Emerson U /400/S/12P, U/300/S/12P, U/300/S/6P, U /400/S/6P Distance From Floor To Connection Point

Models: U /400/S/12P U/300/S/6P 160 200 U/300/S/12P 400KVA U /400/S/6P

1 79
Download 79 pages 37.39 Kb
Page 29
Image 29
Figure 3-3 Power cable connections for 300/400kVA UPS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Chapter 3 Electrical Installation

19

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Note: For split bypass operation,

注: 如采用分离旁路, ensure that the three horizontal 除旁路和整流器入之busbars (*) between the bypass 三个横向跨接母线*

input and rectifier input are removed.

 

 

 

 

Q5

 

Auxiliary助端子

 

 

 

 

 

terminal线block

X3

 

 

 

 

 

 

Q1

Q2

Q3

 

 

 

 

 

 

 

* *

*

 

 

 

 

 

 

 

 

 

U1 V1 W1

U2 V2 W2 N2

 

N3 U3 V3 W3

 

Battery

整流器

旁路Bypass

 

Output

 

Rectifier

connections

Earth

connections

 

connections

connections

Figure 3-3 Power cable connections for 300/400kVA UPS

3.2 Distance From Floor To Connection Point

The distances from floor to connection points are provided in Table 3-2.

Table 3-2 Distance from floor to connection point

 

UPS

 

 

Minimum distance (mm)

 

 

 

160/200kVA

300kVA

400KVA

 

 

 

 

Rectifier AC input supply

247.5

273

273

 

Bypass AC input supply

247.5

273

273

 

UPS AC output

247.5

267.5

273

 

Battery power

244

300

305

 

Battery control and temperature compensation

325

350

350

 

Ground

247.5

270

274

HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual

Page 29
Image 29
Emerson U /400/S/12P, U/300/S/12P Distance From Floor To Connection Point, 3 Power cable connections for 300/400kVA UPS