58

Chapter 8 Specifications

Chapter 8 Specifications

This chapter provides the specifications of the HIPULSE U UPS.

8.1 Conformity And Standard

Table 8-1 Conformity and standard

Description

Year

Normative references

Safety requirements

1999

IEC60950-1, IEC62040-1-1, UL1778

EMC

2005

IEC/EN62040-2

Design and test methods

1999

IEC62040-3

8.2 Environmental Requirements

Table 8-2 Environmental requirements

 

Item

 

 

Unit

 

 

 

 

Power rating (kVA)

 

 

 

 

 

 

 

160

 

200

 

300

 

 

400

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Operating Temperature

 

°C

0~40

 

 

 

 

 

 

 

 

 

Maximal temperature for 8hr day

 

°C

40°C (derate power by 1.5% per °C between 40°C and 50°C

 

 

 

Mean Temperature for 24hr

 

°C

Maximally 35

 

 

 

 

 

 

 

 

Relative humidity

-

 

 

≤95% at 20°C

 

 

 

 

 

 

 

 

Altitude of operation

 

m

 

≤1000m asl (derate power by 1% per 100m between 1000m and 2000m)

 

Storage temperature and transport

 

°C

 

-25 to 70

 

 

 

 

 

 

 

 

temperature

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8.3 Mechanical Characteristics

Table 8-3 Mechanical characteristics

 

 

 

 

 

 

 

 

 

Power rating (kVA)

 

 

 

 

Item

 

 

Unit

 

160

160

200

200

 

300

300

400

400

 

 

 

 

 

 

(6-pulse)

(12-pulse)

(6-pulse)

(12-pulse)

 

 

(6-pulse)

(12-pulse)

(6-pulse)

(12-pulse)

 

Height

 

mm

 

 

 

1900

 

 

 

 

Width

 

mm

1250

1640

1250

1640

 

1640

2280

2280

2280

 

Depth

 

mm

 

 

 

 

875

 

 

 

 

Weight

 

kg

1200

1725

1350

2000

 

1600

2200

2100

2750

 

Ventilation

-

 

 

 

 

By internal

intake fans

 

 

 

 

Airflow

 

m3/h

2590

2750

2750

2910

 

5350

5350

6150

6150

 

Cable entry

-

 

 

 

Bottom or either side (top optional)

 

 

8.4 Electrical Characteristics (Input Rectifier)

Table 8-4 Electrical characteristics (input rectifier)

 

 

 

 

 

 

 

 

Power rating (kVA)

 

 

 

 

Item

 

Unit

 

160

160

200

200

300

300

400

400

 

 

 

 

 

(6-pulse)

(12-pulse)

(6-pulse)

(12-pulse)

(6-pulse)

(12-pulse)

(6-pulse)

(12-pulse)

 

Rated mains voltage

 

Vac

380, 400,

or 415

 

 

 

 

 

 

 

Supply

-

 

Three phase without neutral

 

 

 

 

 

 

Input voltage

%

 

±15, (maxmally, from 290Vac to 498Vac)

 

 

 

 

 

tolerance 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Frequency

 

Hz

 

50 or 60

 

 

 

 

 

 

 

 

Input frequency

 

Hz

45~65

 

 

 

 

 

 

 

 

tolerance

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual