Trane SSP-PRC001-EN manual Selection Procedure, Cooling Capacity, Heating Capacity

Page 8

Selection Procedure

Cooling Capacity

Step 1.

Calculate the building’s total and sensible cooling loads at design conditions.

Step 2.

Size the equipment using Table 3. Match the cooling loads at design conditions.

Example: The following are the building cooling requirements:

a.Electrical Characteristics: 460/60/3

b.Summer Design Conditions: Entering Evaporator Coil: 80°F DB/67°F WB Outdoor Ambient: 95°F

Total Cooling Load: 90 MBh

c.Sensible Cooling Load: 64 MBh

d.Airflow: 3000 cfm External Static Pressure: 0.77 inches of water gauge

Table 3 shows that TWA090A4 with TWE090A has a gross cooling capacity of 91.1 MBh and 65.9 MBh sensible capacity at 95°F DB ambient and 3000 cfm with 80°F DB/67°F WB air entering the evaporator.

To find the net cooling capacities, fan motor heat must be subtracted. Determine the total unit static pressure:

External Static Duct System

0.77 in.

Standard Filter 1 in.

0.10 in.

Supplementary Electric Heat

0.23 in.

Total Static Pressure

1.10 in.

Note: The Evaporator Fan Performance Table has included the effect of a 1 in. filter already. Therefore, the actual Total Static Pressure is

1.10- 0.10 = 1.00 in. With 3000 cfm and 1.00 in., Table 17 shows a 1.17 bhp.

Note: The formula below the table can be used to calculate Fan Motor Heat:

3.5 X bhp = MBh

3.5 X 1.17 = 4.09 MBh

Net Total Cooling Capacity = 91.1 MBh - 4.09 = 87.01 MBh

Net Sensible Cooling Capacity = 65.9 MBh - 4.09 = 61.81 MBh

Heating Capacity

Step 1.

Calculate the building heating load using the Trane calculation form or any other standard accepted method.

Step 2.

Size the equipment using Table 11 to match the heating loads at design conditions. The following are building heating requirements:

a.Total Heating Load: 95.0 MBh

b.Outdoor Ambient (Winter): 17°F DB

c.Indoor Return Temperature: 70°F DB

d.Airflow: 3000 cfm

Table 11 indicates the mechanical heating portion of the heat pump will provide 54.8 MBh for the winter design conditions.

Step 3.

Because 54.8 MBh is less than the building’s required heating capacity, a supplementary heater must be selected. 95.0 - 54.8 = 40.2 MBh minimum heater capacity.

From Table 32, the 14.96 kW heater has a capacity of 51,058 Btu/h.

From Table 37, the 14.96 kW heater at 460V indicates the heater model number is BAYHTRL415A.

This heater will be adequate to cover the residual heat capacity needed for the application.

Air Delivery Selection

External static pressure drop through the air distribution system has been calculated to be 0.77 in. of water gauge.

From Table 31 static pressure drop through the electric heater is 0.12 in. of water (0.77 + 0.12 = .89 in.)

Enter Table 17 for TWE090A4 at 3000 cfm and .90 static pressure. The standard motor at 790 RPM will give the desired airflow.

8

SSP-PRC001-EN

Image 8
Contents Split System Heat Pumps Introduction Manufacturing ControlDesigning the Details Standardized CabinetsContents Air Handlers Offer More Flexibility Features and BenefitsCondensing Units Options Features and Benefits Odyssey a Complete Split SystemApplication Considerations Clearance RequirementsBlower Rotation Low Ambient CoolingApplication Considerations Selection Procedure Cooling CapacityHeating Capacity Air Delivery SelectionAir Handler Model Nomenclature Model Number DescriptionSplit System Heat Pump Model Nomenclature General Data General Data Heat PumpsGeneral Data Air Handlers Indoor Coil TypeIndoor Fan Type Filters Type/FurnishedAmbient Temperature 105 Entering WB CFM Air Flow Ambient Temperature 115 Enter WB CFM Air FlowPerformance Data DB F MBH SHCTons Gross Cooling Capacities SHC MBHTons Gross Cooling Capacities 7200 198 164.3 217.7 137.3 238.9 88.8 DB F MBH SHC MBH SHC MBH SHC MBH SHCDB F Gross Cooling Capacities MBh 7½ Tons TWA090A Heat Pump Only Suction Temperature F Outdoor Temp F½ Tons Gross Cooling Capacities and Capacity Curves Tons Gross Cooling Capacities and Capacity Curves Gross Cooling Capacities MBh 10 Tons TWA120A Heat Pump OnlyCapacity Curves 15 Tons TWA180B Heat Pump Only Gross Cooling Capacities MBh 15 Tons TWA180B Heat Pump OnlyCapacity Curves 20 Tons TWA240B Heat Pump Only Gross Cooling Capacities MBh 20 Tons TWA240B Heat Pump Only½, 10 Tons Gross Heating Capacities 15, 20 Tons Gross Heating Capacities Evaporator Fan Performance, Low Static Fan Drive, 5 Tons Low Static Fan Drive 5 Ton TWE060A, TWE060B Air HandleriExternal Static Pressure Inches of Water Gauge HP Oversized Motor & SheavesCFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP Evaporator Fan Performance, Low Static Fan Drive, 7½ TonsLow Static Fan Drive 7½ Tons TWE090A, B Air Handler Evaporator Fan Performance, Low Static Fan Drive, 10 Tons External Static Pressure Inches of Water Gauge 00 1.20 1.40Tons Evaporator Fan Performance CFM RPM BHPEvaporator Fan Performance, Low Static Fan Drive, 15 Tons Evaporator Fan Performance 15 Tons TWE180B Air HandlerLow Static Fan Drive 15 Ton TWE180B Air Handleri CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHPEvaporator Fan Performance, Low Static Fan Drive, 20 Tons Evaporator Fan Performance 20 Ton TWE240B Air HandlerLow Static Fan Drive 20 Tons TWE240B/TWE240E Air Handler CFM RPM BHP BHP RPM BHP RPM BHPElectric Heat Discharge Plenum and Grille Airflow CFM Sheave Position Turns Tons Unit Model No Open ClosedDischarge Plenum and Grille Assembly Throw Distance Louver Angle Deflection Position Tons Model NoCFM StraightBtuh Tons Static Pressure Drop, Auxiliary Heat CapacityAuxiliary Electric Heat Capacity Air Handler Controls ThermostatsUnit Wiring Heat Pumps Tons Unit Model No Volts PhaseElectrical Data Compressor Fan Motor Condenser Fan Motor AmpsElectrical Characteristics Motors 60Hz Air Handler Tons, Air Handler Unit Wiring, Electrical CharacteristicsUnit Wiring Air Handler Unit Wiring with Electric Heat TWE120AW Jobsite Connections TWA060/TWE060ATW-048/TWE090B TW-030/TWE060B TW-060/TWE120B TWA090A/TWE180B TWA120A/TWE240BTypical Wiring Heat Pump Single Compressor Wiring Diagram Heat Pump Dual Compressor Wiring Diagram Heat Pump Dual Compressor Wiring Diagram Air Handler Wiring Diagram Dimensional Data ½ Tons TWA090 Heat Pump. All dimensions are in inchesTons TWA120A Heat Pump. All dimensions are in inches TonsTons TWA180B Heat Pump. All dimensions are in inches Tons TWA240B Heat Pump. All dimensions are in inches Air Handler Dimensions Tons Model No½ & 10 Ton 10 Ton 10 Tons TWE060A, 090A, 120A TWE060B, 090B, 120B Air HandlersTons TWE180 Air Handlers. All dimensions are in inches Tons TWE180 Air Handlers Tons TWE240B Air Handlers Ton TWE240B Air Handlers Accessories, Electric Heater Discharge Plenum and Grille Accessories, Discharge Plenum and GrilleDischarge Plenum and Grille Dimensions in. No Heat Accessories, Subbase Subbase DimensionsAccessories, Rubber isolators Isolator DimensionsAccessories, Spring Isolators 20 Ton Spring IsolatorsAccessory Weights net lbs WeightsUnit and Corner Weights lbs Air Handlers RISMechanical Specifications Evaporator Fan Refrigeration SystemEvaporator Coil Control Options Page Trane

SSP-PRC001-EN specifications

The Trane SSP-PRC001-EN is a state-of-the-art product designed to enhance the efficiency and performance of HVAC systems. As a part of Trane’s expanding suite of smart building technologies, this device integrates advanced features and cutting-edge technology to provide optimal climate control for various applications, including commercial and industrial settings.

One of the primary features of the SSP-PRC001-EN is its ability to monitor and manage energy consumption effectively. The device employs real-time data analytics to provide insights into energy use patterns, allowing facility managers to make informed decisions that can significantly reduce operational costs. By leveraging this information, organizations can optimize their HVAC operations, leading to enhanced sustainability and compliance with environmental regulations.

Another notable characteristic of the SSP-PRC001-EN is its integration with Trane’s smart building technology. The system is designed to seamlessly connect with various sensors and building management systems, creating a comprehensive ecosystem for energy management. Its compatibility with existing infrastructure means that users can upgrade their systems without the need for extensive retrofitting, minimizing disruption while maximizing efficiency.

The SSP-PRC001-EN also boasts user-friendly interfaces that simplify operation and monitoring. Facility managers can easily access data and analytics through intuitive dashboards, which can be customized to display the most relevant information. This ease of use is critical for timely decision-making, especially in environments where rapid response to changing conditions is essential.

In terms of reliability and performance, the SSP-PRC001-EN is built to withstand demanding conditions. Designed with durability in mind, its rugged construction ensures long-lasting service, making it an ideal choice for facilities operating in various environments. Moreover, the system is engineered for flexibility, allowing for adjustments based on specific operational needs.

Overall, the Trane SSP-PRC001-EN combines advanced technology with practical features to deliver an efficient, reliable, and user-friendly solution for HVAC management. Whether for upgrading existing systems or integrating into new buildings, it stands as a testament to Trane's commitment to innovation and sustainability in the realm of climate control solutions. This product exemplifies how technological advancements can contribute to smarter building management and energy efficiency in today's demanding operational landscapes.