FIREPLACE MANUFACTURERS INCORPORATED UNVENTED NATURAL GAS LOG HEATER

INSTALLATION

Continued

CHECKING GAS

CONNECTIONS

WARNING: Test all gas pip- ing and connections for leaks after installing or servicing. Cor- rect all leaks at once.

WARNING: Never use an open flame to check for a leak. Apply a mixture of liquid soap and water to all joints. Bubbles forming show a leak. Correct all leaks at once.

Pressure Testing Gas Supply Piping System

Test Pressures In Excess Of 1/2 PSIG (3.5 kPa)

Test Pressures Equal To or Less Than 1/2 PSIG (3.5 kPa)

1.Close equipment shutoff valve (see Fig- ure 14).

2.Pressurize supply piping system by ei- ther using compressed air or opening main gas valve located on or near gas meter.

3.Check all joints from gas meter to equipment shutoff valve (see Figure 15). Apply mixture of liquid soap and water to gas joints. Bubbles forming show a leak.

4.Correct all leaks at once.

Open

Equipment

Shutoff

Valve

Closed

Figure 14 - Equipment Shutoff Valve

Pressure Testing Heater Gas Connections

1.Open equipment shutoff valve (see Fig- ure 14).

2.Open main gas valve located on or near gas meter.

3.Make sure control knob of heater is in the OFF position.

4.Check all joints from equipment shutoff valve to control valve (see Figure 15). Apply mixture of liquid soap and wa- ter to gas joints. Bubbles forming show a leak.

5.Correct all leaks at once.

6.Light heater (see Operating Heater, pages 14 and 15). Check all other in- ternal joints for leaks.

7.Turn off heater (see To Turn Off Gas to Appliance, page 15.

1.Disconnect appliance with its appliance main gas valve (control valve) and equip- ment shutoff valve from gas supply pip- ing system. Pressures in excess of 1/2 psig will damage heater regulator.

2.Cap off open end of gas pipe where equipment shutoff valve was con- nected.

3.Pressurize supply piping system by ei- ther using compressed air or opening main gas valve located on or near gas meter.

4.Check all joints of gas supply piping system. Apply mixture of liquid soap and water to gas joints. Bubbles form- ing show a leak.

5.Correct all leaks at once.

6.Reconnect heater and equipment shutoff valve to gas supply. Check re- connected fittings for leaks.

Equipment

 

Shutoff

Control Valve

Valve

 

Location

Gas Meter

 

Figure 15 - Checking Gas Joints

 

12

105070

Image 12
Contents Also DESIGN-CERTIFIED AS a Vented Decorative Appliance What to do if YOU Smell GASSafety Information Product Features Local CodesUnpacking Product IdentificationAIR for Combustion and Ventilation Providing Adequate VentilationUnusually Tight Construction Confined and Unconfined SpaceAIR for Combustion Ventilation Determining FRESH-AIR Flow for Heater LocationDetermining if You Have a Confined or Unconfined Space Ventilation AIR Ventilation Air From InsideBuilding Ventilation Air From OutdoorsInstallation Installation ClearancesCheck GAS Type Vent-Free Operation OnlyIf Using Mantel Minimum NonCombustible Material ClearancesDetermining Minimum Mantel Clearance When Using a Hood Mantel ClearancesFloor Clearances Determining Minimum Mantel ClearanceInstalling Damper Clamp Accessory for Vented Operation Installing Heater Base AssemblyInstallation Items Needed Connecting to GAS Supply Attaching Flexible Gas Hose to Heater Gas RegulatorPressure Testing Gas Supply Piping System Pressure Testing Heater Gas ConnectionsChecking GAS Connections Installing Logs Installing Front Logs #1L and #1RFor Your Safety Read Before Lighting Operating HeaterLighting Instructions Inspecting Burners Cleaning and Maintenance SpecificationsCleaning Burner Injector Holder and Pilot AIR Inlet Hole LogsTroubleshooting Observed Problem Possible Cause RemedyMaintenance, Gas leak. See Warning statement at Illustrated Parts Breakdown Variable Manually Controlled Models VFN18MV VFN24MV VFN30MVParts List Variable MANUALLY- Controlled ModelsVFN18MV VFN24MV VFN30MV Service Hints Technical ServiceReplacement Parts Accessories105070 Warranty Information