36 | Chapter 4 Operator Control And Display Panel |
| Alarm message |
| Description |
| REC FLASH UPDATE | Ongoing update of rectifier firmware | |
| INV FLASH UPDATE | Ongoing update of inverter firmware | |
| MONITOR FLASH |
| Ongoing update of monitor firmware |
| UPDATE |
| |
|
|
| |
|
|
|
|
| Unit off confirm |
| Prompt to press the Enter key (F4) to acknowledge that the UPS will be disconnected from other |
|
| paralleled UPS modules | |
|
|
| |
|
|
|
|
| System off confirm |
| Prompt to press the Enter key (F4) to acknowledge that the all paralleled UPS will be disconnected |
|
| from the load | |
|
|
| |
| Fault reset |
| FAULT CLEAR direct access key pressed |
| Alarm silence |
| SILENCE ON/OFF direct access key pressed |
| Turn on fail |
| Inverter failed to turn on when INVERTER ON direct access key was pressed. This may be as a |
|
| result of Invalid Operation (Maintenance bypass on) or DC bus or rectifier not ready | |
|
|
| |
|
|
|
|
| Alarm reset |
| FAULT CLEAR or SILENCE ON/OFF direct access key pressed |
| Transfer confirm |
| Prompt to press the Enter key (F4) to acknowledge that an interrupted load transfer to bypass will |
|
| happen | |
|
|
| |
|
|
| |
| Transfer cancel | Prompt to press the ESC key (F4) to avoid that an interrupted load transfer to bypass will happen | |
| Manual turn on |
| Manual Turn On through operator control and display panel |
| Manual turn off |
| Manual Turn Off through operator control and display panel |
| Battery ground fault |
| Battery leakage to ground detected (option) |
| Protocol version clash | Firmware incompatibility between Monitor Board and Digital Signal Processor Board | |
| Setting save error |
| History records not saved. (Reserved) |
| Battery overtemp. | The Battery temperature is over limit. Check the battery temperature and ventilation | |
| Ambient overtemp. | The Ambient temperature is over limit. Check the ventilation of UPS room | |
| Battery fault |
| Battery detected faulty (Reserved) |
| Battery maintained |
| Battery test failed, Battery should be replaced |
|
|
| Before the end of discharge, battery undervoltage |
| Battery low |
| battery should have the capacity for 3 minutes discharging with full load. The time is |
|
|
| from 3 to 60 minutes. Shut down the load in time |
|
|
|
|
| Battery end of discharge |
| Inverter turned off due to low battery voltage. Check the utility failure and try to recover it |
| Inverter comm. fail |
| Internal RS485 communication failure between monitor and inverter |
|
|
| The CAN communication between different UPSs within a parallel system fails. 1.Check if there are |
| Parallel comm. fail |
| some UPSs not powered on in the parallel system. If so, power on these UPSs and check if the |
|
|
| alarm disappears. 2. Press the FAULT CLEAR push button |
|
|
|
|
|
|
| This alarm is triggered by an inverter software routine when the amplitude or frequency of bypass |
|
|
| voltage is beyond the normal range. The amplitude threshold is fixed for positive and negative 10% |
|
|
| rating. |
|
|
| This alarm automatically resets once the bypass voltage goes normal. 1. First verify that the bypass |
| Bypass unable to trace |
| voltage and frequency displayed on the operator control and display panel is within the selected |
|
|
| range. Note here the rated voltage and frequency are specified by the system voltage level and |
|
|
| output frequency level respectively. 2. If the displayed voltage is believed to be abnormal, then verify |
|
|
| the bypass voltage and frequency presented to the UPS. Check the external supply if it is found to |
|
|
| be faulty |
|
|
|
|
|
|
| This alarm is triggered by an inverter software routine when the amplitude or frequency of bypass |
|
|
| voltage exceeds the limit. This alarm automatically resets once the bypass voltage goes normal. |
|
|
| First check if there are some relevant alarms such as Bypass disconnect open, Bypass phase |
|
|
| reverse. If they appear, solve them first. 1. Then verify that the bypass voltage and frequency |
| Bypass abnormal |
| displayed on the operator control and display panel is within the bypass limit. Note here the rated |
|
| voltage and frequency are specified by the system voltage level and output frequency level | |
|
|
| |
|
|
| respectively. 2. If the displayed voltage is believed to be abnormal, then verify the bypass voltage |
|
|
| and frequency presented to the UPS. Check the external bypass supply if it is found to be faulty. If |
|
|
| the utility is likely to trigger this alarm frequently, the bypass limit can be changed a little larger |
|
|
| through the configuration software according to the customer’s agreement |
|
|
|
|
|
|
| This alarm is triggered by an inverter software routine when the inverter and bypass waveforms are |
|
|
| misaligned by more than 6 degrees in phase. This alarm resets automatically once the condition is |
| Inverter asynchronous |
| no longer true. 1. First check if the alarm Bypass unable to trace or Bypass abnormal occurs. If so, |
|
| solve it first. | |
|
|
| |
|
|
| 2. Verify the waveform of the bypass voltage. If it is too distorted, ask the customer to verify and seek |
|
|
| any possible measurements |
| Inverter output abnormal |
| Inverter output voltage beyond limits. Load transfers to bypass |
HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual