VANGUARD FLAME MAX®
UNVENTED NATURAL GAS LOG HEATER
INSTALLATION
Continued
NOTICE: Manual control heaters may be used as a vented product. If so, you must always run heater with chimney flue damper open. If running heater with damper open, noncombustible material above fireplace opening is not needed. Go to Installing Damper Clamp Accessory for Vented Op-
If Using Mantel
You must have noncombustible material(s) above the fireplace opening. Noncombus- tible materials (such as slate, marble, tile, etc.) must be at least 1/2 inch thick. With sheet metal, you must have noncombustible material behind it. Noncombustible mate- rial must extend at least 8 inches up (for all models). If noncombustible material is less than 12", you must install the fireplace hood accessory (24", 30" and 36" models only).
Even if noncombustible material is more than 12", you may need the hood accessory to deflect heat away from your mantel shelf. See Figure 5 and Figures 6 and 7 on page 9 for minimum clearances.
IMPORTANT: If you cannot meet these minimum clearances, you must operate heater with chimney flue damper open. Go to Installing Damper Clamp Accessory for Vented Operation, page 10.
eration, page 10.
Minimum Noncombustible Material Clearances
If Not Using Mantel
Note: If using a mantel, proceed to If Using Mantel. If not using a mantel, follow the information below.
You must have noncombustible material(s) above the fireplace opening. Noncombus- tible materials (such as slate, marble, tile, etc.) must be at least 1/2 inch thick. With sheet metal, you must have noncombustible material behind it. Noncombustible material must extend at least 8" up (for all models). If noncombustible material is less than 12", you must install the fireplace hood accessory (24", 30" and 36" models only). See Figure 5 at right for minimum clearances.
IMPORTANT: If you cannot meet these minimum clearances, you must operate heater with chimney flue damper open. Go to Installing Damper Clamp Accessory for Vented Operation, page 10.
Noncombustible |
| Requirements for | ||||
Material Distance (A) |
| Safe Installation | ||||
|
|
| ||||
12" or more |
| Noncombustible material OK. | ||||
Between 8" and 12" |
| 24", 30", or 36" Models: Install fireplace hood ac- | ||||
|
|
|
|
| cessory (GA6050, GA6052 or GA6053 see Acces- | |
|
|
|
|
| sories, page 25). | |
|
|
|
|
| 18" Model: Noncombustible material OK. | |
Less than 8" |
| Noncombustible material must be extended to at | ||||
|
|
|
|
| least 8". See Between 8" and 12", above. If you | |
|
|
|
|
| cannot extend material, you must operate heater | |
|
|
|
|
| with flue damper open. | |
|
|
|
|
|
|
|
Heat Resistant |
|
|
|
| ||
|
|
|
| |||
|
|
|
| |||
Material |
|
|
| |||
|
|
|
|
|
| (A) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Figure 5 - Heat Resistant Material (Slate, Marble, Tile, etc.) Above Fireplace