4.2.2 Primary Screen

Chapter 4 Operator Control And Display Panel

33

4.2.2 Primary Screen

After the UPS starts and finishes system test, the primary screen will appear, as shown in Figure 4-5. For details about the primary screen, refer to 4.1.5 Detailed Description Of Menu Items.

 

 

 

 

 

 

 

 

 

 

 

 

HIPULSE U

2006-01-01

 

12:30:36

 

 

 

 

200kVA-3X3

 

Unit #1

 

Normal

 

 

 

 

 

Main

Bypass

Output

 

 

 

 

 

 

A(AB)

B(BC)

C(CA)

 

 

 

 

Vphase V

220

220

 

220

 

 

 

 

Iphase

A

20.5

20.5

 

20.5

 

 

 

 

Freq. Hz

 

50.1

50.1

 

50.1

 

 

 

 

Vline V

 

380

380

 

380

 

 

 

 

P. F.

 

0.99

0.99

 

0.99

 

 

 

 

Input Breaker Closed

10-12 12:28:16

 

 

 

 

Manual Turn On

 

10-12 12:30:06

 

 

 

 

UPS in Normal Mode

10-22 12:30:16

 

 

 

 

 

 

 

 

 

?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F1

F2

 

F3

F4

HELP

 

 

 

 

 

 

 

 

 

 

Figure 4-5 Primary screen

4.2.3 Default Screen

During UPS operation, if there is neither an alarm nor a keypad operation within two minutes, the default screen will appear, as shown in Figure 4-6. Two minutes later, the LCD backlight will turn off. When an alarm occurs or a key is pressed, the primary screen will return, and the LCD backlight will turn on.

The LCD will also return to the primary screen when pressing any menu key at the default screen.

HIPULSE U

2006-01-01

12:30:36

200kVA-3X3

Unit #1

Normal

 

 

 

 

 

 

Press any key, back to main menu.

F1

F2

F3

F4

HELP

Figure 4-6 Default screen

4.2.4 Help Screen

At the primary screen, use the HELP key to display the help screen, as shown in Figure 4-7. This screen describes current meanings of the menu keys to help you with the menu operation. Pressing the HELP key exits the help screen and returns to the primary screen.

HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual

Page 43