NOTE - Oil burning equipment may be vented into an ap- proved masonry chimney or type L vent. (Type L vent is similar in construction to type B gas vent. Type L vent car- ties a higher temperature rating and is constructed with an inner liner of stainless steel, rather than aluminum.)

Prior to installation of unit, make a thorough inspection of the chimney to determine whether repairs are necessary. Make sure the chimney is properly constructed and sized according to the requirements of the National Fire Protec- tion Association. The smallest dimensions of the chimney should be at least equal to the diameter of the furnace vent connector. Make sure the chimney will produce a steady draft sufficient to remove all the products of combustion from the furnace. A draft of at least .04" w.c. (9.9 Pa) is re- quired during burner operation.

1.Local building codes may have more stringent installa-

tion requirements and should be consulted before installation of unit.

2.The vent connector should be as short as possible to do the job.

3.The vent connector should not be smaller than the out- let diameter of the vent outlet of the furnace.

4.Pipe should be at least 24 gauge galvanized.

5.Single wall vent pipe should not run outside or through any unconditioned space.

6.Chimney should extend 3 feet (0.9 m) above highest point where the vent passes through the roof, and 2 feet (0.6 m) higher than any portion of a building within a horizontal distance of 10 feet (3 m).

7.The vent must not pass through a floor or ceiling. Clearances to single wall vent pipe should be no less than 6" (152 mm); more if local codes require it.

8.The vent may pass through a wall where provisions have been made for a thimble as specified in the Stan- dards of the National Board of Fire Underwriters. See figure 6.

Wall Thimble

COMBUSTIBLE

VENT PIPE

WALL

 

Figure 6

9.The vent pipe should slope upward toward the chim- ney on horizontal run at least 1/4 inch (6 mm) to the foot (0.3 m) and should be supported by something other than the furnace, such as isolation hangers. See figure 7.

Masonry Chimney

BAROMETRIC

CONTROL*LINER

(

LOCATION)

CLEAN OUT

MASONRY

CHIMNEY

CLEAN OUT

*Barometric control may be installed in either vertical or horizontal section of flue pipe within 18" of flue outlet of furnace.

Figure 7

10.Extend the vent pipe into the chimney so that it is flush with the inside of the vent liner. Seal the joint between the pipe and the liner.

11.The furnace shall be connected to a factory built chim- ney or vent complying with a recognized standard, or

masonry or concrete chimney lined with a lining mate- rial acceptable to the authority having jurisdiction.

12.When two or more appliances vent into a common vent, the area of the common vent should not be less than the area of the largest vent or vent connection plus 50% of the area of the additional vent or vent con- nection. Chimney must be able to sufficiently vent all appliances operating at the same time.

13.The vent pipe shall not be connected to a chimney vent serving a solid fuel appliance or any mechanical draft system.

14.All unused chimney openings should be closed.

15.All vent pipe run through unconditioned areas or out- side shall be constructed of factory built chimney sec- tions. See figure 8.

Page 6

505082M 10/05

Image 6
Contents 505,082M Unit Start-Up & AdjustmentsTechnical Blower ControlO23V Model Supply TOP Flue Outlet Side Flue Outlet4X4 Combustion O23V Installation Clearances Inches mmTop of plenum & duct Model NoBeckett Oil Burner Nozzle Adjustment O23V Series Burner RemovalWall Thimble Masonry ChimneyShouldberepairedorreplaced,Accumulationof con Factory-built ChimneyAir from an Adjacent Space Equipment In Confined Space All Air From InsideAir from Outside Removal of Unit from Common Venting System Equipment in Confined Space All Air From OutsideDirect Connection of Outdoor Air for Combus- tion Horizontal VentingRadiation Shield Installation Alternate Side Flue ConnectionsOil Piping One-Pipe System OilSystem One-Pipe Systems Micron replacement cartridge for filter, 45 gphFilter restriction indicator gauge 81 P89Control Board A54 Blower Control Board A54Blower YI ID12 DDZ3g fAdjust Heat PumpModel O23V2/3-70/90 Units Continuous FanCfm Model O23V3/4-105/120 Units023V Wiring Diagram LLLAdjusting Limit Control PsigServicing the Oil Burner Servicing the Air FilterProcedure Check thermostat settings CausesCorrection Source Procedure CausesBurner Replacethe fuseSourceProcedure Causes CorrectionSource Power After burner firesLocate and secure connection Source Procedure Too much heatToo little heat Replacement Installation Data Start-Up ProcedureOwner Record

O23V2-90, O23V-90, O23V4-105, O23V5-154, O23V3-70 specifications

Lennox International Inc. is a leading provider of innovative climate control solutions, widely recognized for its high-quality heating, ventilation, and air conditioning (HVAC) systems. Among its varied product line, the O23 series exemplifies Lennox's commitment to energy efficiency, performance, and user-friendly technology.

The O23V2-90, O23V3-120, O23V3-90, O23V4-105, and O23V2-70 are advanced models of the O23 series, designed specifically for residential settings. Each model offers unique specifications tailored to meet diverse customer needs.

These units are equipped with cutting-edge inverter technology, which allows for precise control of air temperature and flow. By adjusting the compressor speed, these systems optimize energy consumption while maintaining comfort. This variable-speed operation minimizes energy waste and significantly reduces utility bills, a key advantage for homeowners seeking efficient solutions.

The O23V3-120 stands out for its high cooling and heating capacities, making it ideal for larger homes or commercial spaces. Meanwhile, the O23V2-70 model is designed for smaller applications, ensuring that even modest-sized spaces can benefit from Lennox quality. Each model also features robust insulation and construction, enhancing durability and performance over time.

Incorporating smart technology, these units come with Wi-Fi connectivity, empowering users to manage their home’s temperature remotely through a smartphone app. The integration with smart home systems further enhances the user experience, providing convenience and efficiency right at your fingertips.

Quiet operation is another hallmark of the O23 series. Each model is engineered to reduce sound levels, ensuring that comfort does not compromise peace within the home.

Additionally, these units are designed with environmentally-friendly refrigerants, aligning with global sustainability efforts. This focus on eco-conscious technology not only adheres to regulatory standards but also appeals to environmentally-aware consumers.

Overall, Lennox O23 series models showcase a blend of advanced technology, efficient performance, and user-friendly features, embodying the brand’s commitment to excellence in climate control solutions. For homeowners and businesses alike, investing in these models translates to greater comfort, cost savings, and a reduced ecological footprint.