Enerco MHU 75, MHU 45 owner manual Service

Page 12

minimum of 5.0" w.c. for natural gas or 10.4" w.c. for LP/ propane gas should be maintained for proper unit operation.

2.After line pressure has been checked and adjusted, check manifold pressure. Correct manifold pressure is shown on the unit rating plate. See figure 10 for gas pressure adjustment screw location. A natural gas to LP/propane gas changeover kit is required to convert unit. Refer to installation instructions provided with changeover kit for conversion procedure.

LIMIT CONTROL

The limit control switch is factory set and not field adjustable.

TABLE 4

NATURAL GAS MANIFOLD PRESSURES - IN.WC. (KPA)

 

ALTITUDE FT. (M)

MHU45/75 HSU45/75

0-2000

2 000-4500

 

(0-610)

(610-1370)

45/75

4.0 (0.99)*

3.6 (0.89)

*No adjustment required.

TABLE 5

LP/PROPANE GAS MANIFOLD PRESSURES - IN.WC. (KPA)

 

ALTITUDE FT. (M)

MHU45/75 HSU45/75

0-2000

2 000-4500

 

(0-610)

(610-1370)

45/75

10 (2.49)*

8.0 (1.99)

*No adjustment required.

LOUVER VANE ADJUSTMENTS

Rotate louver vanes to direct airflow upward, downward, straight, or any combination of these directions. When unit is installed in an inverted position, louvers may be positioned in the same manner.

COMBUSTION AIR PRESSURE SWITCH

This pressure switch checks for proper combustion air blower operation before allowing an ignition trial. The switch is factory set and no field adjustment is necessary.

FLAME ROLLOUT SWITCH

The flame rollout switch(es) are located on the burner box top, behind the ignition control board. This normally closed switch opens on a temperature rise. Check for adequate combustion air before manually resetting switch.

SERVICE

CAUTION Turn off gas and electrical power to unit before performing any maintenance or service operations on this unit. Remember to follow lighting instructions when putting unit back into operation after service or maintenance.

If any of the original wire as supplied with the appliance must be replaced, it must be replaced with wiring material having a temperature rating of at least 105°C.

Do not use this appliance if any part has been under water. Immediately call a qualified service technician to inspect the appliance and replace any gas control which has been under water.

BURNERS

1.Periodically examine burner flames for proper appearance during the heating season.

2.Before each heating season examine the burners for any deposits or blockage that may have occurred.

3.Clean burners as follows:

Turn off both electrical and gas supplies to unit.

Disconnect gas supply piping, high tension and sensor leads. Remove gas manifold. Remove burner tray.

Clean burners as necessary. Make sure that burner heads line up properly to ensure flame crossover. Check spark gap on electrode and adjust if required. The gap should be between 0.110 inch and 0.140 inch (2.79mm to 3.56mm). The gap may be checked with appropriately sized twist drills or feeler gauges.

Reinstall burner tray, gas manifold, high tension and sensor leads. Reconnect gas supply piping.

Restore electrical power and gas supply. Follow lighting instructions to light unit. Check burner flame.

FLUE PASSAGEWAY AND FLUE BOX

The flue passages and flue box should be inspected and cleaned prior to each heating season. The sequence of operation should be as follows:

1.Turn off both electrical and gas supply to unit.

2.Disconnect combustion air blower wiring.

3.Remove screws securing flue box to unit. Remove flue box. If necessary, remove blower assembly from flue box. Clean flue box with wire brush.

4.Remove turbulator retention bracket and turbulators. Clean turbulators with wire brush.

5.Remove burners as described in section “BURNERS” section.

6.Clean tubes with a wire brush.

7.Reassemble unit. The combustion air and flue box gaskets should also be replaced during reassembly.

8.Restore electrical power and gas supply. Follow lighting instructions to light unit. Check operation of unit.

Enerco Compact Unit Heater

12 Operating Instructions and Owner’s Manual

Image 12
Contents MR. Heater Contents General Hazard WarningMHU45/MHU75 and HSU45/HSU75 Unit Dimensions TOP ViewBack View Side View START-UP and Performance Check ListGarage Installations ShippingRequirements CSA in the USA Requirements CSA in CanadaUnit Heater Installation Install Unit HeaterCombustion and Ventilation AIR VentingHorizontal Venting General Vent Termination on Single Wall VentHorizontal Venting Commercial Horizontal Venting ResidentialCondensate Drain Through TEE Pipe and Drain Loop Venting Using a Masonry Chimney Horizontal Venting Residential InstallationRemoval of Unit from Common Vent Line Voltage Field Wiring Electrical ConnectionsGAS Supply Connection GAS Supply to Unit HeaterGAS Connection Leak CheckStart UP and Operation Unit START-UPAdjustments Service Ladder Diagram Wire DiagramParts List Enerco Compact Unit Heater For Information Regarding Service Limited WarrantyParts Ordering Information

MHU 45, MHU 75 specifications

Enerco is a renowned name in the heating industry, particularly famous for its innovative line of forced air propane heaters. The Enerco MHU 45 and MHU 75 models are among the top choices for both residential and commercial heating needs, showcasing a range of advanced features and technologies designed for efficient performance and user convenience.

The MHU 45 and MHU 75, as their names suggest, deliver heating outputs of 45,000 BTU and 75,000 BTU respectively, making them suitable for a variety of applications, from small workshops to larger industrial spaces. Both models are equipped with a powerful fan that ensures even heat distribution, rapidly warming up an area while maintaining energy efficiency.

One of the standout features of the MHU series is their lightweight and portable design, allowing users to easily move the heaters from one location to another. This is particularly beneficial in a work environment where heating needs may vary based on project demands. The integrated handle and rubber feet add to the convenience, ensuring stability during operation.

The MHU series also incorporates safety technologies that have been meticulously designed to protect both the unit and the user. Both models are equipped with a built-in safety shut-off valve that automatically turns the heater off in the event of a tip-over or overheating, providing peace of mind for users.

Efficiency is a key characteristic of the Enerco MHU heaters. They utilize propane fuel for combustion, which tends to burn cleaner than other fossil fuels. This not only contributes to a reduced environmental impact but also translates to savings on energy costs for users. The MHU 45 and MHU 75 feature adjustable heat settings, which allow for customized heating to match specific needs, further enhancing their efficiency.

In terms of runtime, the MHU series offers impressive performance. The fuel consumption is optimized to ensure users can rely on these heaters for extended periods without frequent refueling interruptions.

In summary, the Enerco MHU 45 and MHU 75 are powerful, portable, and efficient propane heaters designed to deliver excellent performance in a variety of settings. With their robust safety features, lightweight design, and ability to provide rapid heat distribution, they stand out as exceptional choices for those seeking reliable heating solutions. Whether for industrial, commercial, or residential use, these models underline Enerco's dedication to quality and innovation in heating technology.