4.4 UPS Alarm Message List
Table
|
|
| Table |
|
|
|
|
| Alarm message |
| Description |
| Rectifier comm. fail | Internal RS485 communication failure between monitor and rectifier | |
| Mains volt. abnormal |
| Mains Voltage exceeds the upper or lower limit and results in rectifier shutdown. Check the input |
|
| ||
|
|
| |
| Mains undervoltage | Mains voltage is undervoltage. Check the input line voltage | |
| Mains freq. abnormal |
| Mains frequency is out of limit range and results in rectifier shutdown. Check the input voltage and |
|
| frequency | |
|
|
| |
|
|
|
|
| Battery fuse fail |
| Battery fuse flowout led to BCB tripping |
| Rectifier block | Rectifier detected faulty. Rectifier shuts down. Battery discharges | |
| Rectifier overtemp. |
| The temperature of heat sink is too high to keep the rectifier running. The UPS can recover |
|
| automatically. Check the environment and ventilation | |
|
|
| |
|
|
|
|
| Input fuse fail |
| Input fuse blowout led to rectifier turning off |
| Control power 1 fail | UPS operates but Control Power is not available | |
| Control power 2 fail | UPS operates but Redundant Control Power is not available | |
| Mains phase reversed | Rectifier AC input phase sequence is reversed | |
| Rectifier current limit | Rectifier overcurrent led to power limiting operating | |
| Soft start fail |
| Rectifier could not start due to low DC bus voltage |
| Input filter fault |
| Filter inductor overtemperature led to filter contactor tripping |
| Filter contactor fault | Filter contactor operation abnormal | |
| Filter overcurrent |
| Mains power outside the normal voltage or frequency range of the input passive filter results in filter |
|
| overcurrent. Please find out the reason for the mains power abnormality | |
|
|
| |
|
|
| |
| REC drive cirtuit fault | Rectifier being off due to improper connection of rectifier drive cable or rectifier type setting error | |
| REC input Ph. missing | Rectifier input phase missing. Check the input power connection or if the mains power is abnormal | |
| DC bus over voltage |
| Rectifier and inverter were shut down because DC bus voltage is too high. Check whether there is a |
|
| fault in rectifier side | |
|
|
| |
|
|
|
|
| Bus capacitor overvolt |
| Bus capacitor voltage exceeds 350V, rectifier is off. Check the voltages of the two groups of bus |
|
| capacitors | |
|
|
| |
|
|
|
|
| EPO |
| Emergency Power Off direct access key pressed or external command received |
| Input disconnect open | Rectifier input switch open | |
| Input disconnect closed | Rectifier input switch closed | |
| Normal mode | Load supplied from inverter output through double conversion of the AC mains input supply | |
| Source share mode |
| Load supplied from inverter output through shared double conversion of the AC mains input supply |
|
| and of the Battery supply | |
|
|
| |
|
|
| |
| PPF online | Reactive input filter connected | |
| PPF disconnecting | Reactive input filter disconnected | |
| Battery mode |
| Load supplied from inverter output through battery |
| No battery |
| Check the battery and the battery wiring; check whether the BCB is closed and the BCB dry contact |
|
| is connected | |
|
|
| |
|
|
|
|
| Auto start |
| After UPS was shutdown at EOD, inverter auto starts when utility restore |
| Generator connected |
| The generator has been connected to the UPS |
| BCB open |
| Battery Circuit Breaker status (open) |
| BCB closed |
| Battery Circuit Breaker status (closed) |
| Battery float charging |
| Battery status (Float charge mode) |
| Battery boost charging | Battery status (Boost charge mode) | |
| Battery discharging |
| Battery status (discharge mode) |
| Battery period testing |
| Automatic periodic battery maintenance discharge test (20% capacity discharge) |
| Batt. capacity testing |
| User initiated battery capacity discharge test (100% capacity discharge) |
| Batt. maint. testing |
| User initiated maintenance discharge test (20% capacity discharge) |
| UPS system testing |
| User initiated system test |
| Inverter in setting |
| Inverter starting up and synchronizing |
| Rectifier in setting | Rectifier starting up and synchronizing | |
| Battery Room Alarm |
| Environment in Battery Room Needs Attention |