Enerco MHVFB10LP Ventilation AIR, Ventilation from Inside Building, Ventilation from Outdoors

Page 4

1.Find the volume of the space by multiplying room length x width x height.

Example: Space size 18ft (length) x 18ft. (width) x 8ft. (height) = 2592

If additional ventilation to adjoining room is supplied with grills or openings, add the volume of these rooms to the total volume of the space.

2.Divide the space volume by 50 cubic feet to deter- mine the maximum Btu/hr the space can support.

Example: 2592 cu.ft. (volume of space) / 50 cu.ft. = 51.8 or 51,800 (maximum Btu/hr the space can support)

WARNING: If the area in which the heater may be operated is smaller than defined as an unconfined space or if the building is of unusually tight construc- tion, provide adequate combustion and ventilation air by the methods described in the National Fuel Gas Code, NFPA 54/ ANSI Z223.1, Section 5.3 or applicable local codes.

3.Add the Btu/hr of all the fuel-burning appliances in the space such as, Vent–free heater, Gas water heater, Gas furnace, Vented gas heater, Gas fireplace logs, and Other gas appliances*

*Do not include direct-vent gas appliances. Direct- vent draws combustion air from the outdoors and vents to the outdoors.

Example:

 

Gas water heater

40,000 Btu/hr

Vent Free Heater +

20,000 Btu/hr

Total

=60,000 Btu/hr

4.Compare the maximum Btu/hr the space can support with the actual amount of Btu/hr used.

Example: 51,800 Btu/hr (maximum Btu/hr the space can support)

60,000 Btu/hr (Actual amount of Btu/hr used)

The space in the above example is a confined space because the actual Btu/hr used is more than the maximum Btu/hr the space can support.

You must provide additional fresh air. Your options are as follows:

A. Rework worksheet, and the space of an adjoining room. If the extra space provides an unconfined space, remove door to adjoining room or add ventila- tion grills between the rooms. See Ventilation Air From Inside Building (Fig. 2)

B. Vent room directly to the outdoors. See Ventilation Air From Outdoors (Fig. 3).

C. Install a lower Btu/hr heater if lower Btu/hr size makes room unconfined.

If actual Btu/hr used is less than the maximum Btu/ hr the space can support, the space is an uncon- fined space. You will need no additional fresh air ventilation.

VENTILATION AIR

Ventilation from Inside Building

This fresh air would come from an adjoining unconfined space. When ventilation to an adjoining unconfined space, you must provide two permanent openings: one within 12” of the ceiling and one within 12” of the floor on the wall connecting the two spaces (see options 1 & 2 of fig. 2). You can also remove door into adjoining room (see option3, fig 2). Follow the National Fuel Gas Code NFPA 54/ ANSI Z223.1, Section 5.3, Air for Combustion and Ventilation for required size of ventilation grills or ducts.

 

 

12”

Ventilation

Or remove

Ventilation Gills into

Adjoining Room -

Gills into

door into

Adjoining

Option 2

Adjoining

Room -

 

Room -

 

Option 3

 

Option 1

 

 

 

 

12”

Figure 2

WARNING: Rework worksheet, adding the space of the adjoining unconfined space. The combined space must have enough fresh air to supply all appliance in both spaces.

 

 

 

 

 

 

 

 

 

 

 

 

VENTILATION AIR

OUTLET AIR

 

 

 

 

 

 

VENTILATED

 

 

 

 

 

 

 

 

 

 

 

 

 

ATTIC

OUTLET

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TO ATTIC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AIR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TO CRAWL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

INLET

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SPACE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AIR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

VENTILATION234CRAWL SPACE

Figure 3.

Ventilation from Outdoors

If necessary provide extra fresh air by using ventilation grills or ducts. Connect these items directly to the outdoors or spaces open to the outdoors. These include attics* and crawl spaces. Follow the National Fuel Gas

4Installation instructions and Owner’s Manual

Image 4
Contents MR. Heater Carbon Monoxide Poisoning PrecautionsPropane/LP Gas Safety Device Local CodesIgnition System UnpackingVentilation from Inside Building Ventilation AIRVentilation from Outdoors Installation Check GAS Type For Permanent InstallationLocating Heater Fastening Heater to WallAttaching to Wall Stud Installing Bottom Mounting Screws Connecting to GAS Supply for Permanent InstallationPressure Testing Heater Gas Connections Test pressure in Excess of ½ psig 3.5kPaWhat to do if YOU Smell GAS Lighting InstructionsCleaning and Maintenance To Turn OFF GAS to ApplianceInspecting Burner Pilot Flame PatternSpecifications Cleaning ODS/PILOT and BurnerCleaning Burner Pilot AIR Hole Inlet Cleaning Heater CabinetTroubleshooting Observed Symptom Possible Cause RemedyTroubleshooting CON’T Observed Symptom Possible Cause RemedyParts List Description QTY Warranty Information Enerco GROUP, INC., 4560 W TH ST., CLEVELAND, Ohio

MHVFB10LP specifications

The Enerco MHVFB10LP is a high-performance propane infrared heater that has made its mark in the heating equipment industry, thanks to its innovative design and advanced technology. Built for both indoor and outdoor use, this versatile heater is particularly popular for its reliability and efficiency in providing warmth in various settings, including garages, workshops, and outdoor gatherings.

One of the standout features of the MHVFB10LP is its high-efficiency infrared heating capability. Unlike conventional heaters that rely on air convection, this unit delivers heat directly to objects and people in its vicinity. This direct heating method not only ensures faster warmth but also reduces energy waste, making it an economical choice for users. With a heating capacity of up to 10,000 BTUs, it can effectively warm spaces up to 250 square feet.

The Enerco MHVFB10LP is equipped with a state-of-the-art Piezo ignition system, which allows for easy and reliable start-up without the need for matches or lighters. Its adjustable heat settings provide flexibility, enabling users to customize their heating experience depending on the specific needs of the environment. Additionally, the heater features a durable construction made from high-quality materials, ensuring longevity and resilience in both indoor and outdoor conditions.

Safety is paramount in the design of the MHVFB10LP. The model includes an integrated safety shut-off system that activates in the event of a tip-over or if the flame goes out, providing peace of mind during use. The heater also features a sturdy base, ensuring stability and reducing the risk of accidental tipping.

Another notable characteristic of the Enerco MHVFB10LP is its compact and portable design. Weighing moderately and featuring a convenient handle, it allows users to easily move the heater wherever needed. This mobility makes it an ideal choice for construction sites, event setups, and home use.

In summary, the Enerco MHVFB10LP stands out for its efficient infrared heating technology, user-friendly features, safety components, and portability. Whether used for work or leisure, this heater is an excellent investment for anyone looking to enjoy warmth and comfort in any environment. With a combination of safety, efficiency, and versatility, the MHVFB10LP delivers exceptional performance that meets the heating needs of various users.