Weil-McLain PFG CGa, EG-30 to EG-65, PEG-30 to PEG-55, Foryour Safety Read Before Lighting

Page 13

UserísInformationManual

Lighting instructions

CGa, EG-30 to EG-65,

Standing pilot

PEG-30 to PEG-55

Gas valve Honeywell VR8200/VR8300

FORYOUR SAFETY READ BEFORE LIGHTING

If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or loss of life.

A.This appliance has a pilot, which must be lighted by hand. When lighting the pilot, follow these instructions exactly.

B.Before LIGHTING, smell all around the appliance area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor. See below.

C.Use only your hand to push down the reset button or turn the gas control knob. Never use tools. If the knob or reset button will not operate by hand, don't try to repair it, call a qualified service technician. Force or attempted repair may result in a fire or explosion.

D.Do not use this appliance if any part has been under water. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control, which has been under water.

WHAT TO DO IF YOU SMELL GAS

Do not try to light any appliance.

Do not touch any electric switch; do not use any phone in your building.

Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.

If you cannot reach your gas supplier, call the fire department.

LIGHTING INSTRUCTIONS

1.Stop! Read the safety information above on this label.

2.Set the thermostat to lowest setting.

3.When equipped with Effikal vent damper Model RVGP, place service switch in Hold Damper Open position.

4.Turn off all electrical power to the appliance.

5.When equipped with Johnson Controls vent damper Model M35, manually rotate damper blade in direction of arrow to Open position indicated on damper assembly.

6.Turn gas control knob clockwise to OFF.

7.When equipped with vent damper, verify damper blade is in full open position.

Position

 

indicator

Gas

(shown in

control

ON position)

Red

knob

 

reset button

 

59334

 

8.Wait five (5) minutes to clear out any gas. Then smell for gas, including near the floor. If you smell gas, STOP! Follow "B" in the safety information above. If you don't smell gas, go to the next step.

9.Remove access panel located above burners.

10.Find pilot — follow metal tube from gas control. The pilot is between two burners

behind the access panel.

11. Turn gas control knob counterclockwise to PILOT.

12.Push in red reset button and hold. Immediately light the pilot with a match. Continue to hold reset button in for about one (1) minute after the pilot is lit.

13.Release reset button. Pilot should remain lit. If pilot goes out, repeat steps 6 through 13.

If reset button stays depressed after release, stop and immediately call your service technician or gas supplier.

If the pilot will not stay lit after several tries, turn the

gas control knob clockwise to OFF and call your service technician or gas supplier.

14.Replace access panel.

15.Turn gas control knob counterclockwise to ON.

16.Turn on all electric power to the appliance.

17.When equipped with Effikal vent damper, place service switch in Automatic Operation position.

18.Set thermostat to desired setting.

19.Replace front panel.

TOTURN OFF GASTOTHE APPLIANCE

1.

Set the thermostat to lowest setting.

3.

Remove front panel.

 

2.

Turn off all electric power to the appliance if service is to

4.

Turn gas control knob clockwise

to OFF.

 

be performed.

5.

Replace front panel.

 

 

 

 

Part Number 550-110-592/1000

13

Image 13
Contents CGa, CGi, CGs, EG, EGH, LGB, PEG, PFG Manual Please read this page firstHazard definitions STOP!! Read before proceeding UserísInformationManualCGi LGB Tankless water heater EG and EGH Only Maintain boiler using schedule belowCheck daily User maintenance proceduresBoiler area CGa, CGi, CGs, EG, EGH, PEG & PFG-5 onlyCheck monthly Automatic air vents if used Main burner flame Clean vent termination & air intake screensPilot burner flame Check condensate drain systemFloat type low water cutoff Service periodicallyClean gauge glass Service every 6 monthsOperate boiler relief valve Lighting instructions Follow boiler shutdown procedureEnd-of-season shutdown Propane gas odorantCGa, EG-30 to EG-65 Foryour Safety Read Before LightingPEG-30 to PEG-55 Lighting InstructionsStanding pilot Gas valve Robertshaw CGa-25 to CGa-6, EG-30 to EG-50, PEG-30 to PEG-50PFG-6, PFG-7 EG-75, EGH-85, EGH-95Operating Instructions Operating instructions Foryour Safety Read Before OperatingCGa, EG-30 to EG-75, PEG-30 to PEG-55, PFG-5 Spark-ignited pilot Gas valve Honeywell VR8204/VR8304Spark-ignited pilot Gas valve White-Rodgers 36E Spark-ignited pilot Gas valve White-Rodgers 36C CGa-7, CGa-8, EG-55 to EG-75, PEG-55, PFG-5Spark-ignited pilot Gas valve Robertshaw PFG-6 to PFG-8 EGH-85 to EGH-125Spark-ignited pilot CGi, CGs For Your Safety Read Before OperatingTo Turn OFF GAS to the Appliance To Place in Operation Annual Shutdown ProcedureSymptom Common Causes Possible Corrections Common problems and solutionsWeil-McLain Blaine Street Michigan City,

CGi, PFG, PEG, LGB, CGs specifications

Weil-McLain is a highly regarded manufacturer of boilers and hydronic heating systems, well-known for its innovative approach and commitment to quality. Among its extensive product lineup, the PEG, LGB, CGs, PFG, and CGi series stands out due to their advanced engineering, efficiency, and reliability. Each series caters to varying residential and commercial heating needs, making them versatile options for consumers.

The PEG series is recognized for its impressive efficiency ratings and robust construction. It utilizes a cast iron heat exchanger, which not only enhances heat retention but also ensures longevity. Its low water content and advanced control features allow for quick heating response times, making it ideal for homes requiring reliable heat. The PEG series is available in a range of sizes, ensuring a fit for any application.

The LGB series is tailored for light commercial applications, combining efficiency with remarkable performance. Built with Weil-McLain’s signature high-grade cast iron, the LGB models are designed for durability and ease of maintenance. They offer an impressive thermal efficiency and feature a compact design, making them suitable for installations where space is a concern. Advanced options such as multiple venting configurations contribute to their versatility, adapting to various building designs.

The CGs series is specifically designed for commercial applications and emphasizes efficiency through advanced technology, including an intelligent control system that optimizes operation based on demand. Its low NOx design helps meet stringent environmental standards, while its robust build ensures high performance under heavy load conditions. The CGs is often sought after for larger facilities requiring consistent and efficient heating.

Weil-McLain’s PFG series takes efficiency to the next level with its highly efficient gas-fired design. It features a light-weight configuration and quick-connect venting options, which simplify installation. This series is known for its low emissions and high energy efficiency, making it an eco-friendly choice for today’s environmentally conscious consumers.

Lastly, the CGi series is a standout for residential applications, offering flexibility and ease of use. The series features a cast iron heat exchanger and is compatible with various control systems, providing an adaptable and efficient solution for home heating.

Overall, Weil-McLain’s PEG, LGB, CGs, PFG, and CGi series exemplify the company’s dedication to quality, energy efficiency, and customer satisfaction, providing reliable heating solutions for diverse applications.