After the hot surface igniter is heated for 17 seconds, the gas valve permits gas to flow to the main burners. After ignition and a time delay of about 60 sec, the furnace blower will start.
NOTE: If the burners fail to ignite after 4 attempts, the fur- nace control system will lock out. If lockout occurs, main burners fail to light, or blower does not come on, shut down the furnace and call your dealer for service.
12.Set your thermostat to the temperature that satisfies your comfort requirements.
SUGGESTION: Setting the thermostat back a few
When the room temperature drops below the temperature selected on the thermostat, the furnace will switch on auto- matically. When the room temperature reaches the tempera- ture selected on the thermostat, the furnace will be switched off automatically.
OR |
| 22 |
OFF | ON |
Some thermostats have a FAN mode with 2 selections:AUTO and ON. When set on AUTO, the furnace blower cycles on and off. In the ON mode, the furnace blower runs continu- ously. Continuous fan keeps the temperature level in your home more evenly balanced. It also permits the indoor air to be continuously filtered. ComfortFan™
SHUTTING DOWN YOUR FURNACE
Should you ever need to shut down your furnace for service or maintenance, you will need to turn the furnace off. The following procedures must be followed:
1.Set your room thermostat to the lowest temperature setting. (See Fig. 21.)
®
21
2.Close the external manual gas valve (See Fig. 11.)
3.Turn off electrical supply to the furnace. (See Fig. 22.)
4.Remove main furnace door. (See Fig. 13.)
5.Turn the switch on the gas control to the OFF position. (See Fig. 23 or 24.)
For 58MTB and 58MVB
23
| M | 1 |
O | P | 3 |
F | C | 2 |
F |
ON
For 58MCB and 58MXB
24
6.Replace the main furnace door. (See Fig. 18.)
7.If the furnace is being shut down because of a malfunc- tion, call your dealer as soon as possible.
! CAUTION
UNIT AND PROPERTY DAMAGE
Failure to follow this caution may result in damage to the furnace and other property damage. Furnace is not to be installed, operated, and then turned off and left turned off in an unoccupied structure during winter. (See “Heading South for the Winter” procedures in maintenance section on page 10).
PERFORMING ROUTINE
MAINTENANCE
NOTE: The qualified installer or agency must use only
Installing and servicing heating equipment can be hazard- ous due to gas and electrical components.
7