The default setting for the reminders is OFF (disabled). Press Up/Down arrow buttons to select the desired re- minder intervals.
Table 1
Filter and Maintenance Reminders
Buttons to |
| Available Settings and |
Use | Reminder | How to Use |
|
|
|
SETTINGS | FILTER | Total fan run time expressed in |
(1st press) |
| months (Off, 1, 3, 6, 12); for |
| ||
then Arrows |
| example, if fan runs 12 hours a |
to scroll |
| day, 1 month reminder displays |
selections |
| in 2 calendar months. |
|
|
|
SETTINGS | MAINTE- | Elapsed chronological time in |
(2nd press) | NANCE | months (Off, 6, 12). Use this, |
then Arrows |
| for example, to remind yourself |
to scroll |
| when to perform routine checks |
selections |
| or when to call a technician for |
|
| perodic preventive |
|
| maintenance. |
Enter |
| Stores settings. |
|
|
|
NOTE − The HOME screen will reappear about 15 seconds after the final arrow button press. OR, press the ENTER button at any time to store any changes and exit to the HOME screen.
After either programmed interval has elapsed, the remind- er will be displayed as shown in figure 16.
|
| Reminders | |
PROG | MO | I0:26 | |
AM | |||
A B C D | |||
| |||
HOLD PM |
Service Indicator
When abnormal equipment operation is detected, the SERVICE indicator will flash on the screen (see figure 16). This indicates that the equipment requires service from a qualified service technician.
Thermostat RESET
Under some abnormal conditions, it may be necessary to the thermostat to its default condition. Such a RE-
SET would delete all programming and settings and there- fore should only be used on rare occasions when the the thermostat fails to function as designed and/or as pro- grammed. Such an instance can occur as a result of a pow- er surge or similar electrical disturbance (e.g. after an elec- trical storm or power outage). The RESET button can be used to recover from this situation.
CAUTION
When the RESET button is pressed, ALL settings re- vert back to the defaults, including the default pro- gram (see tables 2 and 3).
The RESET button is an unlabeled, recessed button lo- cated behind the door on the right−hand side of the thermo- stat, below the SETTINGS button (see figure 3). Use a pa- per clip or small pencil to press the RESET button; ALL thermostat settings will be reset to the defaults listed in the Default Thermostat Settings section.
Removing/Installing Thermostat
The thermostat hinges on tabs on the top of the subbase; no tool is needed to remove the thermostat from the sub-
FAN ON
AUTO
FILTER SERVICE
MAINTENANCE
ROOM
76°
COOL
OFF
AUTO
EMG.
HEAT
Filter &
Maintenance
Indicators
base. Pivot the bottom of the thermostat outward (releas- ing the snaps), then lift up to remove.
To replace it, first position the top tilted toward the wall bracket and align it until you feel the tabs and slots engage; then, while the top is in place, pivot the bottom toward the wall until the thermostat snaps into place.
Default Thermostat Settings
FAN ON
AUTO
FILTER SERVICE
MAINTENANCE
ROOM
76°
COOL
OFF
AUTO
EMG.
HEAT
Service
Indicator
Flashing
Default thermostat settings are in table 2 and the default program is shown in table 3.
Table 2
Default Thermostat Settings
Mode | Heat (Perm. Hold) |
|
|
Heat Setpoint (Perm Hold) | 70°F (or 21°C) |
|
|
Cool Setpoint (Perm Hold) | 78°F (or 26°C) |
Figure 16
After the filter has been changed or maintenance per- formed, reset the reminder by pressing the SETTINGS button for 4 seconds at the corresponding reminder set- tings screen. The screen will blink for a few moments to in- dicate that the timer has been reset.
Fan | Auto |
|
|
Filter Reminder | OFF |
|
|
Maintenance Reminder | OFF |
|
|
Equipment Protection Timers | Reset Back to Zero |
|
|
Autochangeover | OFF |
Page 6
505067M 7/13/05