Emerson U/300/S/6P, 400KVA Start-Up Procedure Into Normal Mode, Start-Up Procedure Into ECO Mode

Models: U /400/S/12P U/300/S/6P 160 200 U/300/S/12P 400KVA U /400/S/6P

1 79
Download 79 pages 37.39 Kb
Page 51
Image 51
5.2 Start-Up Procedure (Into Normal Mode)

Chapter 5 Operating Instructions

41

5.2 Start-Up Procedure (Into Normal Mode)

This procedure must be followed when turning on the UPS from a fully powered down condition, that is, where the load is not being initially supplied at all or where supplied by the maintenance bypass switch. It is assumed that the installation is complete, the system has been commissioned by authorized personnel and the external power isolators are closed.

Warning – Mains voltage will be applied to UPS output terminals

This procedure results in mains voltage being applied to the UPS output terminals.

Isolate and attach warning labels to any downstream load connections, as applicable.

1.Open the UPS door to gain access to the power switches.

2.Close the bypass switch Q2 and output switch Q5. Close also any external output isolation switches, where used.

The LCD display becomes active and after initialization, the UPS output is powered from the bypass. At this point, the status of the LEDs is as described in Table 5-1.

Table 5-1

LED status

 

 

 

LED

 

Status

Bypass LED

 

Steady green

Load LED

 

Steady green

Battery LED

 

Steady red

Alarm LED

 

Steady yellow

 

 

 

3. Close the input switch Q1.

The rectifier LED flashes during the startup of rectifier and becomes steady green once the rectifier reaches normal operation state after about 15s.

4.Verify the bus voltage and the battery polarities, and close the BCB, which is located in the BCB box.

5.Following battery availability being detected by the UPS, the red battery LED extinguishes.

6.Open (or confirm open) the internal maintenance bypass switch Q3.

7.Press and hold the INVERTER ON button for two seconds.

The inverter will start up and the inverter LED flashes while it synchronizes to the bypass voltage frequency.

After the inverter is ready, the UPS transfers from bypass to inverter, the bypass LED turns off, and the inverter LED becomes steady green.

8.Check that no “Warning” message is displayed in the top right corner of the LCD screen and the status of the LEDs is as described in Table 5-2.

Table 5-2

LED status

 

 

 

LED

 

Status

Rectifier LED

 

Steady green

Bypass LED

 

Off

Battery LED

 

Off

Inverter LED

 

Steady green

Load LED

 

Steady green

Alarm LED

 

Off

The UPS is now operating in Normal mode

5.3 Start-Up Procedure (Into ECO Mode)

Apply only to a single module UPS and when programmed by the commissioning engineer to perform ECO mode control of the power delivered to the load.

HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual

Page 51
Image 51
Emerson U/300/S/6P, U/300/S/12P, U /400/S/12P, 400KVA Start-Up Procedure Into Normal Mode, Start-Up Procedure Into ECO Mode