TROUBLESHOOTING
SYMPTO M S | CAUSE | ||
|
|
| |
FAN WON’T START | 1) | Selector in “OFF” position | |
|
| 2) | Check |
|
|
| (If one line is dead, check fuses or breaker in main |
|
|
| disconnect) |
|
| 3) | Check fuse on control circuit transformer |
|
| 4) | Try “SUM” setting. If fan runs, but won’t run on “WIN”, |
|
|
| check 1THS outdoor thermostat (if used) for open |
|
|
| contact; check limit switch on door for |
|
| 5) | Check overload relay on fan starter. Iftripped,reset. If |
|
|
| relay continues to trip, check motor full load amps versus |
|
|
| M starter’s overload relay’s setting (adjustment dial on the |
|
|
| frontofstarter). See manufacturer’s instruction sheet. |
|
|
|
|
FAN | OPERATES, GAS | 1) | Selector in “SUM” position. Turn to “WIN” |
PILOT WILL NOT IGNITE, | 2) | Check wire 6 to ground 115 V (defective selector switch or | |
GREEN “TURN RESET” |
| wiring to same) | |
DOES | NOT LIGHT | 3) | Check wire 7 to ground (bad |
|
| 4) | 9 to ground (bad |
|
| 5) | 10 to ground (bad |
|
| 6) | 11 to ground (bad |
|
| 7) | 12 to ground (bad |
|
|
| setting too high, turn adjustment screw CCW until switch |
|
|
| trips; clogged tubing in airstream) |
|
| 8) | 13 to ground (reset Thermodisc, inside |
|
| 9) | Check toggle switch in mounting base of Fireye (must be |
|
|
| left in “ON” position) |
|
|
|
|
FAN | OPERATES, GAS | 1) | Defective time delay TDR. (Pull from socket, turn RESET, |
PILOT WILL NOT IGNITE, |
| and try again) | |
GREEN “TURN RESET” | 2) | (IRI type only) - One or both gas pressure switched tripped. | |
LIGHTS CONTINUOUSLY |
| Press reset lever. If | |
WHENEVER FAN RUNS |
| cause of inadequate pressure. Check supply pressure ahead of | |
|
|
| regulator, if pressure exceeds rating of regulator,it may pass no gas or |
|
|
| failtoregulate. |
|
|
|
|
FAN | OPERATES, GAS | 1) | Press reset button on Fireye |
PILOT WILL NOT IGNITE, | 2) | If Fireye won’t reset, check for presence of continuous gas | |
GREEN “LOCKOUT” |
| pilot flame | |
LIGHTS CONTINUOUSLY |
|
| |
WHENEVER FAN RUNS |
| CAUTION - In this case turn off manual cock in pilot | |
|
|
| line before stopping fan. Then investigate cause of |
|
|
| pilot valve 1V sticking open |
|
| 3) | If Fireye can be reset, but on next |
|
|
| lights, refer to next sections. If “LOCKOUT” lightsrefertolast |
|
|
| symptom. |
|
|
|
|
5