22 | Chapter 3 Electrical Installation |
Table 3-5 Description of dry contact output port
Position | Name | Description |
J13.2 | BFP_O | Bypass feedback protection relay (NO) |
J13.3 | BFP_S | Bypass feedback protection relay center |
J13.4 | BFP_C | Bypass feedback protection relay (NC) |
J21.2 | INV_O | On inverter dry contact relay (NO) |
J21.3 | INV_S | On inverter dry contact relay center |
J21.4 | INV_C | On inverter dry contact relay (NC) |
J25.2 | ACF_O | Main input voltage or frequency fault relay (NO) |
J25.3 | ACF_S | Main input voltage or frequency fault relay center |
J25.4 | ACF_C | Main input voltage or frequency fault relay (NC) |
|
|
|
Note
All auxiliary cables must be double insulated. Wire should be 0.5~1.5mm2 stranded.
EPO input port (X2)
The UPS has an Emergency Power Off (EPO) function that operates by a button on the UPS door or by a remote contact provided by the user.
The X2 slot, shown in Figure
Figure 3-7 EPO input port
Table 3-6 Description of EPO input port
Position | Name | Description |
J28.1 | EPO_NC | EPO activated when opened to J28.2 |
J28.2 | EPO_NC | EPO activated when opened to J28.1 |
J28.3 | EPO_NO | EPO activated when shorted to J28.4 |
J28.4 | EPO_NO | EPO activated when shorted to J28.3 |
The remote EPO facility is connected to the normally open or normally closed remote stop switch between these two terminals using shielded cable. If this function is not used, terminals J28: 3&4 must be opened and J28: 1&2 must be closed.
Note
The emergency stop action within the UPS shuts down the rectifier, inverter and static bypass. It does not internally disconnect the input power supply. To disconnect ALL power to the UPS, open the upstream feeder breaker(s) when the remote EPO is activated.
Normally closed
Auxiliary DC power output port (X5)
The auxiliary DC power output port X5 provides auxiliary DC power for optional SNMP card. The voltage is between 9V to 12V. The maximum current is 500mA.
Communication ports
The communication ports include the serial ports
HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual