Chapter 4 Operator Control And Display Panel

29

HIPULSE U

 

2006-01-01

12:30:36

 

200kVA-3X3

 

Unit #1

Normal

Main

Bypass

Output

 

 

 

A(AB)

B(BC)

C(CA)

Vphase V

220

220

220

 

Iphase A

20.5

20.5

20.5

 

Freq. Hz

50.1

50.1

50.1

 

Vline V

380

380

380

 

P. F.

0.99

0.99

0.99

 

Input breaker closed

10-12

12:28:16

 

 

 

 

 

 

Manual turn on

10-12 12:30:06

 

 

 

UPS in normal mode

10-22

12:30:16

 

 

 

 

 

 

 

 

 

 

 

 

 

?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F1

F2

F3

F4

HELP

 

UPS System Window

UPS Menu Window

UPS Data Window

Current Record Window

Keypad Window

Figure 4-2 LCD primary screen

4.1.5 Detailed Description Of Menu Items

The description that follows refers to the LCD primary screen shown on Figure 4-2.

System information window

The system information window displays current time and date and identifies the UPS, its configuration and its status. For details, see Table 4-5.

 

Table 4-5 System information window

 

 

 

No.

Item

Explanation

1

HIPULSE U

UPS family name

2

2006-01-01

Current date

3

12:30:36

Current time

4

200kVA-3x3

200kVA: UPS rated output

3 x 3: 3-phase input and output

 

 

 

 

 

 

 

Single: single unit

5

(Configuration) Single, ECO, or Unit # 1

ECO: single unit operating in ECO mode

 

 

Unit # 1: of max 6 units in a parallel system

 

 

 

 

 

Normal: UPS in normal operation, load on inverter, no alarm

6

(Status) Normal, Warning, or Fault

Warning: system attention required

 

 

Fault: serious UPS fault existing

 

 

 

Menu window and UPS data window

The menu window provides the menus of the STS data window. The UPS data window displays the items of the menu selected in the menu window. UPS parameters can be browsed and functions can be set through the menu window and UPS data window. Details are provided in Table 4-6.

Table 4-6 Menu window and UPS data window

No.

Menu

Item

1

Mains

L-L voltage (V)

Frequency (Hz)

 

 

 

 

L-N voltage (V)

2

Bypass

Frequency (Hz)

 

 

L-L voltage (V)

 

 

L-N voltage (V)

 

 

L-N current (A)

3

Output

Frequency (Hz)

 

 

L-L voltage (V)

 

 

Power factor

Explanation

Line voltage

Input frequency

Phase voltage

Bypass frequency

Line voltage

Phase voltage

Phase current

Output frequency

Line voltage

Power factor

HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual