Chapter 3 Electrical Installation | 23 |
2. Intellislot intelligent communication ports
There are three intelligent communication ports (Intellislot 1, Intellislot 2, and Intellislot 3) available for installing optional SNMP card, UPS JBUS/MODBUS adapter, and relay card.
The serial ports
Table 3-7 Communication port resource deployment table
| Port |
| On the UPS |
| Monitoring devices supported |
| Baud |
| Comments |
|
| LCD screen, under |
|
|
| ||||
|
|
|
| rate |
| ||||
|
|
| Settings, controlled by: |
|
|
|
|
| |
|
|
|
|
|
|
|
|
| |
|
|
|
|
| SNMP card | 9600 |
| Not simultaneous with | |
| Intellislot 2 |
| Comm 1 |
| JBUS/MODBUS adapter |
| Any |
| |
|
|
|
|
| |||||
|
|
|
|
| Relay card |
| Any |
| |
|
|
|
|
|
|
|
| ||
|
|
|
|
| SNMP card | 9600 |
| Not simultaneous with | |
| Intellislot 1 |
| Comm 2 |
| JBUS/MODBUS adapter |
| Any |
| |
|
|
|
|
| |||||
|
|
|
|
| Relay card |
| Any |
| |
|
|
|
|
|
|
|
| ||
|
|
|
|
| SNMP card | 9600 |
| Not simultaneous with | |
| Intellislot 3 |
| Comm 3 |
| JBUS/MODBUS adapter |
| Any |
| |
|
|
|
|
| |||||
|
|
|
|
| Relay card |
| Any |
| |
|
|
|
|
|
|
|
| ||
|
| Comm 1 |
| UPSitePlusTM UPS monitoring software | 9600 | - | |||
|
| Comm 2 |
| Commissioning and service software (only for use by | 9600 |
| Not simultaneous with the | ||
|
|
| authorized commissioning and service personnel) |
| three Intellislot ports | ||||
|
|
|
|
|
|
|
|
3.3.2 Battery Control
The BCB is controlled by the BCB control board. Both are located within the BCB box. This board controls the circuit breaker's undervolts release coil and also provides a path for the circuit breaker auxiliary contacts to signal the circuit breaker status back to the UPS control logic.
All connections between the BCB control board and the UPS module are made through the auxiliary terminal block X3 located on the base of the UPS Cabinet. X3 is shown in Figure
|
|
| X3 |
BCB status feedback | FB |
| 1 |
| |||
GND |
| 2 | |
|
| ||
BCB connection detection | OL |
| 3 |
| |||
+12V |
| 4 | |
|
| ||
Battery temperature sensing 1 | TMP_T |
| 5 |
| |||
GND |
| 6 | |
|
| ||
Battery temperature sensing 2 | LM355+ |
| 7 |
| |||
LM355+ GND |
| 8 | |
|
| ||
BCB drive | DRV |
| 9 |
| |||
DRV_GND |
| 10 | |
|
| ||
Not connected | NC |
| 11 |
| |||
NC |
| 12 | |
|
|
Figure 3-8 Auxiliary terminal block X3
HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual