethod 3 Pedestal Mount Method 2 SEMI-FLANGE CollarRequired on some models Amulet Installation InstructionsNo Amulet AUX Key to lay-outMIN. Wire Size Application Field WiringINSTALLATION/REMOVAL Drawer Assembly Nozzle PlacementElectrode Setting Turbulator SettingSingle Line Gravity Feed System OIL Line ConnectionsSingle Line SYSTEM-PIPE Lengths TWO Line Lift System Pump PurgeLine Lift SYSTEM-PIPE Lengths Setting the AIR Adjustment Plate Burner START-UP Cycle Burner Adjustment TableNON-RETROFIT Applications ~ 12sExploded Spare Parts List Code Description Spare Parts ListCode Description Burner Start-up Info OIL Burner START- UP FormTechnical Support Hotline Riello

800058000-Brn-PO Rie F5, 800059000-Brn-PO Rie F5, 800057000-Brn-PO Rie F5 specifications

Weil-McLain is a well-respected name in the heating industry, known for its commitment to providing high-quality residential and commercial heating solutions. Three models that exemplify this dedication are the Weil-McLain 800057000-Brn-PO Rie F5, 800058000-Brn-PO Rie F5, and 800059000-Brn-PO Rie F5. Each of these models brings unique features, technologies, and characteristics that ensure optimal performance and reliability for users.

The Weil-McLain 800057000-Brn-PO Rie F5 is designed to meet the demands of modern heating systems. This model incorporates advanced materials that enhance durability and efficiency, ensuring lasting performance. A key feature of this unit is its modular design, which facilitates easier installation and maintenance. Its compact size allows for greater flexibility in placement, making it suitable for various residential and commercial environments.

Similarly, the 800058000-Brn-PO Rie F5 focuses on energy efficiency. This model boasts a high AFUE (Annual Fuel Utilization Efficiency) rating, indicating that it converts a significant portion of fuel into heat. This enhances its environmental credentials while also providing cost savings on energy bills. The advanced control systems integrated into this model allow users to customize their heating requirements, making it an excellent choice for those seeking greater control over their indoor climate.

The 800059000-Brn-PO Rie F5 stands out with its robust safety features. It includes multiple safety controls and sensors that monitor system performance, helping to prevent overheating and enhance user safety. This model is also designed for quiet operation, ensuring minimal noise disruption while functioning. Its user-friendly interface simplifies operation, making it accessible for homeowners and professionals alike.

Across all three models, Weil-McLain has utilized cutting-edge technology, including smart thermostats compatibility, to enhance user experience. These units are designed to work seamlessly with modern home automation systems, allowing for remote control and monitoring of heating functions. In summary, the Weil-McLain 800057000, 800058000, and 800059000 models exemplify exceptional engineering, efficiency, and safety, addressing the diverse needs of today’s heating market. With their combination of innovative features and reliable performance, these models stand as a testament to Weil-McLain's expertise and dedication to quality heating solutions.