Figure 5 Opening the front door and removing the back panel

66Appendix 1 Transportation Restraints Removing Procedures

2.There is a transportation restraint respectively on the right side and left side at the bottom of the output transformer. Remove the two M10 bolts of each transportation restraint, as shown in Figure 4.

3.Reinstall the back panel of the cabinet with the screws removed in step 1. This step can also be done after UPS commissioning.

Transformer transportation restraints removing procedures for UPS with 12-pulse rectifier

The removing procedures of the output transformer transportation restraints of 300kVA UPS with 12-pulse rectifier are the same as those of 300kVA UPS with 6-pulse rectifier. The removing procedures of the transportation restraints of the phase-shifting transformer are as follows:

1.Open the front door and remove the back panel of the side cabinet to reveal the phase-shifting transformer, as shown in Figure 5. Retain the screws.

Phase移相-shifting变压

Phase移相-shifting

transformer

transformer

Open the front door

RemoveOpen thebackdoorpanel

Figure 5 Opening the front door and removing the back panel

2.There are two transportation restraints respectively in the front and at the back, totally four, at the bottom of the phase-shifting transformer. Remove the two M10 bots at both sides and one M12 bolt in the middle of each transportation restraint, as shown in Figure 6. Remove the four transportation restraints, and then reinstall the four M12 bolts in their original positions.

M12bolt

 M10螺bolt栓Manual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual background M10bolt

Transportation定件 restraint

Phase移相-shifting变压transformer

A放大

A amplified view

A

Figure 6 Removing the phase-shifting transformer transportation restraints

3.Reinstall the front and back doors of the side cabinet with the screws removed in step 1. This step can also be done after UPS commissioning.