Field Controls UV-18X Flat Bracket Installation, Angled Bracket Installation

Page 4

3.Remove base unit and cover from box.

4.Apply supplied “Duct Seal Kit” according to instructions included in kit. (See Figure 12)

Figure 12

5.Determine whether to use flat or angled bracket. (Refer to UV-Aire Configurations in Section III for aid in this decision)

a. Flat Bracket Installation

i.Remove the two hex nuts and flat bracket from included bagged hardware.

ii.Install the flat bracket and secure to the unit base with the hex nuts provided. (See Figure 13)

Figure 13

b. Angled Bracket Installation

NOTE: For angled bracket mounting, refer to specifications outlined by Diagrams A & B for mounting distances in the “Angled Lamp Mounting Bracket Specifications” in section III.

i.Remove the two hex nuts and angled bracket from included bagged hardware.

ii.Install the angled bracket and secure to the unit base with the hex nuts provided. (See Figure 14)

NOTE: Be sure to note location of lamp hole in bracket relative to unit base.

Figure 14

6.Mount the unit base to the duct using the four mounting screws provided. (See Figure 15)

7.Remove tag and alcohol from lamp. Wipe off lamp being sure not to touch lamp with bare hands. The oils in your hands may cause the lamp to prematurely expire.

Figure 15

WARNING: Never expose eyes or skin to UVC light from any source. Looking directly at the UVC light may cause permanent eye damage or blindness. Never operate the UV-Aire™ Air Purifying System out of the plenum. Avoid touching the glass portion of the lamp with your hands.

Page 4

Image 4
Contents Safety Considerations Items Included in KITIndication for USE III. InstallationII. General Information For flex duct applications, refer to on Flat Bracket Installation Angled Bracket InstallationPage Diagram a IV. Bulb Mounting Bracket Selection and InstallationDiagram B Maintenance VI. Replacement ProcedureVII. Troubleshooting Guide VIII. Replacement Parts ListIX. Flex Duct Installation Provisions