Chapter 4 Operator Control And Display Panel

31

 

 

 

 

 

 

 

 

 

 

 

 

No.

 

 

Menu

 

Item

 

Explanation

 

 

 

 

 

 

 

 

 

 

This setting applies to RS485 communication and the

 

 

 

 

 

 

 

 

 

 

“one-to-multiple points” communication mode of parallel system. It is

 

 

 

 

 

 

Communication address

 

required to set the parameter Host communication mode of COM1 in

 

 

 

 

 

 

 

 

parallel system to Multipoint to point using background software

 

 

 

 

 

 

 

 

 

 

before setting the communication address of each UPS module

 

 

 

 

 

 

 

 

 

 

Reserved modem function. No need to change the default setting

 

 

 

 

 

 

 

 

Communication mode

 

 

 

 

 

 

 

 

 

 

“RS232”

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(reserved)

 

 

 

 

 

 

 

 

Callback times

 

 

 

9

 

 

Settings

 

Phone No.1

(reserved)

 

 

 

 

 

Phone No.2

(reserved)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Phone No.3

(reserved)

 

 

 

 

 

 

 

 

 

 

Modifies password for the Command menu.

 

 

 

 

 

 

 

 

 

 

Use the Shift key (F1) to highligt Command Password, press the

 

 

 

 

 

 

 

 

 

 

Enter key (F4).

 

 

 

 

 

 

 

 

Command password

 

Enter each old password digit with up arrow (F2) and use right arrow

 

 

 

 

 

 

 

 

(F3) to access next field. Press the Enter key (F4) when all digits

 

 

 

 

 

 

 

 

 

 

have been entered.

 

 

 

 

 

 

 

 

 

 

Follow prompts and repeat the process for new password

 

 

 

 

 

 

 

 

 

 

Manually initiates battery maintenance test, which will lead to the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

battery being partly discharged, for rough assessment of the battery

 

 

 

 

 

 

 

 

capacity.

 

 

 

 

 

 

 

 

 

 

The Load must exceed 20% and be less than 80% of rated UPS

 

 

 

 

 

 

 

 

 

 

capacity, and the battery must have been float charging for 5 hours or

 

 

 

 

 

 

Battery maintenance test

 

more.

 

 

 

 

 

 

 

 

 

 

Use the Shift key (F1) and up and down arrow keys (F2, F3) to

 

 

 

 

 

 

 

 

 

 

highligt the desired test. Press the Enter key (F4).

 

 

 

 

 

 

 

 

 

 

Enter each password digit with up arrow (F2) and use right arrow (F3)

 

 

 

 

 

 

 

 

to access next field. Press the Enter key (F4) when all digits have

 

 

 

 

 

 

 

 

 

 

been entered

 

 

 

 

 

 

 

 

 

 

Manually initiates battery capacity test, which will lead to the battery

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

being completely discharged, for accurate assessment of the battery

 

 

 

 

 

 

 

 

capacity.

 

 

 

 

 

 

 

 

 

 

The Load must exceed 20% and be less than 80% of rated UPS

 

 

 

 

 

 

 

 

 

 

capacity, and the battery must have been float charging for 5 hours or

 

 

 

 

 

 

Battery capacity test

 

more.

 

 

10

 

 

Command*

 

 

 

Use the Shift key (F1) and up and down arrow keys (F2, F3) to

 

 

 

 

 

 

 

highligt the desired test. Press the Enter key (F4).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Enter each password digit with up arrow (F2) and use right arrow (F3)

 

 

 

 

 

 

 

 

to access next field. Press the Enter key (F4) when all digits have

 

 

 

 

 

 

 

 

 

 

been entered

 

 

 

 

 

 

 

 

 

 

Manually initiates the system test.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

System test

 

The user actives this function, after 5 seconds, a pop window will

 

 

 

 

 

 

 

 

 

appear to show the result of this diagnosis: Rectifier, Inverter, Monitor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OK or Fault

 

 

 

 

 

 

 

 

 

 

Manually stop the test, including maintenance test, capacity test and

 

 

 

 

 

 

Stop testing

 

 

 

 

 

 

 

 

system test

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Manually initiates freshening charge, when the battery is not in boost

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

charge state.

 

 

 

 

 

 

 

 

 

 

Use the Shift key (F1) and up and down arrow keys (F2, F3) to

 

 

 

 

 

 

 

 

Freshening charge

 

highlight this item. Press the Enter key (F4).

 

 

 

 

 

 

 

 

 

 

Enter each password digit with up arrow (F2) and use right arrow (F3)

 

 

 

 

 

 

 

 

to access next field. Press the Enter key (F4) when all digits have

 

 

 

 

 

 

 

 

 

 

been entered

 

 

 

 

 

 

 

 

 

Manually stop the freshening charge

 

 

 

 

 

 

 

 

Stop freshening charge

 

 

 

 

 

 

 

 

Monitor VersionVxxx

 

Displays UPS firmware versions, including inverter, rectifier,

 

 

 

 

 

 

 

 

Rectifier VersionVxxx

 

 

 

11

 

 

Version

 

 

monitoring board firmware versions

 

 

 

 

 

Inverter VersionVxxx

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Displays UPS model information; for example, 380V-50Hz

 

 

 

 

 

 

 

 

UPS model

 

 

Note*: password controlled. The default passward is “12345”, please enter Settings=>Command password to change the password. In case the password is lost, please contact the local customer service center of Emerson

HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual

Page 41
Image 41
Emerson 160, 200 Explanation This setting applies to RS485 communication, Communication address, Been entered, OK or Fault