Emerson 400KVA, U/300/S/12P, U/300/S/6P Battery Temperature Sensor Optional, 5 BCB box connection

Models: U /400/S/12P U/300/S/6P 160 200 U/300/S/12P 400KVA U /400/S/6P

1 79
Download 79 pages 37.39 Kb
Page 60
Image 60
Figure 6-5 BCB box connection

50

Chapter 6 Battery

660

167

4-Ф13 Knockout

Figure 6-4 Installation hole dimensions for floor mounting of BCB box of 300/400kVA UPS (unit: mm)

The battery circuit breaker (BCB) box contains a BCB and a BCB control board (ULK366SC1).

The BCB box is fitted as close as possible to the battery and connected to the UPS, as illustrated in Figure 6-5.

 

UPS

 

 

 

 

 

FB

 

BCB status feedback

GND

 

BCB connection detection

 

OL

 

 

+12V

 

Battery temperature sensing 1

 

TMP_T

 

 

GND

 

Battery temperature sensing 2

 

LM355+

 

 

LM355+ GND

 

 

BCB drive

 

DRV

 

 

 

DRV_ GND

 

Not connected

NC

 

NC

 

 

 

 

 

BCB control board

6.10 Battery Temperature Sensor (Optional)Manual background TMP12Z

TMP12Z

TMP12Z

TMP12Z

Figure 6-5 BCB box connection

Note: The control cables from the UPS to the BCB control board must be made using the accessory cable of the BCB, which is a shielded cable located in a separate conduit to that containing the battery power cables. The cable shield must be earthed to prevent induced noise affecting the control operation, and a separate safety earth must be connected between the UPS and BCB box.

6.10 Battery Temperature Sensor (Optional)

A battery temperature sensor (model: TMP12Z) supplied separately from the BCB is connected with the UPS logic through the BCB control board. For the connection, see Figure 6-5.

With this feature fitted, the nominal float voltage supplied to the battery is adjusted so as to be inversely proportional to the ambient temperature of the battery cabinet or battery room. This prevents the battery being over charged at high ambient temperatures.

HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual

Page 60
Image 60
Emerson 400KVA, U/300/S/12P, U /400/S/12P, U/300/S/6P, U /400/S/6P Battery Temperature Sensor Optional, 5 BCB box connection