WARNING
Service should be performed only by qualified persons.
SERVICE
If status code recall is needed, do not remove power or blower door.
LED CODE | STATUS |
CONTINUOUS OFF | Check for 115V at L1 and L2, and 24V at SEC1 and SEC2. |
CONTINUOUS ON | Control has 24V power. |
RAPID FLASHING | Line voltage polarity reversed. If twinned, 24V power |
| to one furnace may be out of phase with power to other furnace. |
|
|
EACH OF THE FOLLOWING STATUS CODES IS A
THE FIRST DIGIT DETERMINED BY THE NUMBER OF SHORT FLASHES AND
THE SECOND DIGIT BY THE NUMBER OF LONG FLASHES.
11NO PREVIOUS CODE - Stored status codes are erased when power (115V or 24V) to control is interrupted or 48 hours after each fault is cleared.
12BLOWER ON AFTER POWER UP - Blower runs for 90 seconds, if unit is powered up during a call for heat
13LIMIT OR FLAME
Check for: - Refer to #33
14IGNITION LOCKOUT - Control will
21GAS HEATING LOCKOUT - Control will NOT
Check for: -
22 ABNORMAL
Check for: - Leaky gas valve | - |
23LOW- OR
-Defective pressure switch (stuck closed)
24SECONDARY VOLTAGE FUSE IS OPEN
Check for: -
31
Check for: -Control relay may be defective - Refer to #32
32
- Low inducer voltage (115v) | * Blower motor and capacitor |
- Defective inducer motor | - Defective pressure switch |
- Excessive wind | - Restricted vent |
-Inadequate combustion air supply
-Disconnected or obstructed pressure tubing
33 LIMIT OR FLAME ROLL-OUT (FRS) SWITCH IS OPEN - FRS switch
requires
Check for: - Inadequate combustion air supply (FRS switch only)
- Dirty filter or restricted duct system | - Loose blower wheel |
- Defective switch or connections |
|
- Blower motor or capacitor failure |
|
34
-Proper
-Proper control ground continuity
-
- Smooth flame carryover and ignition - Manual valve(s) OFF
43
-Defective pressure switch (stuck open)
-Refer to #32 and #33
45 REPLACE CONTROL