4.4 UPS Alarm Message List

Chapter 4 Operator Control And Display Panel

35

4.4 UPS Alarm Message List

Table 4-8 provides the complete list of UPS alarm messages supported for display either on the Records menu (historical data) or in the current record window (prevailing data) as described in 4.1.5 Detailed Description Of Menu Items.

 

 

 

Table 4-8 UPS alarm message list

 

 

 

 

 

Alarm message

 

Description

 

Rectifier comm. fail

Internal RS485 communication failure between monitor and rectifier

 

Mains volt. abnormal

 

Mains Voltage exceeds the upper or lower limit and results in rectifier shutdown. Check the input

 

 

line-to-neutral voltage amplitude of rectifier

 

 

 

 

Mains undervoltage

Mains voltage is undervoltage. Check the input line voltage

 

Mains freq. abnormal

 

Mains frequency is out of limit range and results in rectifier shutdown. Check the input voltage and

 

 

frequency

 

 

 

 

 

 

 

 

Battery fuse fail

 

Battery fuse flowout led to BCB tripping

 

Rectifier block

Rectifier detected faulty. Rectifier shuts down. Battery discharges

 

Rectifier overtemp.

 

The temperature of heat sink is too high to keep the rectifier running. The UPS can recover

 

 

automatically. Check the environment and ventilation

 

 

 

 

 

 

 

 

Input fuse fail

 

Input fuse blowout led to rectifier turning off

 

Control power 1 fail

UPS operates but Control Power is not available

 

Control power 2 fail

UPS operates but Redundant Control Power is not available

 

Mains phase reversed

Rectifier AC input phase sequence is reversed

 

Rectifier current limit

Rectifier overcurrent led to power limiting operating

 

Soft start fail

 

Rectifier could not start due to low DC bus voltage

 

Input filter fault

 

Filter inductor overtemperature led to filter contactor tripping

 

Filter contactor fault

Filter contactor operation abnormal

 

Filter overcurrent

 

Mains power outside the normal voltage or frequency range of the input passive filter results in filter

 

 

overcurrent. Please find out the reason for the mains power abnormality

 

 

 

 

 

 

 

REC drive cirtuit fault

Rectifier being off due to improper connection of rectifier drive cable or rectifier type setting error

 

REC input Ph. missing

Rectifier input phase missing. Check the input power connection or if the mains power is abnormal

 

DC bus over voltage

 

Rectifier and inverter were shut down because DC bus voltage is too high. Check whether there is a

 

 

fault in rectifier side

 

 

 

 

 

 

 

 

Bus capacitor overvolt

 

Bus capacitor voltage exceeds 350V, rectifier is off. Check the voltages of the two groups of bus

 

 

capacitors

 

 

 

 

 

 

 

 

EPO

 

Emergency Power Off direct access key pressed or external command received

 

Input disconnect open

Rectifier input switch open

 

Input disconnect closed

Rectifier input switch closed

 

Normal mode

Load supplied from inverter output through double conversion of the AC mains input supply

 

Source share mode

 

Load supplied from inverter output through shared double conversion of the AC mains input supply

 

 

and of the Battery supply

 

 

 

 

 

 

 

PPF online

Reactive input filter connected

 

PPF disconnecting

Reactive input filter disconnected

 

Battery mode

 

Load supplied from inverter output through battery

 

No battery

 

Check the battery and the battery wiring; check whether the BCB is closed and the BCB dry contact

 

 

is connected

 

 

 

 

 

 

 

 

Auto start

 

After UPS was shutdown at EOD, inverter auto starts when utility restore

 

Generator connected

 

The generator has been connected to the UPS

 

BCB open

 

Battery Circuit Breaker status (open)

 

BCB closed

 

Battery Circuit Breaker status (closed)

 

Battery float charging

 

Battery status (Float charge mode)

 

Battery boost charging

Battery status (Boost charge mode)

 

Battery discharging

 

Battery status (discharge mode)

 

Battery period testing

 

Automatic periodic battery maintenance discharge test (20% capacity discharge)

 

Batt. capacity testing

 

User initiated battery capacity discharge test (100% capacity discharge)

 

Batt. maint. testing

 

User initiated maintenance discharge test (20% capacity discharge)

 

UPS system testing

 

User initiated system test

 

Inverter in setting

 

Inverter starting up and synchronizing

 

Rectifier in setting

Rectifier starting up and synchronizing

 

Battery Room Alarm

 

Environment in Battery Room Needs Attention

HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual