9.2.5 Lives And Recommended Replacement Time Of Key Components

Chapter 9 Service & Maintenance

63

9.2.5 Lives And Recommended Replacement Time Of Key Components

The key components listed in Table 9-1 are used in the UPS. To prevent system malfunction caused by failure of key components due to wear and tear during working, you are recommended to check them regularly, and replace them within their life expectancy.

Table 9-1 Lifves and recommended replacement time of key components

 

Key components

 

Life expectancy

Recommended replacement time

 

Recommended check period

 

AC capacitor

 

 

≥7 years (~62,000hr)

5~6 years

 

6 months

 

 

 

 

 

 

 

 

Electrolytic capacitor

 

≥7 years (~62,000hr)

5~6 years

 

1 year

 

Fan

 

 

≥7 years (~62,000hr)

5~6 years

 

1 year

 

Air filter

 

1~3 years

1~2 years

 

3 months

 

Valve-regulated

lead-acid

 

5 years

3~4 years

 

6 months

 

battery ( 5 years of life)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Valve-regulated

lead-acid

 

10 years

6~8 years

 

6 months

 

battery ( 10 years of life)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9.2.6 Replacing Fuses

When replacing the fuse on the high-voltage interface board or the fuse in the fuse box, use a fuse of the same model, avoid being misled by the parameter screenprint on the fuse box.

380V systems can use both 380V/4A fuse and 500V/4A fuse, while 400V/415V systems can use 500V/4A fuse only.

HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual