Chapter 3 Electrical Installation

Chapter 3 Electrical Installation

15

Chapter 3 Electrical Installation

This chapter introduces the electrical installation of the HIPULSE U UPS, including the procedures or methods for power cabling and control cabling, and the distance from floor to connection point.

The UPS requires both power cabling and control cabling once it has been mechanically installed. All control cables, whether screened or not, should be run separate from the power cables in metal conduits or metal ducts which are electrically bonded to the metalwork of the cabinets to which they are connected.

3.1 Power Cabling

3.1 Power CablingWarning

BEFORE CABLING UP THE UPS, ENSURE THAT YOU ARE AWARE OF THE LOCATION AND OPERATION OF THE EXTERNAL ISOLATORS THAT CONNECT THE UPS INPUT/BYPASS SUPPLY TO THE MAINS DISTRIBUTION PANEL. CHECK THAT THESE SUPPLIES ARE ELECTRICALLY ISOLATED, AND POST ANY NECESSARY Warning SIGNS TO PREVENT THEIR INADVERTENT OPERATION.

For cable entry, refer to 2.3.5 Cable Entry.

3.1.1 System Configuration

The power cables of the system must be size with respect to the following description:

Module input cables

The input cables must be sized for the maximum input current, including the maximum battery recharge current, given in the Table 3-1, with respect to the module rating and the input AC voltage.

Module bypass and output cables

The bypass and output cables must be sized for the nominal output current, given in the Table 3-1, with respect to the module rating and the output AC voltage.

Battery cables

Each UPS module has its own battery which is connected using two cables, one positive and one negative. The battery cables must be sized for the battery discharge current at the end-of-discharge voltage, as given in Table 3-1 with respect to the module rating.

3.1.2 Cable Rating

The power cables can be sized to suit the UPS module rating according to Table 3-1.

Table 3-1 UPS module power cable rating

 

 

 

 

Nominal current: Amps

 

 

 

Busbar stud size

 

 

 

UPS rating

Input mains with full battery recharge

Bypass/output at full load

Battery at

Input/output

Battery

Torque

 

 

(kVA)

(subtract 5% for 12-pulse)

minimum battery

cables

 

 

 

 

 

cables

(Nm)

 

 

 

380V

400V

415V

380V

400V

415V

voltage (400Vac)*

Bolt

Ø

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

160

341

324

312

243

231

222

464

M10

11

M10 bolt

26

 

 

 

 

 

 

 

 

 

 

 

 

 

 

200

426

405

390

304

289

278

580

M10

11

M10 bolt

26

 

 

 

 

 

 

 

 

 

 

 

 

 

 

300

634

602

572

456

434

413

870

M12

13

M12 bolt

50

 

 

 

 

 

 

 

 

 

 

 

 

 

 

400

848

803

772

607

578

556

1160

M12

13

M12 bolt

50

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Note*: Maximum battery discharge current at 380Vac supply increases by 3%, and for a 415Vac supply decreases by 3%