Chapter 8

Specifications

59

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power rating (kVA)

 

 

 

 

 

 

Item

 

Unit

160

160

200

200

 

300

300

400

 

400

 

 

 

 

 

(6-pulse)

(12-pulse)

(6-pulse)

(12-pulse)

(6-pulse)

(12-pulse)

(6-pulse)

(12-pulse)

 

Rated input power 2

 

kVA

197

191

245

236

 

365

354

488

 

469

 

 

Rated input current2

 

A

298

289

371

358

 

551

535

739

 

708

 

 

Maximal input Power3

 

kVA

246

239

306

295

 

420

407

609

 

584

 

 

Maximal input

 

A

373

362

464

447

 

634

616

931

 

885

 

 

current3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Duration of

 

 

 

 

 

 

 

 

 

 

 

 

 

 

progressive power

 

s

 

 

 

 

5~300

 

 

 

 

 

 

walk-in4

 

 

 

 

 

 

 

 

 

 

 

 

 

Note:

1. With mains at -15% and suggested battery elements the UPS maintains the output rated voltage at rated load but cannot guarantee float charge to battery; the battery does not discharge.

2. IEC62040-3 (5.2.2): UPS, rated load, input rated voltage 380V, no current to battery.

3. IEC62040-3 (5.2.2): UPS, rated load or overload, input rated voltage 380V, battery on boost charge with maximal allowed current.

4. Set by dedicated background software

8.5 Electrical Characteristics (DC Intermediate Circuit)

Table 8-5 Electrical characteristics (DC intermediate circuit)

 

Item

 

Unit

 

Power rating (kVA)

 

 

 

160

200

 

300

400

 

 

 

 

 

 

Voltage range for inverter operation

 

Vdc

 

 

320~490

 

 

Recommended number of lead-acid cells 12

 

 

 

192 (380Vac)

 

 

 

pcs

 

198 (400Vac)

 

 

 

 

 

 

204 (415Vac)

 

 

 

 

 

 

 

 

 

 

 

 

 

432 (380Vac)

 

 

Recommended float charge voltage 2.25V/el.1

 

Vdc

 

446 (400Vac)

 

 

 

 

 

 

459 (415Vac)

 

 

 

 

 

 

 

 

 

 

 

 

 

451 (380Vac)

 

 

Recommended boost charge voltage 2.35V/el.1

 

Vdc

 

465 (400Vac)

 

 

 

 

 

 

479 (415Vac)

 

 

 

 

 

 

 

 

 

 

 

 

 

461 (380Vac)

 

 

Maximum voltage on manual charge 2.40 V/el.1

 

Vdc

 

475 (400Vac)

 

 

 

 

 

 

490 (415Vac)

 

 

 

 

 

 

 

 

 

 

 

 

 

471 (380Vac)

 

 

End-of-discharge voltage 2.45V/el.1

 

Vdc

 

485 (400Vac)

 

 

 

 

 

 

500 (415Vac)

 

 

 

 

 

 

 

 

 

 

Max boost charge duration 3

 

min

 

 

480~1800

 

 

Freshening charge duration3

 

h

 

 

1~36

 

 

Boost-float threshold current 3

 

A

 

0.001C~0.025C

 

 

Ripple voltage superimposed 4

%

 

 

≤1

 

 

Note:

 

 

 

 

 

 

 

1.(According to rated voltage).

2.Factory set for rated 380V, different cells number and voltage per cell may be set by configuration software.

3.Set by software.

4.Battery disconnected, RMS percentage value referred to DC voltage