Emerson 200, U/300/S/12P, 160 2. 300kVA UPS Transportation Restraints Removing Procedures, A处放大图

Models: U /400/S/12P U/300/S/6P 160 200 U/300/S/12P 400KVA U /400/S/6P

1 79
Download 79 pages 37.39 Kb
Page 75
Image 75
2.300kVA UPS Transportation Restraints Removing Procedures

Appendix 1 Transportation Restraints Removing Procedures

65

5.Reinstall the installation hole cover and the lower switch baffle plate with the screws removed in step 1. You might as well install the lower switch baffle plate after UPS commissioning.

6.Reinstall the back panel of the cabinet with the screws removed in step 2. You can also carry out this step after UPS commissioning.

Transformer transportation restraints removing procedures for UPS with 12-pulse rectifier

1.Repeat the preceding steps 1 through 4 to remove the transportation restraints of the output transformer (see Figure 3).

Output A处放大图Manual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual background变压transformer Manual backgroundManual backgroundManual backgroundManual background

Phase-shifting A Manual backgroundManual backgroundManual background

移相变压A transformer

M10bolt

M12bolt

Transportation固定件 restraint

A amplifiedA放大view

Figure 3 Removing the transformer transportation restraints

2. Remove the transportation restraints of the phase-shifting transformer.

There are two transportation restraints respectively in the front and at the back, totally four, at the bottom of the phase-shifting transformer. Remove the two M10 bots at both sides and one M12 bolt in the middle of each transportation restraint, as shown in Figure 3. Remove the four transportation restraints, and then reinstall the four M12 bolts in their original positions.

3.Repeat the preceding steps 5 and 6.

2.300kVA UPS Transportation Restraints Removing Procedures

Transformer transportation restraints removing procedures for UPS with 6-pulse rectifier

1. Remove the back panel of the cabinet to reveal the output transformer, as shown in Figure 4. Retain the screws.

M10bolts螺栓

Output 变压transformer

Transportation固定件 restraint

A放大

A amplified view

A

Figure 4 Removing the output transformer transportation restraints

HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual

Page 75
Image 75