Superior VFPF-CMN-2, VFST-CMP-2, VFPF-CMP-2, VFST-CMN-2 Possible Cause Remedy, Observed Problem

Page 15

TROUBLESHOOTING GUIDE FOR UNVENTED GAS PRODUCTS

OBSERVED PROBLEM

 

POSSIBLE CAUSE

REMEDY

1.

When igniter button is

 

A. Igniter electrode positioned wrong.

Replace igniter.

 

pressed, there is no spark

 

 

 

 

 

 

 

 

at ODS/pilot.

 

B. Igniter electrode broken.

Replace igniter.

 

 

 

 

 

 

 

 

C. Igniter electrode not connected to igniter cable.

Reconnect igniter cable.

 

 

 

 

 

 

 

 

D. Igniter cable pinched or wet.

Free igniter cable if pinched by any metal or tubing. Keep igniter cable dry.

 

 

 

 

 

 

 

 

E. Piezo igniter nut is loose.

Tighten nut.

 

 

 

 

 

 

 

 

F. Broken igniter cable.

Replace igniter cable.

 

 

 

 

 

 

 

 

G. Bad piezo igniter.

Replace piezo igniter.

 

 

 

 

 

2.

Heater produces unwanted

 

A. Heater burning vapors from paint, hair spray, glues, etc.

Ventilate room. Stop using odor-causing products while fireplace is running.

 

odors.

 

 

 

 

 

B. Gas leak. See Warning statement on the front page.

Locate and correct all leaks.

 

 

 

 

 

 

 

 

3.

Heater shuts off in use

 

A. Not enough fresh air is available.

Open window and/or door for ventilation.

 

(ODS operates).

 

 

 

 

 

B. Low line pressure.

Contact local gas company.

 

 

 

 

 

 

 

 

 

 

 

C. ODS/pilot is partially clogged.

Clean ODS/pilot.

 

 

 

 

 

4.

Gas odor even when control

 

A. Gas leak. See Warning statement on the front page.

Locate and correct all leaks (see Checking Gas Connections, page 7).

 

knob is in “OFF” position.

 

 

 

 

 

B. Control valve defective.

Replace control valve.

 

 

 

 

 

 

 

 

5.

When igniter button is

 

A. Gas supply turned off or manual shut-off valve closed.

Turn on gas supply or open manual shut-off valve.

 

 

 

 

 

 

 

pressed, there is spark at

 

B. Control knob not in “PILOT” position.

Turn control knob to pilot position.

 

ODS/pilot, but no ignition.

 

 

 

 

 

C. Control knob not pressed in while in “PILOT” position.

Press in control knob while in pilot position.

 

 

 

 

 

 

 

 

 

 

 

D. Air in gas lines when installed.

Continue holding down control knob. Repeat igniting operation until air is

 

 

 

 

removed.

 

 

 

 

 

 

 

 

E. ODS/pilot is clogged.

Replace ODS/pilot assembly or get it serviced.

 

 

 

 

 

 

 

 

F. Gas regulator setting is not correct.

Replace gas regulator.

 

 

 

 

 

6.

ODS/pilot lights, but flame

 

A. Control knob not fully pressed in.

Press in control knob fully.

 

goes out when control knob

 

 

 

 

 

 

 

 

is released.

 

B. Control knob not pressed in long enough.

After ODS/pilot lights, keep control knob pressed in 30 seconds.

 

 

 

 

 

 

 

 

C. Manual shut-off valve not fully open.

Fully open manual shut-off valve.

 

 

 

 

 

 

 

 

D. Thermocouple connection loose at control valve.

Hand tighten until snug, then tighten ¹⁄₄ turn more.

 

 

 

 

 

 

 

 

E. Pilot flame not touching thermocouple, which allows

 

 

 

 

thermocouple to cool, causing pilot flame to go out. This

 

 

 

 

problem could be caused by one or both of the following:

1). Contact local gas company.

 

 

 

1). Low gas pressure

 

 

 

2). Dirty or partially clogged ODS/pilot

2). Replace ODS/pilot assembly or get pilot serviced.

 

 

 

 

 

 

 

 

F. Thermocouple damaged.

Replace thermocouple.

 

 

 

 

 

 

 

 

G. Control valve damaged.

Replace control valve.

 

 

 

 

 

7.

Burner does not light after

 

A. Burner orifice is clogged.

Clean burner or replace burner orifice.

 

ODS/pilot is lit.

 

 

 

 

 

B. Burner orifice diameter is too small.

Replace burner orifice.

 

 

 

 

 

 

 

 

 

 

 

C. Inlet gas pressure is too low.

Contact local gas company.

 

 

 

 

 

8.

Delayed ignition of burner.

 

A. Manifold pressure is too low.

Contact local gas company.

 

 

 

 

 

 

 

 

B. Burner orifice is clogged.

Clean burner or replace burner orifice.

 

 

 

 

 

9.

Burner backfiring during

 

A. Burner orifice is clogged or damaged.

Clean burner or replace burner orifice.

 

combustion.

 

 

 

 

 

B. Burner damaged.

Replace burner.

 

 

 

 

 

 

 

 

 

 

 

C. Gas regulator defective.

Replace gas regulator.

 

 

 

 

 

10.

Slight smoke or odor during

 

A. Vapors from paint or curing process of logs.

Problem will stop after a few hours of operation. SFC recommends running the

 

initial operation.

 

 

heater with excess ventilation for the first few hours.

 

 

 

 

 

11.

Heater produces a whistling

 

A. Turning control knob to “HI” position when burner is cold.

Turn control knob to “LO” position and let warm up for a minute.

 

noise when burner is lit.

 

 

 

 

 

B. Air in gas line.

Operate burner until air is removed from line. Have gas line checked by local gas

 

 

 

 

 

 

 

company.

 

 

 

 

 

 

 

 

C. Dirty or partially clogged burner orifice.

Clean burner or replace burner orifice.

15

Image 15
Contents Unvented Decorative Gas Fireplaces 903571 REV. F 03/2005 Standard SeriesTable of Contents Combustion and Ventilation AIR CodesHigh Traffic Areas Windy or Drafty Areas Cable Local CodesLocation of Fireplace ClearancesCheck Gas Type PreinstallationAssembly Steps Installation StepsVfst Appliance Specifications Vfst Framing SpecificationsFraming Dimensions 43 1092 mm Min Vfpf Framing Specifications³⁄₄ 578 mm ¹⁄₈ 1016 mm MinMix a 50% dish soap, 50% water solution Finished Wall Details Vfst Series Standard Wiring DiagramFlame Appearance Assembling the LogsOptional Equipment Remote Control KitWall Switch Kit Installing the Optional Glass DoorWall Thermostat Kit Optional on Unit Rocker SwitchSolid Brass Hood Kit Solid Brass Louver KitOperation and Care of Your Appliance Cleaning and ServicingReplacement Parts Accessories and ComponentsConversion Possible Cause Remedy Observed ProblemTo Turn OFF GAS to Heater Operating InstructionsWhat to do if YOU Smell GAS Lighting InstructionsTurn Control Knob to on Position Turn Control Knob to OFF Position PilotTurn Control Knob to Pilot Position Pilot LocationVfst Replacement Parts List VFST-CMNDescription Replacement Parts Vfst VFPF-CMN Vfpf Replacement Parts ListReplacement Parts Vfpf Page Page Orange, CA 903571 REV. F 03/2005

VFPF-CMP-2, VFPF-CMN-2, VFST-CMN-2, VFST-CMP-2 specifications

The Superior VFST-CMP-2, VFPF-CMN-2, VFPF-CMP-2, and VFST-CMN-2 represent a cutting-edge suite of products designed to meet the demands of modern applications in various industries, including telecommunications, data management, and industrial automation. Each of these models incorporates advanced features and technologies aimed at enhancing performance, reliability, and user experience.

The VFST-CMP-2 is particularly focused on high-speed data processing. With an impressive throughput and low latency, it is engineered for tasks that require rapid data handling, making it suitable for applications in cloud computing and data centers. This model incorporates state-of-the-art error correction algorithms, ensuring data integrity during transmission and significantly reducing downtime.

In contrast, the VFPF-CMN-2 is tailored for network management and monitoring. It boasts a comprehensive interface that allows users to track network performance in real-time. The intuitive dashboard provides insights into traffic loads, bottlenecks, and overall system health. This model is equipped with cutting-edge analytics features that leverage machine learning to predict potential issues before they become critical, enhancing proactive maintenance capabilities.

The VFPF-CMP-2 combines features from both offerings, positioned as a hybrid solution that caters to versatile applications. It balances powerful data processing and efficient network management, making it an optimal choice for organizations looking to streamline operations across various platforms. With its modular architecture, users can easily scale their systems as demand increases without significant overhauls.

Finally, the VFST-CMN-2 excels in interoperability. Designed to integrate seamlessly with existing infrastructures, it supports a wide range of protocols and standards. This flexibility ensures that it can be deployed in diverse environments, minimizing compatibility issues. The device also emphasizes security, incorporating advanced encryption technologies to protect sensitive data during transmission.

In summary, the Superior VFST-CMP-2, VFPF-CMN-2, VFPF-CMP-2, and VFST-CMN-2 are exemplary models that bring together innovative features and technologies. Their unique characteristics make them well-suited for various applications, providing essential tools for enhanced data processing, network management, and operational efficiency. Organizations investing in these products are poised to benefit from improved performance and adaptability in an ever-evolving technological landscape.