Chapter 4 Operator Control And Display Panel

 

Alarm message

 

Description

 

 

 

UPS feeds output voltage back to the mains grill through bypass due to shortcircuit of static switch

 

Byp. feedback fault

 

on bypass side during mains failure. In this case, lack of protective bypass switch or improper

 

 

connection of switch auxiliary contact will endanger the user safety. Special attention should be paid

 

 

 

 

 

 

to this

 

 

 

 

 

INV drive circuit fault

 

Improper connection of inverter drive cable, or equipment type setting error

 

Bypass disconnect

 

Bypass switch closed

 

closed

 

 

 

 

 

 

 

 

Bypass disconnect open

Bypass switch open

 

Maint. disconnect closed

 

Maintenance bypass switch closed

 

Maint. disconnect open

 

Maintenance bypass switch open

 

Output disconnect closed

Output switch closed

 

Output disconnect open

 

Output switch open

 

Check UPS output

The UPS is off and has no output

 

 

 

If the UPS auto-recovery after EOD function is disabled, after UPS shutdown due to battery

 

Output disabled

 

discharge to EOD (end-of-discharge) voltage, when the mains power is restored, the UPS will not

 

 

 

restart automatically, and the LCD will display this alarm message

 

 

 

 

Normal mode

The UPS is in Normal mode

 

Battery mode

 

The UPS is in Battery mode

 

Source share mode

The UPS is in Source Share mode

 

Bypass mode

 

The UPS is in Bypass mode