Emerson U/300/S/12P, U /400/S/12P, U/300/S/6P, 400KVA Electrical Characteristics Inverter Output

Models: U /400/S/12P U/300/S/6P 160 200 U/300/S/12P 400KVA U /400/S/6P

1 79
Download 79 pages 37.39 Kb
Page 70
Image 70
8.6 Electrical Characteristics (Inverter Output)

60

Chapter 8 Specifications

8.6 Electrical Characteristics (Inverter Output)

Table 8-6 Electrical characteristics (inverter output)

 

 

Item

 

 

Unit

 

 

 

 

 

Power rating (kVA)

 

 

 

 

 

 

 

 

 

160

 

 

200

 

 

300

 

 

400

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rated mains voltage1

 

Vac

 

 

 

 

380, 400, or 415

 

 

 

 

Supply

-

 

 

 

 

 

Three phase with neutral

 

 

 

 

Frequency2

 

Hz

 

 

 

 

 

50 or 60

 

 

 

 

Rated Power at cos = 0.9

 

kVA

 

160

 

200

 

300

 

400

 

 

Rated Power at cos = 1

 

kW

 

144

 

180

 

270

 

360

 

 

 

 

 

 

Min,

 

 

 

 

 

60,

1.10

 

 

 

 

 

Three-phase transient overload3

 

 

 

 

 

 

10, 1.25

 

 

 

 

 

 

I/In

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1, 1.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Maximal non linear load allowed4

-

 

 

 

 

 

 

100%Pn

 

 

 

 

Voltage stability, steady State test3

%

 

 

 

 

 

 

±1

 

 

 

 

 

 

Voltage stability, transient test 5

%

 

 

 

 

 

 

±5

 

 

 

 

 

 

Maximum rate of charge of frequency6

 

Hz/s

 

 

 

 

 

0.1

 

 

 

 

 

Note:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.

Factory set 380V 400 or 415 voltages with software setting.

 

 

 

 

 

 

 

 

 

2.

Factory set at 50Hz 60 Hz with software setting.

 

 

 

 

 

 

 

 

 

 

 

3.

IEC62040-3 (5.3.2).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4.

IEC62040-3 (ANNEX E).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5.

IEC62040-3 (5.3.1), also for 0~100~0%, load transient, restore time 20 ms to 1%.

 

 

 

 

 

 

 

6.

Factory set at 0.1Hz/s; up to 1Hz/s with software setting

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8.7 Electrical Characteristics (Bypass Input Mains)

Table 8-7 Electrical characteristics (bypass input mains)

 

Item

 

 

Unit

 

 

 

 

 

 

Power rating (kVA)

 

 

 

 

 

 

 

 

 

 

 

160

 

 

200

 

 

 

 

300

 

 

 

400

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rated mains voltage1

 

Vac

 

 

 

 

 

380, 400, or 415

 

 

 

 

 

 

 

 

Supply

-

 

 

 

 

 

 

Three phase with neutral

 

 

 

 

 

 

 

Rated current

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

380Vac

 

A

 

243

 

 

304

 

 

 

 

456

 

 

 

607

 

 

400Vac

 

 

231

 

 

289

 

 

 

 

433

 

 

 

577

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

415Vac

 

 

 

 

 

 

 

 

 

 

 

 

 

416

 

 

 

 

 

 

 

 

 

 

 

222

 

 

278

 

 

 

 

 

 

 

554

 

 

Bypass voltage tolerance2

%

 

 

 

 

Default upper limit: 15%; default lower limit: -20%

 

 

 

 

Delay time to recognise bypass

 

s

 

 

 

 

 

 

2

 

 

 

 

 

 

 

 

 

 

voltage returned to window

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Inverter output voltage window

%

 

 

 

 

 

 

 

±5

 

 

 

 

 

 

 

 

 

 

Frequency3

 

Hz

 

 

 

 

 

 

50 or 60

 

 

 

 

 

 

 

 

Input frequency tolerance 4

%

 

 

 

 

 

 

 

±5

 

 

 

 

 

 

 

 

 

 

Maximum frequency slew rate

 

Hz/s

 

 

 

 

 

 

1

 

 

 

 

 

 

 

 

 

 

Current rating of neutral cable

-

 

 

 

 

 

 

 

1.3In

 

 

 

 

 

 

 

 

Protection, bypass line

-

 

The bypass line should be protected using an external device in the input distribution

 

 

system. This device should be sized to discriminate with the load protection

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Transient overload

 

ms

10

 

20

50

100

200

 

500

1000

2000

 

5000

 

 

I/In

14.3

 

12.6

11.0

10.0

9.0

 

8.0

7.1

 

6.6

 

5.7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Note:

1.Factory set 380V. 400 or 415 voltages with software setting.

2.Other values in -20%~15% with software setting.

3.Factory set at 50Hz 60 Hz with software setting.

4.Other values -5%~5%with software setting

HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual