Carrier Comprehensive Service Manual for Furnace Models 58MVB and 58MCB

Page 7

After the hot surface igniter is heated for 17 seconds, the gas valve permits gas to flow to the main burners. After ignition and a time delay of about 60 sec, the furnace blower will start. Variable-capacity furnaces start at low speed until the control makes the necessary adjustments to operate the blower at either the low- or high-heat speed.

NOTE: If the burners fail to ignite after 4 attempts, the fur- nace control system will lock out. If lockout occurs, main burners fail to light, or blower does not come on, shut down the furnace and call your dealer for service.

12.Set your thermostat to the temperature that satisfies your comfort requirements.

SUGGESTION: Setting the thermostat back a few degrees—and compensating for the difference with warmer clothing—can make a big difference in your fuel consumption. The few degrees at the top of your thermo- stat “comfort level’’ are the most costly degrees to obtain.

When the room temperature drops below the temperature selected on the thermostat, the furnace will switch on auto- matically. When the room temperature reaches the tempera- ture selected on the thermostat, the furnace will be switched off automatically.

OR

 

22

OFF

ON

Some thermostats have a FAN mode with 2 selections:AUTO and ON. When set on AUTO, the furnace blower cycles on and off. In the ON mode, the furnace blower runs continu- ously. Continuous fan keeps the temperature level in your home more evenly balanced. It also permits the indoor air to be continuously filtered. ComfortFan™ –On all but the 58MCB, the blower speed can be increased or decreased if desired due to change of seasons, large gatherings in your home, etc. Simply change your FAN from ON to OFF for 1 to 3 seconds (or AUTO depending on your thermostat), and then return to ON. The blower will switch to the next higher speed. There are at least 3 speeds to choose from. If the blower is running on its highest speed, a request to change will direct the blower to return to its lowest speed.

SHUTTING DOWN YOUR FURNACE

Should you ever need to shut down your furnace for service or maintenance, you will need to turn the furnace off. The following procedures must be followed:

1.Set your room thermostat to the lowest temperature setting. (See Fig. 21.)

®

21

2.Close the external manual gas valve (See Fig. 11.)

3.Turn off electrical supply to the furnace. (See Fig. 22.)

4.Remove main furnace door. (See Fig. 13.)

5.Turn the switch on the gas control to the OFF position. (See Fig. 23 or 24.)

For 58MTB and 58MVB

23

 

M

1

O

P

3

F

C

2

F

ON

For 58MCB and 58MXB

24

6.Replace the main furnace door. (See Fig. 18.)

7.If the furnace is being shut down because of a malfunc- tion, call your dealer as soon as possible.

! CAUTION

UNIT AND PROPERTY DAMAGE

Failure to follow this caution may result in damage to the furnace and other property damage. Furnace is not to be installed, operated, and then turned off and left turned off in an unoccupied structure during winter. (See “Heading South for the Winter” procedures in maintenance section on page 10).

PERFORMING ROUTINE

MAINTENANCE

NOTE: The qualified installer or agency must use only factory-authorized replacement parts, kits, and accessories when modifying this product.

Installing and servicing heating equipment can be hazard- ous due to gas and electrical components.

7

Image 7
Contents 58MCB, 58MTB, 58MVB, 58MXB MULTIPOISE, Condensing Direct VENT/NON-DIRECT VentFurnaces Table of ContentsWelcome to a NEW Generation of Comfort Models 58MXB ShownModels 58MCB, 58MXB, and 58MTB Furnaces Upflow Position Furnace ComponentsModel 58MVB Furnace Upflow Position These safety rules Safety ConsiderationsFire and Unit Operation Hazard Starting and Shutting Down Your FurnaceSteps for Starting Your Furnace Fire or Explosion HazardFor 58MTB and 58MVB For 58MCB and 58MXB 1112For 58MTB and 58MVB For 58MCB and 58MXB 1920 Shutting Down Your Furnace Performing Routine MaintenanceUnit and Property Damage AIR Filters Loacted in Blower COMPART- Ment Side Filtering OUT TroubleAIR Filterss Located in Blower COMPART- Ment AIR Filter Located in Blower Compartment BottomPersonal Injury Hazard Combustion Area and Vent SystemHeading South for the WINTER? 3940DON’T Forget Your Furnace If Furnace Fails to Operate CHECK-UP ChecklistBefore YOU Request a Service Call For Insufficient AirflowIndoor Coil AIR Conditioner or Heat Pump