Chapter 3 Electrical Installation

23

2. Intellislot intelligent communication ports

There are three intelligent communication ports (Intellislot 1, Intellislot 2, and Intellislot 3) available for installing optional SNMP card, UPS JBUS/MODBUS adapter, and relay card.

The serial ports RS232-1, RS232-2, and the Intellislot intelligent communication ports share the same communication resources, as described in Table 3-7.

Table 3-7 Communication port resource deployment table

 

Port

 

On the UPS

 

Monitoring devices supported

 

Baud

 

Comments

 

 

LCD screen, under

 

 

 

 

 

 

 

rate

 

 

 

 

Settings, controlled by:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SNMP card

9600

 

Not simultaneous with

 

Intellislot 2

 

Comm 1

 

JBUS/MODBUS adapter

 

Any

 

 

 

 

 

 

RS232-2

 

 

 

 

 

Relay card

 

Any

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SNMP card

9600

 

Not simultaneous with

 

Intellislot 1

 

Comm 2

 

JBUS/MODBUS adapter

 

Any

 

 

 

 

 

 

RS232-2

 

 

 

 

 

Relay card

 

Any

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SNMP card

9600

 

Not simultaneous with

 

Intellislot 3

 

Comm 3

 

JBUS/MODBUS adapter

 

Any

 

 

 

 

 

 

RS232-2

 

 

 

 

 

Relay card

 

Any

 

 

 

 

 

 

 

 

 

 

RS232-1

 

Comm 1

 

UPSitePlusTM UPS monitoring software

9600

-

 

RS232-2

 

Comm 2

 

Commissioning and service software (only for use by

9600

 

Not simultaneous with the

 

 

 

authorized commissioning and service personnel)

 

three Intellislot ports

 

 

 

 

 

 

 

 

3.3.2 Battery Control

The BCB is controlled by the BCB control board. Both are located within the BCB box. This board controls the circuit breaker's undervolts release coil and also provides a path for the circuit breaker auxiliary contacts to signal the circuit breaker status back to the UPS control logic.

All connections between the BCB control board and the UPS module are made through the auxiliary terminal block X3 located on the base of the UPS Cabinet. X3 is shown in Figure 3-8 and described in Table 3-8.

 

 

 

X3

BCB status feedback

FB

 

1

 

GND

 

2

 

 

BCB connection detection

OL

 

3

 

+12V

 

4

 

 

Battery temperature sensing 1

TMP_T

 

5

 

GND

 

6

 

 

Battery temperature sensing 2

LM355+

 

7

 

LM355+ GND

 

8

 

 

BCB drive

DRV

 

9

 

DRV_GND

 

10

 

 

Not connected

NC

 

11

 

NC

 

12

 

 

Figure 3-8 Auxiliary terminal block X3

HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual

Page 33
Image 33
Emerson 200, U/300/S/12P, U /400/S/12P, U/300/S/6P, U /400/S/6P Battery Control, Communication port resource deployment table