Bryant 362AAN → ÐBURNER, NOZZLE, and Pump Pressure Chart, VIII. Constant Blower Switch

Page 6

TABLE 4ÐBURNER, NOZZLE, AND PUMP PRESSURE CHART

UNIT

FIRING

PUMP

BECKETT OIL BURNER

RATE

PRESSURE

 

 

SIZE

Model

Nozzle

GAL/HR (US)

(PSIG)

 

036105

0.76

103

AFG

0.75 gph

70° Hollow

 

 

 

 

048125

0.90

100

AFG

0.90 gph

70° Hollow

 

 

 

 

060155

1.12

104

AFG

1.10 gph

70° Hollow

 

 

 

 

 

 

 

 

 

c.Tighten purge fitting. Allow oil to run to nozzle and fire burner.

d.If purging takes longer than 30 sec and no flame has been established, burner stops. Push reset button on top of primary control to restart burner.

e.For detailed information on operation of primary control, refer to instructions included with furnace.

VIII. CONSTANT BLOWER SWITCH

This furnace is equipped with a constant low-speed blower option. Whenever room thermostat is not calling for heating or cooling, blower runs on low speed in order to provide air circulation. If constant blower option is not desired, the rocker switch on side of control box may be used to turn off constant speed.

MAINTENANCE

WARNING: The ability to properly perform mainte- nance on this equipment requires certain expertise, me- chanical skills, tools, and equipment. If you do not

possess these, do not attempt to perform any maintenance on this equipment other than those procedures recom- mended in the User's Manual. FAILURE TO FOLLOW THIS WARNING COULD RESULT IN POSSIBLE DAMAGE TO THIS EQUIPMENT, SERIOUS PER- SONAL INJURY, OR DEATH.

III.FAN ADJUSTMENT CHECK

This furnace is equipped with a 3-speed direct-drive motor to deliver a temperature rise (between return and supply plenums) within range specified on rating plate at external duct static pressure noted on rating plate.

CAUTION: When operating furnace in heating mode, static pressure and temperature rise (supply-air tempera- ture minus return-air temperature) must be within those limits specified on rating label. Failure to follow this warning could lead to severe furnace damage.

Adjust fan speed so that temperature rise is within rise range specified on rating plate. Consult wiring diagram for speed changes on direct-drive motor.

To adjust fan off time, set DIP switches on control board to obtain desired timing. (See Fig. 1.)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

2

 

 

1

2

 

 

1

2

 

 

1

2

 

 

 

 

60 Sec

 

 

90 Sec

 

120 Sec

 

150 Sec

 

 

 

 

 

 

 

DELAY OFF DIP SWITCH SETTINGS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A95115

Fig. 1ÐFan Off Time DIP Switch Settings (Black Box Represents Switch Position)

IV. LIMIT CONTROL CHECK

After furnace has been in operation for at least 15 minutes, restrict return-air supply by blocking filters or closing return registers and allow furnace to shut down on high limit. The burner should shut off, and main blower should continue to run.

Remove restriction, and burner should come back on in a few minutes.

V.FOR YEAR-ROUND AIR CONDITIONING

This furnace is designed for use in conjunction with cooling equipment to provide year-round air conditioning. The blower has been sized for both heating and cooling, however, fan motor speed may need to be changed to obtain necessary cooling airflow.

VI. HEATING

The blower speed is factory set to deliver required airflow at normal duct static pressure.

VII. COOLING

The blower speed may be field adjusted to deliver required airflow for cooling application. (See Table 5.)

WARNING: Before performing any service functions, unless operations specifically require power to be on, make sure all utilities are turned off upstream of appli- ance. Failure to comply with this warning will cause a fire hazard and/or bodily harm.

WARNING: To avoid personal injury, make sure elec- trical supply power is off before servicing.

I. GENERAL

In order to keep this furnace in good operating condition and to maintain its warranty, the furnace MUST be serviced on an annual basis. This servicing includes a nozzle change, a burner inspection, a visual check of tube passages through flue outlet and cleanout ports, and a visual inspection of combustion chamber when burner is removed.

Depending on above inspection, service could also include a cleaning and vacuuming of heat exchanger tubes and possibly the heat exchanger drum section.

Removal of any heat exchanger components which are sealed by gaskets requires replacement of gasket.

WARNING: Failure to replace any heat exchanger gas- kets with new gaskets when any heat exchanger plates or covers are removed could lead to heat exchanger leakage, sooting, and/or a hazardous condition capable of causing bodily harm.

This furnace should never be operated without an air filter. Disposable filters should be replaced at least once a year. If equipped to provide cooling, filters should be replaced a minimum of twice a year. Permanent filters should be cleaned at least twice a year.

ALWAYS KEEP MAIN OIL VALVE TURNED OFF IF BURNER IS SHUT DOWN FOR AN EXTENDED PERIOD OF TIME.

II.OIL BURNER

Contact your service technician for service.

Lubricate burner motor with SAE 10 oil. Once each year, pour 2 teaspoons of oil slowly into each oil cup.

To maintain proper performance, oil burner nozzle must be replaced once a year.

Ð6Ð

Image 6
Contents This symbol → indicates a change since the last issue Index Recommended Installation PracticesSafety Considerations Location Ðminimum Clearances to Combustible MaterialsIntroduction AIR for Combustion and VentilationÐ3Ð Lockouts on start-upII. Duct Work Recommendations II. Masonry Chimney PRE-INSTALLATION Vent System InspectionVenting Instructions Ðminimum Certified Furnace Pipe SizeFilters II. Recommended Installation Practices and Combustion CheckElectrical Operational CheckoutMaintenance → ÐBURNER, NOZZLE, and Pump Pressure ChartVIII. Constant Blower Switch III. FAN Adjustment Check→ III. Heat Exchanger and Flue Pipe Ð7Ð→ Ðairflow Data CFM Keeping Filters CleanIV. Blower Oiling and Removal Ð8ÐDimensions Ð9ÐBAD Locations Ð10ÐÐ11Ð Factory SET Heating SpeedII. Preparing Your Furnace for Operation Users Information Heres HOW Your Heating System WorksIII. Lighting Your Furnace IV. Turning OFF Your Furnace

362AAN specifications

The Bryant 362AAN is an exemplary air conditioning unit renowned for its durability, efficiency, and advanced technology. Designed to cater to both residential and light commercial applications, the 362AAN stands out as a highly reliable solution for cooling needs.

One of the main features of the Bryant 362AAN is its high-efficiency performance. With SEER ratings reaching as high as 16, this unit can significantly reduce energy costs while providing optimal cooling. The 362AAN employs a two-stage cooling system that enhances comfort by maintaining a more consistent indoor temperature. This feature not only ensures a pleasant environment but also helps in saving energy by adjusting the cooling output according to the indoor conditions.

The Bryant 362AAN is built using high-quality materials and components, ensuring reliability and longevity. Its all-aluminum coil enhances corrosion resistance, making it suitable for various climates. This durability extends the unit's lifespan and reduces the need for frequent repairs or replacements, providing homeowners with peace of mind.

A standout technology in the Bryant 362AAN is the EcoNet Smart Thermostat compatibility, which allows users to monitor and control their cooling system remotely. This smart technology provides real-time data, enabling users to optimize energy consumption and receive alerts for maintenance needs. The integration of smart technology also allows for potential energy savings, as users can customize their cooling schedules based on their lifestyle.

Noise reduction is another key characteristic of the Bryant 362AAN. Designed with advanced sound technology, this unit operates at quieter levels, ensuring minimal disruption to indoor activities. This is particularly beneficial in residential areas where noise can be a concern.

In terms of installation versatility, the Bryant 362AAN can be easily integrated into various home setups. Its compact design and flexible installation options ensure that it can fit in tight spaces without compromising performance.

Overall, the Bryant 362AAN air conditioning unit combines efficiency, technology, and reliability to provide an outstanding cooling solution. With its range of features and commitment to sustainability, it remains a popular choice among homeowners and businesses looking to enhance their indoor comfort while minimizing energy consumption.