Emerson U/300/S/12P, U /400/S/12P, 200 3. 400kVA UPS Transportation Restraints Removing Procedures

Models: U /400/S/12P U/300/S/6P 160 200 U/300/S/12P 400KVA U /400/S/6P

1 79
Download 79 pages 37.39 Kb
Page 77
Image 77
3. 400kVA UPS Transportation Restraints Removing Procedures

Appendix 1 Transportation Restraints Removing Procedures

67

3. 400kVA UPS Transportation Restraints Removing Procedures

Transformer transportation restraints removing procedures for UPS with 6-pulse rectifier

1.Open the front door of the main cabinet, remove the lower switch baffle plate and the installation hole covers, as shown in Figure 7. Retain the screws.

Installation hole covers

Figure 7 Removing the installation hole covers

2.Remove the back panel of the main cabinet to reveal the output transformer, then remove the two transportation restrains at the back of the output transformer, as shown in Figure 8.

Output transformer

A

Bolt (2 pcs) Transportation restraint

A amplified view

Transportation restraints

Figure 8 Removing the two transportation restraints at the back

HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual

Page 77
Image 77
Emerson U/300/S/12P, U /400/S/12P 3. 400kVA UPS Transportation Restraints Removing Procedures, Installation hole covers