Chapter 4 Operator Control And Display Panel

Chapter 4 Operator Control And Display Panel

27

Chapter 4 Operator Control And Display Panel

This chapter expounds the functions and use of the components on the operator control and display panel of the HIPULSE U UPS, and provides LCD display information, including the LCD screen types, detailed menu messages, prompt windows and UPS alarm message list

4.1 Introduction

The operator control and display panel is located on the front door of the UPS. The panel is the access point for operator control and monitoring of all measured parameters, UPS and battery status and of event and alarm logs.

The operator control and display panel is divided into three functional areas: mimic power flow chart, graphic LCD monitor with menu keys, control buttons, as shown in Figure 4-1.

 

Graphic LCD monitor

 

Mimic power flow chart

with menu keys

Control buttons

Bypass LED Inverter LED

Rectifier LED

Load LED

Battery LED

HIPULSE U

 

2006-01-01

12:30:36

200kVA-3X3

 

 

Unit #1

Normal

Main

 

Bypass

Output

 

A(AB)

B(BC)

C(CA)

Vphase V

220

 

220

220

Iphase A

20.5

 

20.5

20.5

Freq. Hz

50.1

 

50.1

50.1

Vline V

380

 

380

380

P. F.

0.99

 

0.99

0.99

Input Breaker Closed

 

10-12 12:28:16

Manual Turn On

 

 

10-12 12:30:06

UPS in Normal Mode

 

10-22 12:30:16

?

INVERTER INVERTER

ON OFF

Buzzer

F1

F2

F3

F4 HELP

FAULT

SILENCE

 

 

 

 

CLEAR

ON/OFF

Alarm LED

LCD menu keys

 

 

 

 

 

Figure 4-1 Operator control and display panel

 

 

4.1.1 LED Indicators

The six LEDs mounted on the mimic flow chart represent the various power paths of the UPS, and indicate the current UPS operational status and alarm status by color (red, green, yellow) and state (ON, OFF, flashing), as described in Table 4-1.

 

LED

 

State

 

 

 

Steady green

 

Rectifier LED

 

Flashing green

 

 

Steady red

 

 

 

 

 

 

OFF

 

 

 

Steady green

 

Bypass LED

 

Steady red

 

 

 

OFF

 

 

 

Steady green

 

Battery LED

 

Flashing green

 

 

Steady red

 

 

 

 

 

 

OFF

 

 

 

Steady green

 

Inverter LED

 

Flashing green

 

 

Steady red

 

 

 

 

 

 

OFF

Table 4-1 Description of LED indicators

Description

Rectifier in normal operation

Input AC normal, but rectifier not operating Rectifier f failed

Rectifier not operating, input ac not available or out of normal range Load on bypass power

Bypass not available, out of normal range or static bypass switch fault Bypass normal, load not on bypass power

Battery normal, but discharging and powering the load Battery end-of-discharge pre-warning

Battery abnormal (failed, absent or polarity reversed) or battery circuit breaker abnormal Battery and battery circuit breaker normal, battery charging

Inverter normal and powering the load

Inverter ON, starting up, synchronizing, or standing by (ECO mode) Inverter failed

Inverter not operating

HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual