Chapter 1 General Description | 5 |
Auto-restart mode
The battery becomes exhausted following an extended AC mains failure. The inverter shuts down when the battery reaches the
Bypass mode
The load power is supplied though the mains static bypass line. This may be considered as an intermediate operating condition being utilized for the purpose of load transfers between inverter and maintenance bypass or supply under abnormal operating conditions.
Maintenance mode
The UPS is shut down but the load is connected to the unprotected mains through the maintenance bypass supply line.
Source Share mode
The UPS has the capability of fully supporting their critical load while limiting the amount of power taken from the incoming AC mains supply. Any balance of power required is supplied by the UPS battery. This feature is useful, for example, in applications where
ECO mode (for single UPS only)
All power switches and the BCB are closed, the system prefers to put the load on the bypass mains, with the inverter on
Parallel redundancy mode (system expansion)
For higher capacity or higher reliability or both, the outputs of up to six UPS modules can be programmed for directly paralleling while a
Frequency converter mode
The UPS can be programmed into Frequency Converter mode for either 50Hz or 60Hz stable output frequency. The input frequency may vary from 45Hz to 65Hz. In this mode, it is required to open the bypass switch to disable the static bypass operation, and the battery becomes optional depending on any requirement to operate in Battery mode.