Carrier 50PG03-16 installation instructions Electric Heater Wire Routing

Page 4

50PG03−16

SINGLE

POINT

BOX

POWER WIRES ARE

ROUTED INTO BOTTOM

OF SINGLE POINT BOX

ROUTE HEATER POWER WIRES

THROUGH RACEWAY AND BEHIND

COMPRESSORS (COMPRESSORS

REMOVED FOR CLARITY)

CONNECT PL3 PLUG

AND RECEPTACLE

HEATER ASSEMBLY

C06185

Fig. 4 Electric Heater Wire Routing

AFFIX HEATER WIRING LABEL DIAGRAM

SUPPLIED WITH HEATERS ON

FOIL FACE INSULATION IN AREA SHOWN

C06186

Fig. 5 Heater Label Location

Install Single Point Box

See Tables 1 and 2 to determine the correct single point box accessory for the selected heater. The appropriate single point box is determined by the MOCP (maximum overcurrent protection) for the heater and unit combination. Refer to the correct figure for correct installation of the single point box components.

Single point accessories CRSINGLE028A00 and CRSINGLE030A00 are for use on units where the combined MOCP rating is less than 60 amps. These accessories contain

only a terminal block; no fuses are provided. Fuses are not required per the National Electrical Code in these single point accessories since the circuit is below 60 amps. Field−supplied pressure connectors (Kerneys) may be used in place of these single point boxes.

All fuses provided in the single point boxes are rated at 60 amps.

UNIT VOLTAGE

FUSE VOLTAGE RATING

UL CLASS

208/230

250

RK5

460

600

T

575

600

T

To install single point box:

1.Remove single point box access panel located on the end of the unit. Save panel and screws. (See Fig. 3.)

2.Using the screws provided, install the terminal blocks and fuse blocks (if required). (See Fig. 6-12.)

3.If required, using the wires provided, connect the terminal block to the fuse block. (See Fig. 13-22.)

4.Route power wires from the control box and electric heaters into the single point box. Route power wires from the disconnect into the single point box through power entry hole located next to the access panel. Make all wiring connections.

5.If single point box has fuses, install hinged cover using rivets provided. Install magnetic latch in rectangular hole. (See Fig. 7-10 and 12.)

6.Install wiring label on back of single point box access panel or on hinged cover.

7.Replace single point box access panel removed in item 1. Configuring the ComfortLinkt Control

The ComfortLink control must be configured for Electric Heat (default is No Heat). In addition, if a single-stage electric heater has been installed, it will be necessary to change the N.HTR configuration (2 is the default setting). These configurations are changed through the Scrolling Marquee Display or a Carrier network device.

4

Image 4
Contents Installation Instructions 50PG03−16 − Block−Off Plate − Electric Heater Wire Routing CRSINGLE028A00, CRSINGLE030A00 − Single Point Box CRSINGLE033A00 − Single Point Box CRSINGLE036A00 − Heater Wiring CRSINGLE030A00 − Heater Wiring CRSINGLE035A00 FLA 221A00 10.0 14.1 030A00 222A00 13.9 15.0 20.0 Low 15.9 21.8 MIN MAX RLA LRA FLA MOCP† VOLTS−PH−HZ MCA VOLTS-PH-HZ MIN MAX RLA LRA FLA Type MCA MOCP† − Rated Load Amps Nominal Voltage Compressor Unit Range OFM Ifmf Power Supply Type Crheater Nominal Nominal Voltage Compressor OFM IFM Unit Range Power Supply FLA Type Crheater Nominal Nominal Voltage Compressor Unit Range OFM IFM Power Supply 208/230-3-60 575-3-60 VOLTS-PH-HZ RLA LRA FLA MOCP† MIN MCA MIN MAX RLA LRA FLA MCA MOCP† VOLTS-PH-HZ MIN MAX RLA LRA FLA MOCP† MCA VOLTS-PH-HZ MIN MAX RLA LRA Rated Load Amps VOLTS-PH-HZ MIN MAX RLA FLA FLA LRA Type 50PG03−16 Nominal Voltage Compressor Power Range Unit OFM IFM MIN MAX RLA LRA FLA MOCP† VOLTS-PH-HZ MCA See legend pg Compr Power OFM Catalog No50PG−16SI

50PG03-16 specifications

The Carrier 50PG03-16 is a notable air conditioning unit designed for residential and light commercial applications. This model stands out due to its combination of efficiency, durability, and innovative technology, making it a popular choice among homeowners and businesses looking for reliable cooling solutions.

One of the primary features of the Carrier 50PG03-16 is its high energy efficiency ratio (EER). This model meets or exceeds the latest environmental standards, which is essential for users looking to reduce their energy consumption and lower utility bills. The unit's efficient refrigerant cycle maximizes cooling output while minimizing energy use.

Carrier's commitment to using advanced technology is evident in the design of the 50PG03-16. The unit is equipped with a highly reliable scroll compressor, which not only operates quietly but also enhances the overall performance and longevity of the system. This type of compressor offers improvements in energy efficiency and reduces maintenance needs, providing peace of mind to the end user.

Another significant characteristic of the Carrier 50PG03-16 is its robust construction. The cabinet is fabricated from high-quality galvanized steel, ensuring durability and resistance to corrosion. This enhances the unit's lifespan and protects it from various environmental factors, which is particularly beneficial in regions with harsh weather conditions.

The ease of installation is another plus with this model. Designed with installers in mind, the Carrier 50PG03-16 simplifies the setup process, allowing for quick and efficient installation. This feature reduces overall labor costs while ensuring that the unit operates optimally from the start.

Furthermore, the Carrier 50PG03-16 offers compatibility with a variety of controls and accessories, allowing homeowners to tailor their system for maximum comfort. Users can integrate smart thermostats and zoning options, promoting enhanced control over indoor climates.

In conclusion, the Carrier 50PG03-16 air conditioning unit is a leading choice for those seeking an efficient, reliable, and durable cooling solution. With its innovative compressor technology, robust construction, and flexible installation features, it is designed to meet the demands of both residential and light commercial applications, ensuring a comfortable environment year-round.