Lennox International Inc 51M37 operation manual Technical Specifications

Models: 51M37

1 54
Download 54 pages 14.47 Kb
Page 45
Image 45
Manual background

Technical Specifications

Thermostat Type

Electronic programmable thermostat for heat pump, 3-stage heat/2-stage cool.

NOTE − 2 stages of heat pump heat and one stage of auxil- iary (gas or electric) backup heat are supported.

Power Supply Range

18VAC − 30VAC (24VAC nominal), 60Hz

Manual background CAUTION

24VAC is present on the terminals of the thermostat bracket. If removing the thermostat from the wall, use caution and avoid touching any of the connec- tor terminals on the wall bracket.

Also, when working with the thermostat dip switches, use a non−conductive tool and take cau- tion to avoid making any contact with the circuit board, its imprinted circuitry and its connector prongs.

Temperature Display

Display Scale: Fahrenheit or Celsius user selectable (via DIP switch; see figure 21)

Display range: 35°F (2°C) to 99°F (37°C)

Display resolution: 1°F (1°C)

Display Accuracy: +/−1°F

If the Fahrenheit/Celsius display must be changed, use a plastic, non−conductive tool to push the dip switch to the right position (see figure 21).

 

Changing Fahrenheit/Celsius Setting

1

 

2

 

3

 

4

 

5

 

6

PLUG IN (Use Care To Avoid Bending Prongs.)

7

 

 

F/C (Fahrenheit/Celsius) switch

 

shown in Celsius position

Figure 21

Indoor Temperature Measurement Range

Measurement Scale: Fahrenheit

Measurement Range: 35°F to 99°F

Measurement Resolution: 0.5°F

Measurement Accuracy: +/−1°F

Field Offset: via DIP switches to +/−3°F

Sampling Method: temperature measurements sampled every 15 seconds. Displayed temperature is the average of the last four measurements.

Outdoor Temperature Measurement Range

Measurement Scale: Fahrenheit

Measurement Range: −22°F to 122°F

Measurement Resolution: 1°F

Measurement Accuracy: +/−2°F

Temperature Setpoint Range

Setting range: 50°F (10°C) to 90°F (32°C)

Setting resolution: 1°F (1°C)

Smart Setback Recovery (via DIP switch #6)

Smart Setback Recovery (SSR) affects the way the ther- mostat responds to program events. If SSR is disabled, the thermostat will react to a program event at the time the event occurs. However, if SSR is enabled, the thermostat will react to a program event before the event occurs such that the desired temperature is reached at the time of the event, not after.

Autochangeover Deadband Selection (via DIP switch #7)

Autochangeover deadband can be set to 4 or 6 degrees. When autochangeover is enabled (via the AUTO button), the thermostat will automatically change over from heating to cooling and vice versa, to keep the room temperature in between the heating and cooling setpoints. The deadband is the minimum difference between the heating and cooling setpoints.

Fan Control

AUTO or ON modes.

I/O Relays

All thermostat relays are latching type to minimize power consumption.

Page 9

51M42 SERIES 5/2

Page 45
Image 45
Lennox International Inc 51M37 operation manual Technical Specifications