Desa UNVENTED (VENT-FREE) PROPANE/LPGAS LOG HEATER Minimum Non Combustible Material Clearances

Page 11

INSTALLING

Continued

NOTICE

Manual control heaters may be used as a vented product. If so, you must always run heater with chimney flue damper open. If running heater with damper open, non-combustible material above fireplace opening is not needed. Go to Installing Damper Clamp Accessory for Vented Operation, page 14.

Minimum Non Combustible Material Clearances

If Not Using Mantel

Note: If using a mantel, go to page 12. If not using a mantel, follow the informa- tion on this page.

You must have non combustible material(s) above the fireplace opening. Non combustible materials (such as slate, marble, tile, etc.) must be at least 1/2 inch thick. With sheet metal, you must have non combustible material behind it. Non combustible material must extend at least 8" up (for all models). If non combus- tible material is less than 12", you must install the fireplace hood accessory (24" model only). See chart below and Figure 4 on page 10 for minimum clearances.

IMPORTANT: If you cannot meet these minimum clearances, you must operate heater with chimney flue damper open. Go to Installing Damper Clamp Accessory for Vented Operation, page 14.

Non-Combustible

Requirements for

Material Distance (A)

Safe Installation

 

 

12" or more

Non combustible material OK.

Between 8" and 12"

24" Model: Install fireplace hood accessory (GA6050

 

or GA6052, see Accessories, page 34).

 

18" Model: Non combustible material OK.

Less than 8"

Non combustible material must be extended to at

 

least 8". See Between 8" and 12", above. If you

 

cannot extend material, you must operate heater

 

with flue damper open.

 

 

Heat Resistant

Material

(A)

Figure 5 - Heat Resistant Material (Slate, Marble, Tile, etc.) Above Fireplace

Continued

103310

11

Image 11
Contents Log Design OWNER’S Operation and Installation ManualFLAME-MAX What to do if YOU Smell GASContents Safety Information With this heater Product Identification Product FeaturesLocal Codes UnpackingUnconfined Space AIR for Combustion and VentilationProviding Adequate Ventilation Unusually Tight ConstructionDetermining if You Have a Confined or Unconfined Space AIR forDetermining AIR Flow for Heater Location Ventilation Air From Outdoors Ventilation AIRVentilation Air From Inside Building Check GAS Type InstallingMinimum Wall and Ceiling Clearances see Figure Minimum Fireplace Clearance To Combustible MaterialsLOG Sizing Requirements Minimum Non Combustible Material Clearances If Using Mantel Installing Attaching Damper Clamp Installing Damper Clamp Accessory for Vented OperationInstallation Items Needed InstallingInstallation Items Needed Connecting to GAS SupplyExternal Regulator With Vent Pointing Down Checking GAS Connections Pressure Testing Gas Supply Piping SystemManual Shutoff Valve Pressure Testing Heater Gas ConnectionsFor Standard Oak Model Installing LogsFor Premium Models Installing Premium One-Piece Log SetOperating Heater For Your Safety Read Before LightingVariable Control Operation Pilot Flame Pattern Operating Heater Inspecting BurnersLogs Trouble ShootingQualified service person should service and repair heater ODS/PILOT and BurnerTROUBLE- Shooting Maintenance,Refer to Air for Com Gas leak. See Warning Hints ServiceReplacement TechnicalIllustrated Parts Breakdown KEY Part Number for VYS18P VYS24P Description QTY Parts ListBirch Log Models VYD24P and VYBD24P KEY Part Number for VYD24P VYBD24P Description QTY Hood GA6052 AccessoriesValve GA5010 Hood GA6050103310 Keep this Warranty Warranty Information