DETERMINING FRESH-AIR FLOW FOR HEATER LOCATION

Determining if You Have a Confined or Unconfined Space

Use this worksheet to determine if you have a confined or unconfined space.

Space: Includes the room in which you will install heater plus any adjoining rooms with doorless passageways or ventilation grills between the rooms.

1.Determine the volume of the space (length x width x height).

Length x Width x Height = _________________ cu. ft. (volume of space)

Example: Space size 20 ft. (length) x 16 ft. (width) x 8 ft. (ceiling height) = 2560 cu. ft. (volume of space)

If additional ventilation to adjoining room is supplied with grills or openings, add the volume of these rooms to the total volume of the space.

2.Divide the space volume by 50 cubic feet to determine the maximum Btu/Hr the space can support.

_________________ (volume of space) ÷ 50 cu. ft. = (Maximum Btu/Hr the space can support)

Example: 2560 cu. ft. (volume of space) ÷ 50 cu. ft. = 51.2 or 51,200 (maximum Btu/Hr the space can support)

3.Add the Btu/Hr of all fuel burning appliances in the space.

Vent-free heater

___________________ Btu/Hr

 

 

 

 

Gas water heater*

___________________ Btu/Hr

Example:

 

 

 

Gas furnace

___________________ Btu/Hr

Gas water heater

 

40,000

Btu/Hr

Vented gas heater

___________________ Btu/Hr

Vent-free heater

+

30,000

Btu/Hr

Gas fireplace logs

___________________ Btu/Hr

Total

=

70,000

Btu/Hr

Other gas appliances* + ___________________ Btu/Hr

 

 

 

 

Total

= ___________________ Btu/Hr

 

 

 

 

*Do not include direct-vent gas appliances. Direct-vent draws combustion air from the outdoors and vents to the outdoors.

4.Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.

_________________ Btu/Hr (maximum the space can support)

_________________ Btu/Hr (actual amount of Btu/Hr used)

Example: 51,200 Btu/Hr (maximum the space can support) 70,000 Btu/Hr (actual amount of Btu/Hr used)

The space in the above example is a confined space because the actual Btu/Hr used is more than the maximum Btu/Hr the space can support. You must provide additional fresh air. Your options are as follows:

A.Rework worksheet, adding the space of an adjoining room. If the extra space provides an unconfined space, remove door to adjoin- ing room or add ventilation grills between rooms. See Ventilation Air From Inside Building, page 6.

B.Vent room directly to the outdoors. See Ventilation Air From Outdoors, page 6.

C.Install a lower Btu/Hr heater, if lower Btu/Hr size makes room unconfined.

If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an unconfined space. You will need no additional fresh air ventilation.

WARNING: If the area in which the heater may be operated is smaller than that defined as an unconfined space, or if the building is of unusually tight construction, provide adequate combustion and ventilation air by one of the methods described in the National Fuel Gas Code, ANS Z223.1, Section 5.3 or applicable local codes.

Continued

107340

5

Image 5
Contents What to do if YOU Smell GAS OWNER’S Operation and Installation Manual FGHS30NGBBlue Flame Natural GAS Heater Safety InformationProduct Identification Product FeaturesLocal Codes UnpackingProviding Adequate Ventilation AIR for Combustion and VentilationUnusually Tight Construction Confined and Unconfined SpaceDetermining if You Have a Confined or Unconfined Space AIR for Combustion VentilationDetermining FRESH-AIR Flow for Heater Location Ventilation Air From Outdoors Ventilation AIRVentilation Air From Inside Building Installation Items InstallationLocate heater where moving ve- hicle will not hit it Check GAS TypeInstalling Thermostat Sensing Bulb Installing Heater to WallPlacing Heater On Mounting Bracket Installing Bottom Mounting ScrewsAttaching Mounting Bracket To Wall Typical Inlet Pipe Diameters Connecting to GAS SupplyPressure Testing Gas Supply Piping System For Your Safety Read Before LightingPressure Testing Heater Gas Connections Operating HeaterLighting Instructions Manual Lighting ProcedureTo Turn OFF GAS To Appliance Thermostat Control OperationInspecting Burner Cleaning and MaintenanceObserved Problem Possible Cause Remedy TroubleshootingMaintenance, Gas leak. See Warning statement at TopParts Centrals SpecificationsThermostat Model FGHS30NGB ODS/Pilot AssemblyIllustrated PARTS8 Breakdown KEY Part Number Description QTY Parts ListService Hints Replacement PartsTechnical Service Service Publications Accessories107340 Warranty Information

FGHS30NGB specifications

The Desa FGHS30NGB is a leading model in the world of portable propane gas heaters, widely renowned for its exceptional performance, advanced features, and versatile applications. Designed to provide efficient heating, this model delivers warmth where it is needed most, perfect for both indoor and outdoor environments.

One of the standout features of the FGHS30NGB is its powerful heating capability, boasting an output of 30,000 BTUs. This makes it ideal for quickly warming up large spaces, whether that be a workshop, garage, or patio. The unit is designed with an adjustable heat setting, allowing users to customize their heating preferences according to their specific needs.

Another significant aspect of the FGHS30NGB is its safety features. The unit is equipped with a built-in automatic shut-off system that activates when the heater is tipped over or does not detect oxygen, ensuring peace of mind during usage. Additionally, the unit is designed with a sturdy and durable construction, making it suitable for outdoor use as well.

The FGHS30NGB incorporates modern technologies that enhance its efficiency. It features an innovative combustion system that allows for optimal fuel utilization, minimizing emissions and maximizing heat output. This not only makes it environmentally friendly but also economical for users, as they can expect reduced operational costs.

Portability is a key characteristic of the FGHS30NGB. It comes with a convenient handle and lightweight design, making it easy to transport from one location to another. Whether you're heading to a construction site or enjoying a weekend camping trip, this portable heater provides the flexibility needed for various situations.

In terms of design, the FGHS30NGB is both functional and aesthetically pleasing. Its compact size ensures it fits comfortably in tight spaces, while its modern look allows it to blend seamlessly with different decor styles.

In summary, the Desa FGHS30NGB propane heater is an excellent choice for anyone seeking reliable, efficient, and portable heating solutions. Its powerful performance, advanced safety features, and user-friendly design make it a top contender in today’s market, offering unmatched versatility for an array of heating needs.