Trane SSP-PRC001-EN manual Jobsite Connections, TWA060/TWE060A, TWA090A/TWE180B TWA120A/TWE240B

Page 36

Jobsite Connections

Wiring shown with dashed lines is to be furnished and installed by the customer. All customer- supplied wiring must be copper only and must conform to NEC and local electrical codes. Codes may require line of sight between disconnect switch and unit.

Note: When electric heater accessory is used single point power entry or dual point power entry is field optional. Single point power entry option is through electric heater only.

TWA060/TWE060A

Field Wiring:

Figure 16. Title goes here in this table cell

A3 power wires. Line voltage for 3 phase; 2 wires for single phase.

B3 power wires. Line voltage for 3 phase; 2 wires for single phase

CHeat pump thermostat: 6 wires, 24 volts.

Electric heat: add 2 additional wires, 24 volts.

D2 wires, 24 volts.

Outdoor thermostat: add 1 additional wire per ODT, 24 volts. Electric heat: add 1 additional wire, 24 volts.

(2)TW-048/TWE090B

(2)TW-030/TWE060B

(2)TW-060/TWE120B

Field Wiring:

A3 power wires. Line voltage for 3 phase; 2 wires for single phase.

B3 power wires. Line voltage for 3 phase; 2 wires for single phase.

CHeat pump thermostat: 7 wires,

24 volts Electric Heat: add 2 additional wires, 24 volts.

D5 wires, 24 volts to outdoor section "A’’ 2 wires, 24 volts to outdoor section “B’’ 2 wires, 24 volts between outdoor sections “A” “B’’

Electric heat: add 1 additional wire, 24 volts.

Outdoor thermostat: add 1 additional wire, 24 volt.

TWA090A/TWE090A

TWA120A/TWE120A

Field Wiring:

A3 power wires, line voltage.

B3 power wires, line voltage for

3 phase; 2 wires for single phase.

CHeat pump thermostat: 6 wires, 24 volts.

Electric heat: add 2 additional wires, 24 volts.

D6 wires, 24 volts. Outdoor thermostat: add 1additional wire, 24 volts. Electric heat: add 1 additional wire, 24 volts.

(2)TWA090A/TWE180B

(2)TWA120A/TWE240B

Field Wiring:

A3 power wires, line voltage.

B3 power wires, line voltage.

CHeat pump thermostat: 7 wires, 24 volts.

Electric heat: add 2 additional wires, 24 volts.

D9 wires, 24 volts.

Electric heat: add 4 additional wires, 24 volts.

Outdoor thermostat: add 3 additional wires, 24 volts.

TWA180B/TWE180B

TWA240B/TWE240B

Field Wiring:

A3 power wires, line voltage.

B3 power wires, line voltage.

CHeat pump thermostat: 7 wires, 24 volts.

Electric heat: add 2 additional wires, 24 volts.

D7 wires, 24 volts.

Electric heat: add 4 additional wires, 24 volts.

Outdoor thermostat: add 1 additional wire, 24 volts.

36

SSP-PRC001-EN

Image 36
Contents Split System Heat Pumps Introduction Manufacturing ControlDesigning the Details Standardized CabinetsContents Features and Benefits Condensing Units OptionsAir Handlers Offer More Flexibility Features and Benefits Odyssey a Complete Split SystemApplication Considerations Clearance RequirementsBlower Rotation Low Ambient CoolingApplication Considerations Selection Procedure Cooling CapacityHeating Capacity Air Delivery SelectionModel Number Description Split System Heat Pump Model NomenclatureAir Handler Model Nomenclature General Data General Data Heat PumpsGeneral Data Air Handlers Indoor Coil TypeIndoor Fan Type Filters Type/FurnishedAmbient Temperature 105 Entering WB CFM Air Flow Ambient Temperature 115 Enter WB CFM Air FlowPerformance Data DB F MBH SHCTons Gross Cooling Capacities SHC MBHTons Gross Cooling Capacities DB F MBH SHC MBH SHC MBH SHC MBH SHC DB F7200 198 164.3 217.7 137.3 238.9 88.8 Suction Temperature F Outdoor Temp F ½ Tons Gross Cooling Capacities and Capacity CurvesGross Cooling Capacities MBh 7½ Tons TWA090A Heat Pump Only Tons Gross Cooling Capacities and Capacity Curves Gross Cooling Capacities MBh 10 Tons TWA120A Heat Pump OnlyCapacity Curves 15 Tons TWA180B Heat Pump Only Gross Cooling Capacities MBh 15 Tons TWA180B Heat Pump OnlyCapacity Curves 20 Tons TWA240B Heat Pump Only Gross Cooling Capacities MBh 20 Tons TWA240B Heat Pump Only½, 10 Tons Gross Heating Capacities 15, 20 Tons Gross Heating Capacities Evaporator Fan Performance, Low Static Fan Drive, 5 Tons Low Static Fan Drive 5 Ton TWE060A, TWE060B Air HandleriExternal Static Pressure Inches of Water Gauge HP Oversized Motor & SheavesEvaporator Fan Performance, Low Static Fan Drive, 7½ Tons Low Static Fan Drive 7½ Tons TWE090A, B Air HandlerCFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP Evaporator Fan Performance, Low Static Fan Drive, 10 Tons External Static Pressure Inches of Water Gauge 00 1.20 1.40Tons Evaporator Fan Performance CFM RPM BHPEvaporator Fan Performance, Low Static Fan Drive, 15 Tons Evaporator Fan Performance 15 Tons TWE180B Air HandlerLow Static Fan Drive 15 Ton TWE180B Air Handleri CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHPEvaporator Fan Performance, Low Static Fan Drive, 20 Tons Evaporator Fan Performance 20 Ton TWE240B Air HandlerLow Static Fan Drive 20 Tons TWE240B/TWE240E Air Handler CFM RPM BHP BHP RPM BHP RPM BHPElectric Heat Discharge Plenum and Grille Airflow CFM Sheave Position Turns Tons Unit Model No Open ClosedDischarge Plenum and Grille Assembly Throw Distance Louver Angle Deflection Position Tons Model NoCFM StraightTons Static Pressure Drop, Auxiliary Heat Capacity Auxiliary Electric Heat Capacity Air HandlerBtuh Controls ThermostatsUnit Wiring Heat Pumps Tons Unit Model No Volts PhaseElectrical Data Compressor Fan Motor Condenser Fan Motor AmpsTons, Air Handler Unit Wiring, Electrical Characteristics Unit Wiring Air HandlerElectrical Characteristics Motors 60Hz Air Handler Unit Wiring with Electric Heat TWE120AW Jobsite Connections TWA060/TWE060ATW-048/TWE090B TW-030/TWE060B TW-060/TWE120B TWA090A/TWE180B TWA120A/TWE240BTypical Wiring Heat Pump Single Compressor Wiring Diagram Heat Pump Dual Compressor Wiring Diagram Heat Pump Dual Compressor Wiring Diagram Air Handler Wiring Diagram Dimensional Data ½ Tons TWA090 Heat Pump. All dimensions are in inchesTons TWA120A Heat Pump. All dimensions are in inches TonsTons TWA180B Heat Pump. All dimensions are in inches Tons TWA240B Heat Pump. All dimensions are in inches Air Handler Dimensions Tons Model No½ & 10 Ton 10 Ton 10 Tons TWE060A, 090A, 120A TWE060B, 090B, 120B Air HandlersTons TWE180 Air Handlers. All dimensions are in inches Tons TWE180 Air Handlers Tons TWE240B Air Handlers Ton TWE240B Air Handlers Accessories, Electric Heater Accessories, Discharge Plenum and Grille Discharge Plenum and Grille Dimensions in. No HeatDischarge Plenum and Grille Accessories, Subbase Subbase DimensionsAccessories, Rubber isolators Isolator DimensionsAccessories, Spring Isolators 20 Ton Spring IsolatorsWeights Unit and Corner Weights lbsAccessory Weights net lbs Air Handlers RISMechanical Specifications Refrigeration System Evaporator CoilEvaporator Fan Control Options Page Trane

SSP-PRC001-EN specifications

The Trane SSP-PRC001-EN is a state-of-the-art product designed to enhance the efficiency and performance of HVAC systems. As a part of Trane’s expanding suite of smart building technologies, this device integrates advanced features and cutting-edge technology to provide optimal climate control for various applications, including commercial and industrial settings.

One of the primary features of the SSP-PRC001-EN is its ability to monitor and manage energy consumption effectively. The device employs real-time data analytics to provide insights into energy use patterns, allowing facility managers to make informed decisions that can significantly reduce operational costs. By leveraging this information, organizations can optimize their HVAC operations, leading to enhanced sustainability and compliance with environmental regulations.

Another notable characteristic of the SSP-PRC001-EN is its integration with Trane’s smart building technology. The system is designed to seamlessly connect with various sensors and building management systems, creating a comprehensive ecosystem for energy management. Its compatibility with existing infrastructure means that users can upgrade their systems without the need for extensive retrofitting, minimizing disruption while maximizing efficiency.

The SSP-PRC001-EN also boasts user-friendly interfaces that simplify operation and monitoring. Facility managers can easily access data and analytics through intuitive dashboards, which can be customized to display the most relevant information. This ease of use is critical for timely decision-making, especially in environments where rapid response to changing conditions is essential.

In terms of reliability and performance, the SSP-PRC001-EN is built to withstand demanding conditions. Designed with durability in mind, its rugged construction ensures long-lasting service, making it an ideal choice for facilities operating in various environments. Moreover, the system is engineered for flexibility, allowing for adjustments based on specific operational needs.

Overall, the Trane SSP-PRC001-EN combines advanced technology with practical features to deliver an efficient, reliable, and user-friendly solution for HVAC management. Whether for upgrading existing systems or integrating into new buildings, it stands as a testament to Trane's commitment to innovation and sustainability in the realm of climate control solutions. This product exemplifies how technological advancements can contribute to smarter building management and energy efficiency in today's demanding operational landscapes.